Table 11. Error analysis of the considered methodologies with ZR compressor.

R407C R450A
Method 1 Method 2 Method 3 Method 1 Method 2 Method 3
Relative
average
error
Discharge temperature (°C) 1.07 1.36 1.37 0.62 0.60 1.75
Electric power (%) 0.95 2.41 2.40 1.83 3.02 3.01
Mass flow rate (%) 0.97 0.69 2.09 2.49 0.96 1.14
Isentropic efficiency (%) 1.29 2.49 2.43 3.47 2.88 3.58
Standard
deviation
Discharge temperature (°C) 0.69 1.98 1.79 0.74 0.71 0.93
Electric power (kW) 0.02 0.05 0.05 0.02 0.02 0.02
Mass flow rate (kg/s) 0.00066 0.00043 0.00058 0.00034 0.00051 0.00044
Isentropic efficiency (-) 0.0045 0.0169 0.0183 0.0139 0.0125 0.0126