Table 2. Reference operating conditions and main characteristics available by the manufacturer of the LG Chem Resu10 48 V LIB 38 .

Variable Unit Value
General
DC voltage operating range V 42.0~58.8
Volume (exterior box) m 3 0.05
Weight Kg 75
Average environmental temperature °C 20
Depth of discharge % 80
Energetic
Nominal energy / useful kWh 9.8 (25°C, 100% SOC) / 8.8
Nominal power / maximum / peak (in 3 s) kW 3.3 / 5.0 / 7.0
Nominal Capacity Ah 189
Maximum Current A 119 at 42V
DC nominal Voltage V 51.8
Cycles number (90% DOD, 25°C) - 6000
Cycles number (80% DOD, 25°C) - 10000
Environmental conditions
Cooling - Natural convection
Operating Temperature °C -10 a 45
Optimal Operating Temperature °C 15 a 30
Storage temperature °C -30 a 60
Humidity % 5 a 95 (no condensation)
Altitude m < 2000