Table 2.
HVAC Transmission line data.
| Positive and negative sequence impedance per phase in ohm | 3.307 + j14.053 |
| Zero sequence impedance per phase in ohm | 10.75 + j45.67 |
| No. of sub-conductors per phase | 3 |
| No. of ground wires | 2 |
| Diameter of sub-conductor in mm | 30.6 |
| Vertical height of conductor at mid-span in meter | 9 |
| Vertical height of ground wire at mid-span in meter | 21 |
| Diameter of ground wire in mm | 11.02 |
| DC resistance of conductor in ohm per km | 0.0133 |
| DC resistance of ground wire in ohm per km | 0.35 |
| Ground tower rod length in meter | 1.5 |
| Ground tower rod radius in cm | 1.25 |