Skip to main content
. 2024 Aug 27;14:19816. doi: 10.1038/s41598-024-69840-3

Table 3.

Simulation results in HVAC transmission system.

Parameters of CB Maximum recorded TRV (kV) Arc re-ignition
RRDS (V/µs) L (mH) C (µF)
50 752.7 No
10 797.8 Yes
10 0.3 20 431.02 No
10 1 20 431.33 No
10 10 20 434.93 No
10 0.3 5 395.3 Yes and Phase B failed to open
10 0.3 40 433.2 No