Table 2.

Comparison of design axial capacities between numerical predictions, test results and ACI 440.2R-17.

Fire condition Design axial capacity (kN) Differences from numerical predictions
Numerical Test results
(Cree et al. [23])
ACI 440.2R-17
[43]
Test results
(Cree et al. [23])
ACI 440.2R-17
[43]
Room temp. 2208 2265 2342 2.5% 5.7%
4-h fire 1894 1948 - 2.8% -