Table 3.

Fire endurance ratings for CFRP-strengthened RC column insulated with SFRM.

Insulation Criterion 1 (CFRP) Criterion 2 (CFRP) Criterion 3 (Side rebar) Criterion 3 (Corner rebar)
Tg < 71 ℃ Tig < 450 ℃ Tr < 593 ℃ Tr < 593 ℃
No insulation 3.2 min 11 min 3.1 h 1.3 h
10-mm SFRM 10 min 1.4 h 2.8 h
20-mm SFRM 19 min 3.3 h
30-mm SFRM 32.4 min