Table S5:
PSA plant capacity (LPM) | Minimum no. of h/day when used only with electricity | Maximum no. of h/day on DG set when used for 24 h/day | Maximum no. of hours on DG set if used for 12 h/day | |||
---|---|---|---|---|---|---|
|
|
|
||||
Manufacturing (h/day) | Manufacturing + Cylinder Refilling (h/day) | Manufacturing (h/day) | Manufacturing + Cylinder Refilling (h/day) | Manufacturing (h/day) | Manufacturing + Cylinder Refilling (h/day) | |
100 | 10 | 18 | 2 | 0 | 0 | 0 |
200 | 6 | 10 | 8 | 1 | 2 | 0 |
400 | 5 | 8 | 8 | 2 | 3 | 0 |
500 | 5 | 8 | 8 | 2 | 3 | 1 |
800 | 5 | 8 | 9 | 3 | 4 | 1 |
1000 | 5 | 8 | 9 | 3 | 4 | 1 |
1200 | 5 | 8 | 9 | 3 | 4 | 1 |
1500 | 5 | 8 | 9 | 3 | 4 | 1 |
2000 | 5 | 8 | 9 | 3 | 4 | 1 |
2500 | 5 | 8 | 9 | 3 | 4 | 1 |
3200 | 5 | 8 | 9 | 3 | 4 | 1 |
LPM – Litres per minute; PSA – Pressure Swing Adsorption; DG – Diesel generator