Skip to main content
Heliyon logoLink to Heliyon
. 2023 Apr 26;9(5):e15786. doi: 10.1016/j.heliyon.2023.e15786

Simple mathematical models to link climate-based daylight metrics with daylight factor metrics and daylighting design implications

Shuyang Li a, Danny HW Li a, Wenqiang Chen b,, Siwei Lou c, Ernest KW Tsang d
PMCID: PMC10172922  PMID: 37180937

Abstract

Determination of interior daylight illuminance is the key step in daylighting schemes. Recently, climate-based daylight metrics (CBDMs) which considers the real climatic data for the location has been adopted to evaluate the dynamic daylight performance. However, the usual method to calculate the CBDMs is full scale computer simulations which are quite time demanding and designated skills are required. Architects and building practitioners prefer simple methods to assess daylight performance particularly during initial design process when various building schemes and concepts are being appraised. Daylight factor (DF) is the traditional daylight metric and it has a strong relationship with room parameters which can be simply modified to fit the design criteria. This paper puts forward a series of simple mathematical expressions to correlate the CBDMs with DF metrics (DFMs). The vertical outdoor illuminance at the window center point and the 49 interior points were simulated via the RADIANCE software. The results showed that there are strong correlations between these daylight metrics. The proposed approach would be useful to building professionals conducted in visual comfort, fenestration and daylighting design and evaluation in the preliminary design phase.

Keywords: Daylight factor, Useful daylight illuminance, Daylight autonomy, Daylight-linked lighting controls, RADIANCE

1. Introduction

Daylighting is an impressive and sustainable development strategy [1] and design concept is an important issue for the architecture and building research to enhance visual comfort, physical health and green building developments [[2], [3], [4]]. Appropriate daylight-linked lighting controls can substantially save the electric lighting expenditure in commercial buildings [5]. To predict the daylight performance of room spaces and set a scale for architects and building engineers to use when comparing the aspects of various daylighting schemes, there are a number of rules of thumb and design metrics [6]. Traditionally, the daylight factor metrics (DFMs) have been used in evaluating of the interior daylight performance for a long time [7]. Owing to the simplicity, DFMs can be computed by simple equations, figures or several calculation tools [8] which are commonly used among architects and building engineers for conceptual designs and studies [9]. It is adopted by various design manuals [10] for daylighting criteria and widely used in many countries [11]. One of the main strengths is that DFMs are well defined in terms of room variables such as the window area, glazing transmittance and the ratio of window surface to room surface area and the fraction of visible sky [12]. It means that DFMs (under a CIE overcast sky) can represent various room designs which can be conveniently adjusted to fit the daylighting norm. Regression models using input room variables for estimating DFMs are helpful to architects and building engineers at an early design stage [13]. However, DFMs are determined under traditional overcast sky conditions without direct sunlight. In this case, the sky luminance is symmetrical about the zenith and the amount of vertical daylight is identical for all directions. It implies that DFMs are independent of time, non-overcast skies and window orientation [14] which are not the cases especially under clear skies. Large DFMs indicate well daylit space with few artificial lighting demands only, while the visual discomfort such as daylight glare cannot be identified.

Recently, climate-based daylight metrics (CBDMs) containing daylight autonomy (DA) and useful daylight illuminance (UDI) are employed for providing further information on the different daylight conditions throughout the year [15,16]. Such daylighting metrics concern the hours of actual work and real weather conditions for a given place to provide a significant functional account of authentic daylighting environments, which are appropriate for evaluating luminous comfort [17], glare issues [18] and daylight-linked lighting control systems [19,20]. To obtain results that are close to potential actual daylight situations, lighting simulations are the appropriate approach [21]. Nowadays, the advances in computer tools are quite promising, which enable building practitioners to explore daylighting design methodologies more accurately and efficiently. Architects and designers are therefore should evolve towards and familiar with the use of such simulation tools. However, performing full-scale hour-by-hour computer simulation of an entire year is laborious and expensive, as it requires modelling a building geometry over a long simulation period and the use of lengthy input and post-processes. Similarly, parametric analyses for individual building projects are also a laborious undertaking [18,22,23], as the total number of illuminance values that need to be simulated could be close to 12 million [15]. Such sophisticated computational and simulation techniques are difficult for novice students [24] and some building professionals to use [25,26] and typically require expert management [27]. Currently, some studies initiated the link of CBDMs including DA and spatial daylight autonomy (sDA) with DFMs [28,29] but no simple mathematical models are recommended. Lo Verso et al. [22] developed a set of mathematical models to estimate various DA and energy demand for lighting in the early design stages. However, the large sets of input variables in terms of architectural features of building lead to quite complex mathematical expressions and uncertainties. Setting the working period for calculating CBDMs is a major challenge, as although a fixed daytime period may be appropriate for locations near the equator (with small daylength variations throughout a year), it is not appropriate for locations closer to the poles with large daylength differences between summer and winter, which makes it very difficult to set the working period for the latter locations.

Recently, more simple design tools such as simplified geometry maps, regression equations and charts developed through thorough examination using sophisticated simulation tools [[30], [31], [32]] and these are now adopted in the initial planning phase of a project, before overarching design schemes have been finalized. Subsequently, full-scale computer simulation can be conducted to obtain more detailed and accurate findings. This paper attempts to correlate various CBDMs with traditional DFMs (under the CIE Overcast Sky) for buildings facing different directions, where the CBDMs are generated by the simulation software RADIANCE. Ultimately, CBDM can properly be estimated by the room parameters which are simple and fast calculation tools, attaining appropriate architectural and daylighting designs. The performance of daylight-linked lighting controls and visual comfort in terms of daylight glare are evaluated, and the design implications are expounded.

2. Daylight metrics

The daylight metrics being studied here include the DFMs and the latest CBDMs. Generally, there are three forms of DFMs viz. point daylight factor (PDF), average daylight factor (ADF) and vertical daylight factor (VDF). The CBDMs mainly consist of daylight autonomy (DA), continuous daylight autonomy (cDA), maximum daylight autonomy (mDA), spatial daylight autonomy (sDA) and useful daylight illuminance (UDI). This section reviews these daylight metrics covering their main features, merits and limitations.

2.1. Daylight autonomy

DA was originally proposed by the Association Suisse des Electricians in 1989. Later, Reinhart and Walkenhorst redefined the total natural lighting percentage for DA as a dynamic lighting evaluation indicator [33]. DA is expressed as the percentage of daylight hours for a given point in a space above a specified illumination level in a whole year. It takes geographic location and specific weather information into account on an annual basis. Users are free to set the threshold above which DA is calculated. It means that DA could be used to estimate the lighting energy saving under standard daylight-linked on-off lighting controls [34]. However, DA cannot reflect excessive indoor daylight, mDA was proposed to solve this issue [35]. The threshold of mDA is usually ten times the design illuminance of a space. This upper threshold criterion is appropriate to measure the appearance of direct sunlight or other glare conditions. The mDA could provide an indication of the frequency and location for large illuminance contrasts for a given space [36].

Reinhart et al. proposed cDA which is the basic modification of DA [37]. The cDA represents the percentage of occupied hours during the year when the illuminance of a particular point in the room is at or above the target threshold level, with proportional credit given for cases if its daylight contribution meets this level partially. For example, if the value of daylight illuminance is 250 lux at an interior grid point, DA500 lux would give it 0 point whereas cDA500 lux would give it 250/500 = 0.5 point. This daylight metric will help estimate the energy savings by dimming or multistage switching controls. DA and cDA, however, can only evaluate the performance of indoor daylighting environment for a particular point rather than an area. The sDA describes the amount of sufficient daylight received by a given space [38]. Specifically, it describes the percentage of floor area that exceeds a specified illuminance level (e.g., 500 lux) for a standard percentage (e.g., 75%) of the annual occupied hours (e.g., from 8 a.m. to 4 p.m.). sDA500/75% represents the specified illuminance of 500 lux and the standard percentage of 75%. The Illuminating Engineering Society (IES) guideline recommends two different levels for sDA: the first level is preferred daylight sufficiency, if more than 75% of the analysis area meet the above criteria; the second level is nominally accepted daylight sufficiency, if 55% or more of the analysis area meet the above criteria [27]. The Leadership in Energy and Environmental Design (LEED) awards Credit Points 1, 2 and 3 to the sDA300/50% for the regularly occupied floor area at least 40%, 55% and 75%, respectively [39]. The sDA can well reflect the indoor daylight uniformity, while it cannot evaluate the visual glare issue. Uribe et al. used sDA to evaluate those louvers with 120 mm spacing and 5%–20% perforations could meet sDA300/50% between 96% and 100% [40]. DA, mDA, cDA and sDA are not limited to the overcast sky conditions. If the dynamic variations of sky brightness distribution throughout the year is considered, the natural lighting quality of indoor space in a year can be evaluated more accurately.

2.2. Useful daylight illuminance

Nabil and Mardaljevic proposed the UDI in 2005 [41]. For each point in the room, the UDI indicates the percentage of occurrence for a point with its daylight illuminance higher than 100 lux and lower than 2000 lux. Daylight illuminance below the lower threshold (e.g., 100 lux) gives few useful assistances in the perception of the visual environment or performance of visual tasks. Daylight illuminance higher than the maximum threshold (e.g., 2000 lux) may produce visual or thermal discomfort. The UDI scheme reflects the distributions of annual daylight level by determining the occurrence of daylight illuminances within the upper and lower thresholds, indicating whether the indoor daylight is insufficient, desirable, tolerable, and excessive. However, there is some debate about the choice of 2000 lux as an ‘upper threshold’ above which daylight is not required due to potential glare or overheating. For example, LEED V4.1 option 2 adopts the illuminance levels between 300 lux and 3000 lux. Lu et al. [42] used the area-weighted average UDI to prove that the optimized curved facades can improve the daylight efficiency of office building, and Hong et al. used UDI 300–3000 lux to evaluate the performance of thermos-chromic glazing window. They reported that UDI 300–3000lux for single- and double-glazed windows were 70.9% and 71.9%, respectively [43].

2.3. Daylight factor metrics

DFs can be logically estimated through simple calculation aids [9] without the use of the actual daylight data. PDF is defined as the ratio of daylight illuminance at a point on the indoor working plane to simultaneous outdoor illuminance on a horizontal plane (EHD) from an unobstructed hemisphere of CIE standard overcast sky. It has been reported that PDF can be adopted in estimating of energy reduction in electric lighting [44]. ADF represents the daylight sufficiency for interior area rather any specific point [45]. Compared with PDF, ADF is closely related to the room parameters and do not require detailed data. It could be used in the sketch design stage [46]. Both PDF and ADF are the summation of sky component, externally reflected component and internally reflected component. VDF consists of light from the sky and daylight reflected from opposite buildings and the ground to the vertical surface. It has been appropriately used to quantify the daylighting performance for compact city regions with vast external obstructions [47], such as Hong Kong [48]. As daylight passes into internal space via window openings, VDF is the sum of the two daylight configuration factors above (C) and below (D) horizon of the daylight flux incident on the mid-height of windowpane.

3. Model and methodology

The data for the correlations can be generated using computer simulation techniques with examples. The model under study is a simple rectangular room of 6 m (m) x 5.4 m (L) x 3 m (H) containing a vertical rectangular window that represents a common case. The room model conforms to the current Standard for design of office building [49]. The reflectance coefficients of ceiling, wall and floor are 0.6, 0.5 and 0.2, respectively. Totally, 49 reference points were adopted to demonstrate the proposed approach. The spacing between the reference points was 0.75 m and the height was 0.8 m above the floor. Fig. 1 presents the layout of the room and the points for simulating the daylight illuminance. The vertical window was considered facing the four cardinal orientations (i.e., N, E, S and W). The window area and the visual transmittance were varied to form different situations for the 49 internal points (Table 1). Unobstructed skies were considered, and such sky conditions are appropriate for rooms at upper floors of high-rise buildings located in compacted areas or houses constructed in low-density cities. Ultimately, the outdoor illuminance transmitted via the center point of the window was also simulated for analysis. The room layout is a simple shoebox model which represents a typical open-plan office, and the findings can be generalisable to a range of applications during early design stage. Such simple ‘shoebox’ model rooms are commonly adopted to demonstrate and evaluate daylighting performance in terms of DFM and CBDM [27,30,31,37,41,46,50].

Fig. 1.

Fig. 1

Room layout and reference points.

Table 1.

Window area and visual transmittance for the simulation.

Cases Window area (m2) Window transmittance
1 4 0.3
2 6 0.4
3 6 0.6
4 8 0.6
5 9 0.65

Direct sunlight and sky-diffuse illuminance measured from January to December 2004 in Hong Kong were used for the simulation task. The selected daytime for the study were between 8:00 and 16:00 in True Solar Time. The vertical outdoor illuminance at the window center point and the 49 interior points were simulated via the RADIANCE software that was developed by Lawrence Berkeley Laboratory [51]. RADIANCE is a well-established lighting simulation package employing backward ray-tracing technologies to examine high-ranking lighting regimes. It has been used by a number of researchers for predicting outdoor illuminances and solar radiation [52], indoor daylighting and evaluating lighting and daylighting technologies [53,54]. The primary advantage of RADIANCE is only a few limitations on geometry and the many materials may be simulated. In the present study, the RADIANCE version 5.3 running under a Windows 10 workstation was used for the analysis. The simulation accuracy of Radiance software settings are as follows: -ab = 3, -aa = 0.15, -ar = 64, -ad = 512 and -as = 64. The simulation steps and the program used in each calculation step are illustrated in Table 2.

Table 2.

Simulation steps and program.

Step Command Explanation
1 Genbox Create the room model based on the parameters in Table 1 and Fig. 1.
2 Gensky Define the 15 CIE Standard Sky Types based on Tregenza's model [55].
3 Oconv Arguments all material and scene files
4 Rtrace Trace specific rays to find out the illuminance.

4. Results analysis and design implications

The absolute daylight illuminance at all reference points were simulated by RADIANCE. Accordingly, DFMs were calculated by dividing the daylight illuminance to the corresponding EHD under the CIE Sky 1 [56]. The VDF is calculated at the center point of the window, PDF is the value of 49 points inside the room and ADF is the mean value of the PDF of these 49 points. The DAs and UDI were obtained based on the year-round indoor daylight illuminance simulation. As DFMs are constants under traditional overcast sky condition, their correlations with UDI and DAs should be with respect to the CIE Sky 1. Therefore, DFMs can represent various room designs which are useful for building façade and daylighting design.

4.1. Correlations between dynamic daylight metrics and point daylight factor

The correlations between PDFs (under Sky 1) and DA at the indoor illuminance thresholds of 100, 300 and 500 lux when the window facades facing the four cardinal orientations (i.e., N, E, S and W) under unobstructed skies are shown in Fig. 2(a–f).

Fig. 2.

Fig. 2

Correlation between point daylight factor and daylight autonomy for the three indoor illuminance thresholds (a) 100 lux; (b) 300 lux; (c) 500 lux facing north; (d) 500 lux facing east; (e) 500 lux facing south; (f) 500 lux facing west.

The figure can give a convenient way to demonstrate the DA under different PDFs. No substantial orientation effects can be observed for DA100 and DA300 since daylight illuminance below 500 lux which is mainly sky-diffuse component without direct sunlight for all orientations. Through regression analysis, the model equations correlating DA with PDF were developed and the findings including R2 are expressed as Eqs. (1), (2), (3), (4), (5), (6):

DA100lux=101.714.54×PDF1.13R2=0.98 (1)
DA300lux=127.276.56×PDF0.48R2=0.92 (2)
DA500luxN={0,PDF<0.8%120.9117.8×PDF0.66,PDF0.8%R2=0.96 (3)
DA500luxE=414.3387.3×PDF0.08R2=0.93 (4)
DA500luxS=194.3159.6×PDF0.22R2=0.95 (5)
DA500luxW=247.7216.2×PDF0.16R2=0.92 (6)

As the indoor illuminance thresholds are usually no more than 500 lux, large DAs can be resulted at relatively low PDFs. These plots also indicate diminishing return for PDF up to 2% or more. As the illuminance threshold increases from 100 to 500 lux, the lowest DA100 lux of 22% reduces to 0% for DA500 lux. It means that at very small DF, 22% of the daytime period for the given point can take a daylight level higher than 100 lux, but it can never be more than 500 lux. Initially, DA100 lux rises rapidly to around 90% with PDF of about 1.2%. Afterwards, DA100 lux increases slightly and becomes the full value of 100% when PDF > 6%. Similar patterns can be found for DA300 lux which reach 90% with the corresponding PDF at 4.2%. With the increase of PDF, DA500 lux is significantly different in four orientations. The DA500 lux values in the south and west are larger than those in the north and east when the PDF is in the range between 1% and 4%. The R2s are more than 0.92, showing that over 92% variations of DA can be explained by the changes in PDF and the correlations are considered very strong. It indicates that the mathematical models can provide a reliable way to estimate the DA from the PDF.

Similarly, the cDA data were determined and correlated with the corresponding PDF under Sky 1. Fig. 3(a–f) presents such correlations between PDF and cDA for the interior illuminance thresholds of (a) 100, (b) 300 and (c) 500 lux.

Fig. 3.

Fig. 3

Correlation between point daylight factor and continuous daylight autonomy for the three indoor illuminance thresholds (a) 100 lux; (b) 300 lux; (c) 500 lux facing north; (d) 500 lux facing east; (e) 500 lux facing south; (f) 500 lux facing west.

Since daylight illuminance below the threshold will also be counted as a credit in the cDA which is generally greater than DA for all cases. Using regression analysis, the correlation equations and regression statistics were computed and are depicted in Eqs. (7), (8), (9), (10), (11), (12).

cDA100lux=100.85.72×PDF1.23R2=0.98 (7)
cDA300lux=105.929.04×PDF0.79R2=0.96 (8)
cDA500luxN=12973.09×PDF0.42R2=0.95 (9)
cDA500luxE=121.561.54×PDF0.46R2=0.96 (10)
cDA500luxS=114.249.27×PDF0.55R2=0.98 (11)
cDA500luxW=116.753.16×PDF0.52R2=0.96 (12)

The R2 is 0.96 or more, indicating a strong relation that correlates cDA to the PDF accurately. The PDFs are 0.6%, 1.9% and 3.4% respectively for cDA100 lux, cDA300 lux and cDA500 lux at around 90%.

Daylighting is an important and useful strategy for reducing the electricity consumption by switching-off the light fittings when the daylight lux levels are appropriate. In a well day-lit space when the available daylight is far larger than the required level, daylighting can provide substantial energy savings when proper daylight-linked lighting controls are adopted. However, such circumstance may cause glare and brings about visual discomfort. DA and cDA are quite appropriate for predicting the electric lighting saving due to standard daylight-linked switching and dimming lighting controls, respectively. Assuming that there are three rows of luminaries parallel to the window façade are separately monitored (neglect the electric lighting) and Points 11, 25 and 39 on Fig. 1 are the locations to detect the illuminance for Rows 1, 2 and 3, respectively. Accordingly, the PDFs, annual daylight illuminance, DA and cDA for the three points representing the 3 rows were determined. If the installed lighting power density was 20 W/m2, the annual electric lighting energy consumption (E) for switching or dimming controls can be calculated by Eq. (13):

E=(1DAorcDA)×A×LPD×h (13)

where A is the room area, m2; LPD is the lighting power density; h is the annual work hours.

Table 3 summaries the percentage of electric lighting consumption under standard on-off and dimming controls for the three rows based on Case 1. As cDA is always larger than DA, dimming control is more efficient than the simple on-off control. The annual electric lighting energy consumption for switching controls can range from 71 to 329 kWh under various numbers of lamp fittings monitored and window orientations. The outcomes can give a convenient alternative to predict the electric lighting savings. It is envisaged that more energy reduction can be achieved due to less of heat dissipation from artificial light and thus a smaller internal cooling load.

Table 3.

Electric lighting energy consumption under different daylighting controls at three zones with the target illuminance = 500 lux.

Daylighting controls (Case 1) Row 1: sensor location Point 11
Row 2: sensor location Point 25
Row 3: sensor location Point 39
N E S W N E S W N E S W
Standard switching control E (simulated DA) 108 96 71 76 328 284 262 271 329 327 326 323
Eqs. (3), (4), (5), (6) (modelled DA) 93 113 83 90 313 238 212 223 329 329 328 329
Diff. 14 16 11 14 15 46 50 48 0 3 2 7
Dimming control E (simulated cDA) 39 37 29 29 184 154 132 139 260 240 226 228
Eqs. (9), (10), (11), (12) (modelled cDA) 43 40 32 33 143 130 113 118 254 234 217 222
Diff. −4 −2 −3 −4 41 25 18 21 6 6 9 6

Note: E is annual electric lighting consumption (kWh); Diff. is the difference between modelled and simulated annual electric lighting consumption.

If PDF under CIE Sky 1 is known, DA500 lux and cDA500 lux can be calculated by Eqs. (3), (4), (5), (6), (9), (9), (10), (11), (12). It is easily to get the electric lighting energy usage under different daylight-linked lighting controls. The results of electric lighting consumption are shown in Table 3. The difference at three points is not more than 50 kWh indicating that the proposed model can be used in the initial design of building schemes.

The correlation between mDA and PDF was made and the plots of mDA 2000 lux against PDF facing the four cardinal orientations (i.e., N, E, S and W) are presented in Fig. 4(a–d). The mDA indicates a visual glare issue with an intolerable indoor daylighting condition. The graph also gives prominence to the differences that appear with orientation. When PDFs are less than 1.1%, the interior daylight illuminance is less than 2000 lux (mDA 2000 lux = 0) for the room facing east, south and west orientations. For north facing room, the PDFs can be lower than 4%. Also, at the mDA 2000lux of 10%, the PDFs are around 5.6%, 2.9%, 2.6% and 2.4% for north, east, south and west orientations, respectively. Regression analysis was carried out for mDA 2000 lux and PDF and the regression equations including correlation coefficients for the four principal directions are presented in Eqs. (14), (15), (16), (17):

mDAN={0,PDF4%276.6×PDF0.14341.6,PDF>4%,R2=0.99 (14)
mDAE={0,PDF1.1%11.94×PDF0.7216.24,PDF>1.1%,R2=0.96 (15)
mDAS={0,PDF1.1%39.91×PDF0.4147.23,PDF>1.1%,R2=0.98 (16)
mDAW={0,PDF1.1%16.88×PDF0.6420.87,PDF>1.1%,R2=0.96 (17)

Fig. 4.

Fig. 4

Correlation between point daylight factor and maximum daylight autonomy facing four orientations (a) North; (b) East; (c) South; (d) West.

Again, R2 is greater than 0.96, showing that the above equations are appropriate to estimate the mDA.

UDI and the corresponding PDF were analyzed and four bell shape curves for north-, east-, south- and west-facing surfaces are depicted in Fig. 5(a–d). At first, the UDI increases with increasing PDF for individual orientation. When PDF is up to around 2%, a peak UDI ranging from 88% to 96% can be viewed for east, south and west orientations. With considerable daylight illuminance of less than 2000 lux, window facing north has a higher UDI (i.e., 99%) than the other vertical directions. As PDF subsequently rises from 2% to 20%, resulting more daylight illuminance over 2000 lux and the UDI drops gently. Large daylight illuminance may cause visual glare. It is interesting to note that PDF just between 2 and 4% would be an appropriate criterion which has been widely adopted by many countries [11].

Fig. 5.

Fig. 5

Correlation between point daylight factor and useful daylight illuminance facing four orientations (a) North; (b) East; (c) South; (d) West.

Likewise, regression analysis was conducted to correlate UDI with PDF. It has been found that UDI are better correlated with PDF by quadratic equations. The mathematical expressions and correlation coefficients are determined as Eqs. (18)–(21):

UDIN={101.715.19×PDF1.22,PDF4%,R2=0.99409.4246.1×PDF0.16,PDF>4%,R2=0.99 (18)
UDIE={100.615.32×PDF1.1,PDF2%,R2=0.98133.323.71×PDF0.54,PDF>2%,R2=0.95 (19)
UDIS={99.5613.15×PDF1.1,PDF2%,R2=0.98257.8140.4×PDF0.19,PDF>2%,R2=0.98 (20)
UDIW={95.89.49×PDF1.3,PDF2%,R2=0.97146.536.03×PDF0.45,PDF>2%,R2=0.94 (21)

With the R2 of more than 0.94, it indicates that the UDI can be accurately calculated by the corresponding PDF. Such issue can help the design of indoor daylight environment quickly reaching the required standard.

4.2. Correlations between dynamic daylight metrics and vertical daylight factor

The correlations between VDF after transmitted to the room interior under Sky 1 and mDA with 2000 illuminance threshold at the center of vertical window for north, east, south and west are shown in Fig. 6.

Fig. 6.

Fig. 6

Correlations between vertical daylight factor and maximum daylight autonomy facing four orientations (t is in the range of 0.2–0.65).

It can be seen that mDA rises with increasing VDF. Containing more amount of sky-diffuse component, the mDA for north- and east-facing surfaces are less than those for south-and west-facing surfaces. When the VDF is 9%, the mDA for north and east directions are around 6% smaller than those for south and west orientations. Through regression analysis, R2 values were found of unity indicating perfect correlations and their correlations are expressed in as Eqs. (22)–(25):

DAmaxN=99.57972.3×VDF1.42R2=1 (22)
DAmaxE=105.4422.2×VDF1.01R2=1 (23)
DAmaxS=108204.8×VDF0.76R2=1 (24)
DAmaxW=100.8504.7×VDF1.21R2=1 (25)

The VDF is a constant of around 47% before transmitted into the room space under an unobstructed Sky 1. It would be easily to vary the window transmittance (change the window type) for getting the transmitted VDF to meet the required mDA.

There are simple correlations between PDF and VDF under all sky conditions [57]. The ratio of PDF to VDF can be computed using a number of room parameters and the configuration factor for a vertical rectangle plane to a horizontal point [24]. Such findings are useful to daylight-linked open-loop lighting controls which can get rid of the influence due to the electric lighting. The primary drawback for closed-loop daylight-linked switching control is the sudden and quite often of lamp fittings turning on and off when the sensed daylight plus electric lighting is merely greater than the illuminance set point. The daylight illuminance monitored at the reference point is the recorded vertical daylight illuminance (VDI) times the ratio of PDF to VDF which is well correlated [57]. Further study for open-loop daylight-linked lighting controls based on such technique will be examined in near future.

Daylight glare probability (DGP) is a simplified method for glare evaluation [58]. There are four subjective perception levels for DGP ‘< 35% imperceptible’, ‘35%–40% perceptible’, ‘40%–45% disturbing’ and ‘> 45% intolerable’. Equation (26) presents the mathematical expression for calculating the DGP.

DGP<6.22×105×EV+0.184 (26)

where EV is the vertical illuminance at eye, lux.

Accordingly, the DGPs at the center point of window for the whole year were computed by substituting the transmitted VDI (excluding direct sunlight) into EV. Fig. 7(a–d) displays the frequency of occurrence (FOC) for the four perception levels against the VDF (under Sky 1) facing various orientations.

Fig. 7.

Fig. 7

Correlation between vertical daylight factor and daylight glare probability (t is in the range of 0.2–0.65) facing four orientations (a) North; (b) East; (c) South; (d) West.

For the four orientations, the ‘imperceptible’ drops with VDF but an opposite trend for ‘intolerable’ can be observed. For the other two perceptions, they vary slightly with VDF. Regression analysis was carried out and the mathematical expressions including the R2 are summarized in Table 4. The R2 values for ‘imperceptible’ and ‘intolerable’ equations are close to unity, representing excellent correlation. The R2 for ‘disturbing’ and ‘perceptible’ is in the range of 0.93–1, still denoting a very good correlation. The VDF, therefore, can be used for predicting various daylight glare perceptions. The results also reveal the effects due to orientation. For a given VDF, the FOC of ‘imperceptible’ perception for windows facing north and east is larger than that facing south and west. When VDF is 14%, the FOC of ‘imperceptible’ perception for the glazing facing north, east, south and west are 41%, 38%, 28% and 32%, respectively. To limit the visual glare, the ‘imperceptible’ perception should be the majority. To achieve the FOC of more than 40% for ‘imperceptible’ perception, the VDFs should not be more than 11% for the four orientations. In order to accomplish such small VDF under unobstructed skies, shading devices such as overhang, side-fin and recessed glazed opening with vertical louvres [50,59] may be the appropriate approach and further study will be carried out.

Table 4.

Equations for the relationship between vertical daylight factor and daylight glare probability.

Orientation DGP Equation R2
North <35% 0.19 × VDF2 – 10.31 × VDF + 150.6 0.99
35%–40% – 0.022 × VDF2 + 0.21 × VDF + 18.69 0.93
40%–45% 0.0078 × VDF3 − 0.52 × VDF2 + 10.74 × VDF − 53.02 0.97
>45% −0.32 × VDF2 + 15.77 × VDF − 115.5 0.98
East <35% 0.13 × VDF2 − 7.14 × VDF + 114.9 1
35%–40% 0.0014 × VDF2 − 0.5 × VDF + 19.91 0.99
40%–45% −0.02 × VDF2 + 0.59 × VDF + 7 0.93
>45% −0.23 × VDF2 + 11.86 × VDF − 73.04 0.97
South <35% 0.11 × VDF2 − 6 × VDF + 92.75 0.99
35%–40% 0.026 × VDF2 − 1.58 × VDF + 28.08 1
40%–45% 0.014 × VDF2 − 1.03 × VDF + 22.69 1
>45% −0.15 × VDF2 + 8.6 × VDF − 43.52 1
West <35% 0.14 × VDF2 − 7.46 × VDF + 111.3 0.99
35%–40% 0.014 × VDF2 − 1.16 × VDF + 26.92 0.99
40%–45% −0.014 × VDF2 + 0.13 × VDF + 13.1 0.95
>45% −0.14 × VDF2 + 8.5 × VDF − 51.29 1

4.3. Correlation between spatial daylight autonomy and average daylight factor

The correlations between ADF (under Sky 1) and sDA of various occupied space areas (30%, 50%, 70% and 80%) with three illuminance thresholds (100 lux, 300 lux and 500 lux) facing the four cardinal orientations (N, E, S & W) are shown in Fig. 8(a–c). Several important aspects can be noticed. Except north orientation, the sDA100 lux 30% is close to 100%. It means that sDA with low occupied space area and illuminance thresholds is generally independent of the ADF and orientation. When the analysis area and illuminance threshold increase, the sDA can be reduced from 100% to around 10% (sDA500 lux 80%). The sDA for room facing north and east is generally less than that facing south and west. LEED v4.1 regards the sDA300 lux 50% as the scoring criteria for daylight performance. As shown clearly in Fig. 8(b), sDA300lux 30% and sDA300lux 50% are 100% when ADF is more than 4%. It indicates that sDA can only reflect indoor daylighting requirement but cannot evaluate whether indoor daylighting is excessive and may cause visual discomfort. The sDA values can be predicted by corresponding ADFs. For instance, the sDA500 lux 30% with the window wall facing south is 70% when the ADF is 3%. It means that appropriate sDA criteria can be obtained from the corresponding ADF. Based on the data shown in the figure, the range of daylight illuminance for the area concerned can also be specified. The sDA100 lux 30% also implies no daylight illuminance is less than 100 lux when the window facing south. It can be deduced that for 30% of the floor area of the room facing south there is 30% of the annual occupied hours with the daylight illuminance ranging between 100 lux and 500 lux when the ADF is 3%. Such analysis would be important to daylight distribution and uniformity.

Fig. 8.

Fig. 8

Fig. 8

Fig. 8

Correlations between average daylight factor and spatial daylight autonomy with three illuminance thresholds (a) 100 lux; (b) 300 lux; (c) 500 lux.

4.4. Design implications

The CBDMs including DA, cDA, mDA, sDA and UDI are appropriate to evaluate visual performance, indoor daylight distribution, daylight glare and daylight-linked lighting controls. However, the usual method for estimating these CBDMs is to employ sophisticated computer simulation packages containing long-term prevailing weather files. Full-scale computer simulations can be quite complex, costly and time demanding in making the building configurations and running simulations. Sophisticated techniques are required for dealing with pre- and post-processing. Such complicated and advanced simulation software would be appropriately used by a specialist or skillful user [27]. Simple calculation aids formulated via in-depth examination are commonly used by building practitioners particularly in the preliminary design period when various design options and architecture schemes are considered and assessed. Apart from daylight availability, building façade also involves thermal aspect such as the heat gain and loss through the external walls, and the performance of building integrated solar electric and solar thermal. Detailed simulations analysis can be carried out to get subsequent precise findings after all these issues are finalized and the estimated outcomes can be adopted to check with the simulated results. This study demonstrates that such CBDMs are well correlated with DFMs namely PDF, VDF and ADF under the traditional CIE Standard Sky 1. It means that the required criteria in terms of DA, cDA, mDA, sDA and UDI can be easily obtained from the corresponding DFs. The key strength is that the three types of DFMs (i.e., PDF, VDF and ADF) are highly linked with fraction of visible sky and room variables, especially the window area and visual transmittance. There are many simple calculation tools and design aids to determine the DFMs based on these room parameters [10,45] and sky luminance distributions under the traditional CIE Overcast Sky [7]. It could be easily to change the size of these parameters to satisfy the criteria. Previously, a number of studies reported that the CIE Overcast Sky performed the best among many worldwide models adopted in places of various climates under overcast conditions [[60], [61], [62]]. Outdoor illuminance for a particular site is mainly affected by the solar positions and its own sky conditions such that sky-diffuse and direct sunlight datasets are different from one place to another. There may be too many variables for predicting the CBDMs and only the most influencing input factors should be adopted. The CBDMs for a given place may not be accurately predicted from individual input data using a general mathematical model. Using DFMs (i.e., room parameters + fraction of visible sky) as the input data can eliminate such effects. To achieve the LEED [39] ratings system for a 3-point credit, the sDA300lux 50% is 75% for a regularly occupied floor area. Based on Fig. 8b, this would be met by an ADF of 2.7% in a south-facing room in Hong Kong. Using the Longmore model [45], the correct daylight configuration factors above (C) and below (D) horizon (under unobstructed and obstructed CIE Sky 1) and the room parameters can be determined for use in initial daylighting designs. Thus, the corresponding VDF (i.e., C + D) can be computed and then the mDA can be obtained from Fig. 6. Subsequently, the PDFs at various interior grid points will also be found using the sky component table for CIE Sky 1 and a simple equation to determine the internally reflected component [7]. Ultimately, the DA, cDA, mDA and UDI for the corresponding interior points can be predicted based on Fig. 2, Fig. 3, Fig. 4, Fig. 5c, respectively. In addition, the DGP for the four subjective perception levels can be reckoned from Fig. 7. After this initial design scheme has been confirmed, full-scale building simulations will be conducted to get precise outcomes, such as CBDMs. The cases for analysis, however, did not include the use of external shading devices which are appropriate to lower the excessive daylight for rooms located at the top floors of high-rise buildings facing unobstructed skies. Further research studies to compute the amount of daylight reduced by overhang, side-fin and recessed window [50,59] will be conducted soon. To enhance the generalizability and representativeness of the proposed approach, locations with different climates obtained from accessible websites [63] will be examined later.

5. Conclusions and discussions

Correlations between various CBDM including DA, cDA, mDA, sDA and UDI with DFMs under the CIE Overcast Sky (Sky 1) with window wall facing north, east, south and west were established. All the data were obtained via the same software RADIANCE. Generally, all the modelled equations are strongly correlated, indicating that different forms of DA and UDI can be computed from the corresponding DFMs. Accordingly, using the findings in DA and cDA, the lighting energy consumption under standard daylight-linked lighting on-off and dimming controls were computed. Peak UDIs range from 88% to more than 99% when PDFs are between 2% and 4%. Such findings are well agreed with DFMs criteria adopted by many countries. sDA can denote the indoor daylight distribution and uniformity. ADF was employed to correlate with sDA for various occupied room areas at different daylight thresholds. The correlations are useful to obtain proper daylight distributions from a particular room daylighting scheme (i.e., ADF). Further, the frequency of occurrence for the perception levels of DGP were calculated and correlated with VDF. Lower the VDF at the vertical window can allow less ‘distributing’ and ‘intolerable’ perceptions. The present study takes Hong Kong as an example and considers the typical room facing the four cardinal directions under unobstructed skies. Further work will deal with more orientations under unobstructed and obstructed sky conditions and other places with their representative weather files containing sky diffuse and direct sunlight data.

Author contribution statement

Shuyang Li: Conceived and designed the experiments; Performed the experiments; Analyzed and interpreted the data; Wrote the paper.

Danny H W Li: Conceived and designed the experiments; Analyzed and interpreted the data; Wrote the paper.

Wenqiang Chen: Analyzed and interpreted the data; Contributed reagents, materials, analysis tools or data.

Siwei Lou, Ernest K. W. Tsang: Contributed reagents, materials, analysis tools or data.

Data availability statement

The authors do not have permission to share data.

Acknowledgements

Work described was fully supported by a Faculty Development Scheme from the Research Grant Council of HKSAR [Project No. UGC/FDS16/E03/20].

Abbreviations

ADF

Average Daylight Factor

CBDMs

Climate Based Daylight Metrics

cDA

Continuous Daylight Autonomy

CIE

International Commission on Illumination

DA

Daylight Autonomy

DF

Daylight Factor

DFMs

Daylight Factor Metrics

DGP

Daylight Glare Probability

FOC

Frequency of Occurrence

IES

Illuminating Engineering Society

LEED

Leadership in Energy and Environmental Design

mDA

Maximum Daylight Autonomy

PDF

Point Daylight Factor

sDA

Spatial Daylight Autonomy

UDI

Useful Daylight Illuminance

VDF

Vertical Daylight Factor

VDI

Vertical Daylight Illuminance

References

  • 1.Vaisi S., Kharvari F. Evaluation of Daylight regulations in buildings using daylight factor analysis method by radiance. Energy Sustain. Dev. 2019;49:100–108. [Google Scholar]
  • 2.Xue P., Mak C.M., Cheung H.D. The effects of daylighting and human behavior on luminous comfort in residential buildings: a questionnaire survey. Build. Environ. 2014;81:51–59. [Google Scholar]
  • 3.Dong Y., Zhang X. Investigation of the effects of awakening daylight on the morning alertness, mood, and sleep quality of male college students. Build. Environ. 2020:180. [Google Scholar]
  • 4.Yener A.K. Daylight analysis in classrooms with solar control. Architect. Sci. Rev. 2002;45(4):311–316. [Google Scholar]
  • 5.Doulos L., Tsangrassoulis A., Topalis F. Quantifying energy savings in daylight responsive systems: the role of dimming electronic ballasts. Energy Build. 2008;40(1):36–50. [Google Scholar]
  • 6.Nigra M., et al. ‘Re-coding’ environmental regulation – a new simplified metric for daylighting verification during the window and indoor space design process. Architect. Eng. Des. Manag. 2021:1–24. [Google Scholar]
  • 7.Hopkinson R.G., Petherbridge P., Longmore J. Heinemann; London: UK: 1966. Daylighting. [Google Scholar]
  • 8.Carlos J.S. A simple method to determine the daylight factor from the vertical daylight factor in different stree canyon geometry. J. Green Build. 2016;8(1):58–69. [Google Scholar]
  • 9.Aizlewood M.E., Littlefair P.J. 1996. Daylight prediction methods: a survey of their use; pp. 126–140. (Proceedings of the CIBSE National Lighting Conference). Bath, UK. [Google Scholar]
  • 10.CIBSE . CIBSE; London, UK: 1997. Code for Interior Lighting. [Google Scholar]
  • 11.Hraska J. Brno University of Technology; Czech Republic: 2011. Criteria of daylighting and sunlight access in sustainable construction evaluation systems; pp. 98–103. (Proceedings of the 5th International Conference on Solar Radiation and Daylighting). [Google Scholar]
  • 12.Tregenza P. Opinion: climate-based daylight modelling or daylight factor? Light. Res. Technol. 2014;46:618. [Google Scholar]
  • 13.Mavromatidis L.E., Marsault X., Lequay H. Daylight factor estimation at an early design stage to reduce buildings' energy consumption due to artificial lighting: a numerical approach based on Doehlert and Box–Behnken designs. Energy. 2014;65:488–502. [Google Scholar]
  • 14.Acosta I., et al. Analysis of daylight factors and energy saving allowed by windows under overcast sky conditions. Renew. Energy. 2015;77:194–207. [Google Scholar]
  • 15.Nabil A., Mardaljevic J. Useful daylight illuminances: a replacement for daylight factors. Energy Build. 2006;38(7):905–913. [Google Scholar]
  • 16.Munoz C.M., et al. Climate-based daylighting analysis for the effects of location, orientation and obstruction. Light. Res. Technol. 2014;46:268–280. [Google Scholar]
  • 17.Xue P., Mak C.M., Huang Y. Quantification of luminous comfort with dynamic daylight metrics in residential buildings. Energy Build. 2016;117:99–108. [Google Scholar]
  • 18.Tabadkani A., Banihashemi S., Hosseini M.R. Daylighting and visual comfort of oriental sun responsive skins: a parametric analysis. Build. Simulat. 2018;11(4):663–676. [Google Scholar]
  • 19.Acosta I., Campano M.Á., Molina J.F. Window design in architecture: analysis of energy savings for lighting and visual comfort in residential spaces. Appl. Energy. 2016;168:493–506. [Google Scholar]
  • 20.Acosta I., et al. Dynamic daylight metrics for electricity savings in offices: window size and climate smart lighting management. Energies. 2018;11(11) [Google Scholar]
  • 21.Navvab M. Opinion: simulation in lighting design and research. Light. Res. Technol. 2014;46(2):92. [Google Scholar]
  • 22.Lo Verso V.R.M., et al. Estimation of the daylight amount and the energy demand for lighting for the early design stages: definition of a set of mathematical models. Energy Build. 2017;155:151–165. [Google Scholar]
  • 23.Pellegrino A., et al. Impact of daylighting on total energy use in offices of varying architectural features in Italy: results from a parametric study. Build. Environ. 2017;113:151–162. [Google Scholar]
  • 24.Li D.H.W., et al. A review of calculating procedures on daylight factor based metrics under various CIE Standard Skies and obstructed environments. Build. Environ. 2017;112:29–44. [Google Scholar]
  • 25.Betman E. Daylight calculations using constant luminance curves. Renew. Energy. 2005;30(2):241–257. [Google Scholar]
  • 26.Jones P.J., et al. Evaluation of methods for modelling daylight and sunlight in high rise Hong Kong residential buildings. Indoor Built Environ. 2016;13(4):249–258. [Google Scholar]
  • 27.Tsagrassoulis A., Kontadakis A., Roetzel A. 2015. Comparing climate based daylight modelling with daylight factor assessment – implications for architects. (The 49th International Conference of the Architectural Science Association). [Google Scholar]
  • 28.Asfour O.S. A comparison between the daylighting and energy performance of courtyard and atrium buildings considering the hot climate of Saudi Arabia. J. Build. Eng. 2020;30 [Google Scholar]
  • 29.Acosta I., et al. Minimum daylight autonomy: a new concept to link daylight dynamic metrics with daylight factors. Leukos. 2019;15(4):251–269. [Google Scholar]
  • 30.Kleindienst S., Bodart M., Andersen M. Graphical representation of climate-based daylight performance to support architectural design. Leukos. 2008;5(1):39–61. [Google Scholar]
  • 31.Petersen S., Momme A.J., Hviid C.A. A simple tool to evaluate the effect of the urban canyon on daylight level and energy demand in the early stages of building design. Sol. Energy. 2014;108:61–68. [Google Scholar]
  • 32.Šprah N., Košir M. Daylight provision requirements according to EN 17037 as a restriction for sustainable urban planning of residential developments. Sustainability. 2019;12(1) [Google Scholar]
  • 33.Reinhart C.F., Walkenhorst O. Validation of dynamic RADIANCE-based daylight simulations for a test office with external blinds. Energy Build. 2001;33:683–697. [Google Scholar]
  • 34.Acosta I., et al. Smart controls for lighting design: towards a study of the boundary conditions. Int. J. Eng. Technol. 2018;10(6):481–486. [Google Scholar]
  • 35.Protzman B. Daylight autonomy welcomes back the sun. Illumination in focus. 2013:20–22. [Google Scholar]
  • 36.Li S., Li D.H.W., Chen W. 2020. A comparative study between Daylight Factor Based Metric and other-Daylight Metrics for Daylighting Design. (The 54th International Conference of the Architectural Science Association (ANZAScA) 2020). [Google Scholar]
  • 37.Reinhart C.F., Mardaljevic J., Rogers Z. Dynamic daylight performance metrics for sustainable building design. Leukos. 2013;3(1):7–31. [Google Scholar]
  • 38.IES . 2012. Approved Method: Spatial Daylight Autonomy and Annual Sunlight Exposure. USA: IES LM-83-12. [Google Scholar]
  • 39.U.S. Green Building Coumcil . 2021. LEED v4.1_Building Design and Construction. [Google Scholar]
  • 40.Uribe D., Bustamante W., Vera S. Potential of perforated exterior louvers to improve the comfort and energy performance of an office space in different climates. Build. Simulat. 2018;11(4):695–708. [Google Scholar]
  • 41.Nabil A., Mardaljevic J. Useful daylight illuminance: a new paradigm for assessing daylight in buildings. Light. Res. Technol. 2005;37(1):41–59. [Google Scholar]
  • 42.Lu S., Lin B., Wang C. Investigation on the potential of improving daylight efficiency of office buildings by curved facade optimization. Build. Simulat. 2019;13(2):287–303. [Google Scholar]
  • 43.Hong X., et al. Multi-objective optimization of thermochromic glazing based on daylight and energy performance evaluation. Build. Simulat. 2021;14(6):1685–1695. [Google Scholar]
  • 44.Leslie R.P., et al. The potential of simplified concepts for daylight harvesting. Light. Res. Technol. 2005;37(1):21–40. [Google Scholar]
  • 45.Longmore J. Daylighting: a current view. Light Light. 1975;68:113–119. [Google Scholar]
  • 46.Lynes J.A., Littlefair P.J. Lighting energy savings from daylight: estimation at the sketch design stage. Light. Res. Technol. 1990;22(3):129–137. [Google Scholar]
  • 47.Ng E. Studies on daylight design and regulation of high residential housing in Hong Kong. Light. Res. Technol. 2003;35(2):127–139. [Google Scholar]
  • 48.Buildings, Department . 2015. Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-130, Lighting and Ventilation Requirements-Performance-Based Approach. [Google Scholar]
  • 49.MOHURD JGJ/T 67-2019 . MOHURD; Beijing: 2019. Standard for Design of Office Building. (In Chinese) [Google Scholar]
  • 50.Tregenza P.R. Modification of the split-flux formulae for mean daylight factor and internal reflected component with large external obstructions. Light. Res. Technol. 1989;21(3):125–127. [Google Scholar]
  • 51.Ward G.L., Shakespeare R. Morgan Kaufmann; Los Altos, CA: 1998. Rendering with RADIANCE. The Art and Science of Lighting Visualization. [Google Scholar]
  • 52.He Y., et al. Modeling solar radiation on a human body indoors by a novel mathematical model. Build. Environ. 2021:187. [Google Scholar]
  • 53.Dolnikova E., Katunsky D., Darula S. Assessment of overcast sky daylight conditions in the premises of engineering operations considering two types of skylights. Build. Environ. 2020:180. [Google Scholar]
  • 54.Mendis T., Huang Z., Xu S. Determination of economically optimised building integrated photovoltaic systems for utilisation on facades in the tropical climate: a case study of Colombo, Sri Lanka. Build. Simulat. 2019;13(1):171–183. [Google Scholar]
  • 55.Tregenza P.R. Analysing sky luminance scans to obtain frequency distributions of CIE Standard General Skies. Light. Res. Technol. 2004;36(4):271–281. [Google Scholar]
  • 56.Kittler R., Darula S., Perez R. Ploygrafia; Bratislava: 1998. A Set of Standard Skies. [Google Scholar]
  • 57.Li D.H.W., et al. Simple correlations between point daylight factor, average daylight factor and vertical daylight factor under all sky conditions and building design implications. Indoor Built Environ. 2022;31:1700–1714. [Google Scholar]
  • 58.Wienold J. vol. 2009. 2009. Dynamic daylight glare evaluation. (Proceedings of the Building Simulation). (Glasgow, Scotland) [Google Scholar]
  • 59.Li D.H.W., Li S., Aghimien E. 2021. Study the impacts of external shading devices at top floors of highrise buildings facing unobstructed skies. (The 11th SOLARIS 2021). [Google Scholar]
  • 60.Enarun D., Littlefair P. Luminance models for overcast skies: assessment using measured data. Light. Res. Technol. 1995;27(1):53–58. [Google Scholar]
  • 61.Tregenza P.R. Standard skies for maritime climates. Light. Res. Technol. 1999;31(3):92–106. [Google Scholar]
  • 62.Li D.H.W., Lau C.C.S., Lam J.C. Evaluation of overcast-sky luminance models against measured Hong Kong data. Appl. Energy. 2001;70:321–331. [Google Scholar]
  • 63.DOE . U.S. Department of Energy; Washington, DC: 2022. EnergyPlus Software. Building Technologies Office.http://energyplus.net/ [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

The authors do not have permission to share data.


Articles from Heliyon are provided here courtesy of Elsevier

RESOURCES