Table 1.
Air conditioning, hot water and lighting energy consumption table (2022).
| Category | Application | Total installed power/kW | Installed power/kW | Parameters | Annual energy consumption/104kW | Ratio |
|---|---|---|---|---|---|---|
| Cold Water | Air Conditioning | 12180 | Outpatient Building: 2 × 250RT +2 × 250 + 3 × 160RT; |
Summer: 7/12 °C | 835 | 44.25 % |
| Inpatient building: 3 × 400RT | ||||||
| Winter: 11/16 °C | ||||||
| Synthetic building: 2 × 860 kW + 1000 kW + 120 kW | ||||||
| Hot Water | Washing and rinsing, Air Conditioning | 3400 | Outpatient Rooftop: 3 × 200RT Heat Pumps | 45/40 °C | 190 | 10.07 % |
| Highland air source heat pumps: 2 × 300 kW | ||||||
| Low zone air source heat pump: 2 × 350 kW | ||||||
| Solar hot water on the sky of outpatient + complex building: about 500m2 | ||||||
| Air circulation | Air Conditioning | / | Comfort area: fan coils + fresh air | Cleanliness/Comfort | 250 | 13.25 % |
| Outpatient building 6F, complex building 4F for clean area: all air system | ||||||
| Lighting facilities | Lighting | / | / | / | 150 | 7.95 % |
| Other | / | / | / | / | 462 | 24.48 % |