Table 5.

Peak value of switching overvoltage across circuit breaker S1 in single sided ring topology.

Mitigation method TRV (kV)
Phase A Phase B Phase C
Without mitigation 16.021 34.272 39.452
With PIR 3237 12,800 15,700
With R–C 14.700 29.216 32.775
With choke coil R–L 2.440 9.238 11.616
With surge capacitor 15.260 31.500 34.835