Table 3.
Labeling basis on six types of classification.
| Category | Description | Criteria |
|---|---|---|
| Normal condition | Standard operating conditions without any faults | All parameters within expected range; no anomalies or irregular patterns |
| Supply fan fault | Issues related to the HVAC system's fan | Significant deviations in airflow rate, fan speed, or electrical consumption patterns |
| Total heating pump fault | Issues related to the heating pump | Lower median and higher variance in heating pump status |
| Return air temperature sensor fault | Malfunctions in the sensors measuring return air temperature | Return temperature readings outside the 25th to 75th percentile range (13.55 °C to 20.2 °C) |
| Supply air temperature sensor fault | Malfunctions in the sensors measuring supply air temperature | Supply air temperature readings outside the 25th to 75th percentile range (18.21 °C to 27.44 °C) |
| Valve position fault | Problems with the heating valve operation | Failure to open/close as commanded, delays in response, abnormal range of motion, irregular position readings |