Table 10.
Ranked Order | Risk Factors | Corresponding mitigation actions | Simplified generalized mitigation actions | NFPA Standard |
---|---|---|---|---|
1 | F16 | Combustible storage separation with a minimum 1-h fire-rated construction | Fire-rated construction | NFPA 101 [96] |
2 | F22 | Regular standardized ITM for fire detection, sprinkler, fire extinguisher, fire pump, and standpipe | Inspection, testing, and maintenance | NFPA 72 [97]; NFPA 25 [98]; NFPA 10 [99]; NFPA 20 [100]; NFPA 14 [101] |
3 | F28 | Occupant load reduction as per regulation or providing additional exits to increase exit capacity | Adequate exit capacity | NFPA 101 [96] |
4 | F27 | Fire detection and protection system standardization according to occupant load and area coverage | Standardized detection and protection | NFPA 101 [96]; NFPA 1 [102] |
5 | F30 | Electrical connections standardization in panel and distribution board at an approved location | Standardized electrical safety | NFPA 70 [103]; NFPA 70E [104] |
6 | F19 | Provide automatic smoke detection with audible alarms throughout the building | Audible alarm | NFPA 72 [97] |
7 | F26 | Separate the gas cylinder room with a 2-h fire-rated construction and seal all penetrations/openings with 1.5-h fire-rated materials Or, Relocate and maintain a minimum 3 m (10 ft) spatial separation distance from the building. |
Relocate unsafe equipment | NFPA 101 [96] |
8 | F9 | Keep egress paths and stairs clear of storage or any obstruction | Unobstructed egress | NFPA 101 [96] |
9 | F29 | Ensure self-closing, positive latching certified fire doors | Certified fire doors | NFPA 80 [105] |
10 | F1 | Maintain minimum unobstructed clear width of 0.9 m (36 in.) | Widened egress | NFPA 101 [96] |
11 | F11 | Separate heat-producing equipment by a minimum 2-hr fire-rated construction, and seal all penetrations and openings with 1.5-hr fire-rated materials to maintain the fire separation. All exhaust systems shall discharge to the exterior of the building in a safe location. In case of relocation, maintain a minimum 3 m (10 ft) spatial separation distance from the building. |
Sealed penetrations | NFPA 101 [96] |
Outside exhaust discharge | ||||
12 | F5 | Unlock egress doors, or remove all non-standard locking features from egress doors | Unlocked egress doors | NFPA 101 [96] |
13 | F12 | Enclose stairs with a minimum 1-h fire-rated construction | Fire-rated construction | NFPA 101 [96] |
14 | F14 | Seal all penetrations and openings with fire-rated materials for at least 1-hr fire separation | Sealed penetrations | NFPA 101 [96] |
15 | F4 | Use side‐hinged swinging-type doors | Side‐hinged swinging doors | NFPA 80 [105]; NFPA 101 [96] |
16 | F8 | Arrange regular fire training and drills | Training and drills | NFPA 101 [96] |
17 | F23 | Provide adequate illumination (10.8 lux at the floor level) | Adequate illumination | NFPA 101 [96] |
18 | F3 | Make the exit doors swing in the direction of egress travel | Outward directed doors | NFPA 101 [96] |
19 | F24 | Provide illuminated directional/exit signs (with uninterruptable power supply) along the path of travel | Illuminated exit signs | NFPA 101 [96] |
20 | F20 | Provide automatic sprinkler protection throughout the building for floor areas greater than 2000 sq m | Sprinkler protection | NFPA 13 [106] |
21 | F25 | Remove the manual on/off switch for emergency lighting/exit signage units | Automated emergency lighting | NFPA 101 [96] |
22 | F7 | Provide remoteness of the exists at least one-half of the maximum diagonal length of the area to be served | The remoteness of the exists | NFPA 101 [96] |
23 | F21 | Provide standpipe protection for floor lengths greater than 10 m | Standpipe protection | NFPA 14 (2019) |
24 | F17 | Separate the exit corridor by a minimum 1-hr fire-rated construction | Fire-rated construction | NFPA 101 [96] |
25 | F2 | Reduce the maximum distance to at most 45 m, if there are no automated fire safety systems and additional exits | Shortened dead-end aisles | NFPA 101 [96] |