Skip to main content
. 2023 Sep 20;9(9):e20312. doi: 10.1016/j.heliyon.2023.e20312

Table 10.

Remediation of the top-ranked 25 fire risk factors.

Ranked Order Risk Factors Corresponding mitigation actions Simplified generalized mitigation actions NFPA Standard
1 F16 Combustible storage separation with a minimum 1-h fire-rated construction Fire-rated construction NFPA 101 [96]
2 F22 Regular standardized ITM for fire detection, sprinkler, fire extinguisher, fire pump, and standpipe Inspection, testing, and maintenance NFPA 72 [97]; NFPA 25 [98]; NFPA 10 [99]; NFPA 20 [100]; NFPA 14 [101]
3 F28 Occupant load reduction as per regulation or providing additional exits to increase exit capacity Adequate exit capacity NFPA 101 [96]
4 F27 Fire detection and protection system standardization according to occupant load and area coverage Standardized detection and protection NFPA 101 [96]; NFPA 1 [102]
5 F30 Electrical connections standardization in panel and distribution board at an approved location Standardized electrical safety NFPA 70 [103]; NFPA 70E [104]
6 F19 Provide automatic smoke detection with audible alarms throughout the building Audible alarm NFPA 72 [97]
7 F26 Separate the gas cylinder room with a 2-h fire-rated construction and seal all penetrations/openings with 1.5-h fire-rated materials
Or,
Relocate and maintain a minimum 3 m (10 ft) spatial separation distance from the building.
Relocate unsafe equipment NFPA 101 [96]
8 F9 Keep egress paths and stairs clear of storage or any obstruction Unobstructed egress NFPA 101 [96]
9 F29 Ensure self-closing, positive latching certified fire doors Certified fire doors NFPA 80 [105]
10 F1 Maintain minimum unobstructed clear width of 0.9 m (36 in.) Widened egress NFPA 101 [96]
11 F11 Separate heat-producing equipment by a minimum 2-hr fire-rated construction, and seal all penetrations and openings with 1.5-hr fire-rated materials to maintain the fire separation.
All exhaust systems shall discharge to the exterior of the building in a safe location.
In case of relocation, maintain a minimum 3 m (10 ft) spatial separation distance from the building.
Sealed penetrations NFPA 101 [96]
Outside exhaust discharge
12 F5 Unlock egress doors, or remove all non-standard locking features from egress doors Unlocked egress doors NFPA 101 [96]
13 F12 Enclose stairs with a minimum 1-h fire-rated construction Fire-rated construction NFPA 101 [96]
14 F14 Seal all penetrations and openings with fire-rated materials for at least 1-hr fire separation Sealed penetrations NFPA 101 [96]
15 F4 Use side‐hinged swinging-type doors Side‐hinged swinging doors NFPA 80 [105]; NFPA 101 [96]
16 F8 Arrange regular fire training and drills Training and drills NFPA 101 [96]
17 F23 Provide adequate illumination (10.8 lux at the floor level) Adequate illumination NFPA 101 [96]
18 F3 Make the exit doors swing in the direction of egress travel Outward directed doors NFPA 101 [96]
19 F24 Provide illuminated directional/exit signs (with uninterruptable power supply) along the path of travel Illuminated exit signs NFPA 101 [96]
20 F20 Provide automatic sprinkler protection throughout the building for floor areas greater than 2000 sq m Sprinkler protection NFPA 13 [106]
21 F25 Remove the manual on/off switch for emergency lighting/exit signage units Automated emergency lighting NFPA 101 [96]
22 F7 Provide remoteness of the exists at least one-half of the maximum diagonal length of the area to be served The remoteness of the exists NFPA 101 [96]
23 F21 Provide standpipe protection for floor lengths greater than 10 m Standpipe protection NFPA 14 (2019)
24 F17 Separate the exit corridor by a minimum 1-hr fire-rated construction Fire-rated construction NFPA 101 [96]
25 F2 Reduce the maximum distance to at most 45 m, if there are no automated fire safety systems and additional exits Shortened dead-end aisles NFPA 101 [96]