Abstract
Indoor air pollutants and airborne contamination removal have been challenging in healthcare facilities. The airborne transmission control and HVAC system may collapse in hospitals due to the highly infectious respiratory disease-associated patient surge, like COVID-19. Common air filtration systems and HVAC systems enhance the patients' comfort and support indoor hygiene, hitherto insufficient to control highly infectious airborne pathogens and hospital-borne pollutants such as radon, PM2.5, patient droplets, VOC, high CO2, and anesthetic gases. This review summarized important air cleaning interventions to enhance HVAC efficiency and indoor safety. We discussed efficient air cleaning and ventilation strategies including air filtration, air ionization, passive removal materials (PRM), and UVGI to minimize cross-contamination in hospital wards.
Keywords: Indoor air pollutants, High ventilation, Wards design, Passive removal materials, Air purifier, Advance HVAC, Bipolar air ionization, Ultraviolet C, Trombe wall
Graphical abstract
1. Introduction
Indoor air quality and associated health risks have been one of the critical subjects during the COVID-19 pandemic. Areas such as surgical theaters, ICU, and isolation wards are susceptible to multiple airborne contaminants and pollutants due to continuous exposure of respiratory droplets, skin squames, lint, respiratory droplets, aerosols, disinfection and sterilizing substances, outdoor pollutants, and leakage of anesthetic gasses [1]. Hospital-acquired infections represent serious health burdens and mortality worldwide [2,3,4,5].
Indoor air pollutants may aggravate and facilitate respiratory infection spread, particulate pollutants particles may provide substrate to airborne pathogens deposition and transmission [6,7].
According to the World Health Organization (WHO), indoor air pollution causes 3.8 million deaths annually. Indoor air pollution short- and long-term exposure may cause a wide range of diseases.In 2020, COVID-19 transmission was highest in healthcare facilities. However, healthcare-associated airborne and other infections and antimicrobial resistance-associated worldwide mortality are uncountable. It is observed that around 24 % of patients are affected by healthcare-associated sepsis and 52.3 % of those patients die each year when treated in an intensive care unit. In the case of antimicrobials resistant deaths are increased by two to threefold [8,[9], [10],11].
Besides airborne infections, cleaning agents and detergents may deteriorate indoor air quality as raise indoor HCHO and Volatile Organic Compounds (VOCs) concentrations in hospital environments. PM2.5 concentration in the patients' wards may reach more than outdoors in polluted regions. Increased exposure to VOC and particulate pollutants may come with several negative effects on patients and hospital staff [12,13]. Disinfectants, sanitizers, medical equipment, polymer materials-based blood bags, injectors plastic, infusion bags plastic film, and rubber tubing may be a potential source of phthalate and VOC. Air pollutants radon, anesthetic gases such as halothane, isoflurane, sevoflurane, and N2O may also occur in hospitals [[14], [15]]. Microbial count may reach up to 104 cells m3 in hospital air. So pollutant-free air supply could be challenging in hospital settings [16]. A recent study in India indicates that outside and inside air pollutant types and concentrations are influenced by the surrounding area where hospitals are situated, for instance particulate matter M1.0–2.5, PM0.50–1.0, PM0.25–0.50, PM < 0.25, and indoor fungi load are highest in the industrial belt. In contrast, PM > 2.5 and bacterial load are higher in residential belts [17]. Similarly, indoor air pollutants negative impact and hospital-acquired infections (HAI) is 19 % higher in developing countries due to high air pollution. HAI-associated financial burden due to antimicrobial resistance bacteria such as Methicillin-resistant Staphylococcus aureus (MRSA), and carbapenem-resistant Enterobacterales is more in polluted regions [18,19]. Air disinfection is a routine and integral part of hospital cleaning. Air Handling Unit (AHU) systems Including Heating, ventilation, and air-conditioning (HVAC) are crucial in providing a compatible safe environment for hospital patients, filtering dust particles, and biological contaminants, and maintaining air change rates and ventilations. Nevertheless, the chance of air-conditioning-associated microbial transmission remains uncertain [20,21].
Hitherto, the risk of secondary transmission of contaminants in healthcare facilities is high as many hospitals' capacity is limited to safely handle the surge of infectious patients [22]. Sneezing, coughing, biological waste products, spraying of liquids, and dust generate aerosolized particles. Aerosolized particles that are smaller than 100 μm float and are dispersed via air currents to different places [23]. Air pollutants CO2, PM2.5, PM10, TVOCs, patient droplets, and anesthetic gasses leakage remain active and entrapped due to the packed indoor atmosphere and affect hospitals and ambulance services [24,25]. Indoor ventilation design and air cleaning are crucial in healthcare facilities since any glitch in the air-conditioning system may lead to serious consequences [26,27]. Air conditioning units themselves may also act as reservoirs of contaminants. A study in 25 operating theatres in India showed around 26 % of AC units filter with fungal colonization [28].
An obstructed airflow or poor HVAC maintenance can increase the pathogen concentrations in healthcare facilities. There are limited studies on indoor air quality management in health sectors to tackle the sudden surge of highly infectious patients. Few studies suggest that good ventilation with fibrous filters (HEPA), ultraviolet radiation, or plasma units may reduce the biological droplet and chemical contaminants [29,30,31].
Considering this context, this review discussed how the healthcare air conditioning/filtration system can be improved with advanced air filtration, disinfection, and ventilation techniques. Control of hospital-borne aerosol reduces the chances of contaminants exposure and enhances the safety preparedness against the potential risk of nosocomial outbreaks, occupational airborne pollutants, and COVID-19-like highly contagious transmission.
2. Methodology
This review is comprised of recent literature related to the theme. A total of 17300 relevant records were found in PubMed, Scopus, Web of Science, Embase, Cochrane Library, and Google Scholar. Searching filters such as “Air Pollutants in Hospitals” “HVAC in hospitals” and “air cleaning in hospitals” from 2015 to 2023 time period were used during the draft preparation and writing, and more keywords were used during revision to fill the gaps suggested by reviewers. Articles selection criteria were based on the number of citations. Irrelevant/duplicate articles were removed, and 188 articles were incorporated into the final version of the paper, Fig. 1.
Fig. 1.
Schematic representation of methodology.
Healthcare-associated contaminants and their possible removal strategies are summarized under the following main 7 sections, numbered as.
-
3.
Potentially hazardous air pollutants in healthcare facilities.
-
4.
Airborne droplets Transmission Control in different Wards
-
5.
Air Filtration Strategies
-
6.
Advanced HVAC System
-
7.
Photocatalytic oxidation (PCO), plants and Trombe wall role to manage nearby outdoor air pollutants
-
8.
Organic pollutants abatement by Passive Removal Materials (PRMs)
-
9.
Air cleaning Intervention in Emergency Health Vehicles
3. Potentially hazardous air pollutants in healthcare facilities
Hospital wards, especially surgical theatres are among the most demanding healthcare work areas with the potential exposure of contaminated air containing disinfection and sanitizing substances, and anesthesia gasses Fig. 4. The concentration of CO2, VOCs, and PM2.5 may increase in clinics. Therefore, HVAC installations with air-cleaning interventions are recommended to provide a safe environment for surgeons, medical staff, and patients [32,1]. Poor air quality can interfere with patients’ recovery and also cause sudden outbreaks of sick-building syndrome including nausea, fatigue, headaches, and eye irritation. Moreover, the risk of high indoor air pollutants could be immensely high in most polluted countries due to the positive correlation between outdoor and indoor PM1.0 and PM2.5 concentrations [33,34]. Indoor air pollutants in hospital environments may cause several negative health conditions, Table 1. A study in China indicated that total volatile organic compounds (TVOC) such as formaldehyde, toluene, and xylene, etc. are the main carcinogenic indoor air pollutants [35,36].
Fig. 4.
Types and sources of air pollutants in the healthcare system.
Table 1.
Hospital-borne air contaminants associated health complications and their removal techniques.
| Indoor Air Pollutants and contaminants | Potential Exposure Source in Hospitals | Health Impact | Source Control & Cleaning Techniques |
|---|---|---|---|
| Asbestos (Mg3(Si2O5)(OH)4) | Asbestos-containing building materials in surfacing materials, thermal system insulation [37] | Lung cancer (asbestosis) and mesothelioma [[38], [39], [40]] | Water misting [41] |
| Arsenic (As) | Nearby industries, orchards, coal combustion, pesticide residues [42] | Extremely toxic, lung damage, shortness of breath, chest pain, and cough. Long term Exposure can lead the development of various cancer [43,44] | Several types of adsorbents such as Calcium-based adsorbents and ion exchanges [45,46] |
| Biological Pollutants (Pollen, viruses, bacteria, mold, dried allergens) | Mostly operating rooms and intensive care units [47] | Infectious illnesses, hypersensitivity, allergies, dizziness [39,43] | High ventilation [48], downward ventilation [49], HEPA Filters, portable air cleaners (if HVAC not functional), negative-pressure, Recommended Ventilation 80–160 L/s/patient for airborne isolation wards 60 L/s/patient for general wards 2.5/sec/m3 for corridors [50] Or 6-12 ACH for new building and about 6 ACH in existing buildings [50] |
| TVOC (Benzene, HCHO) | Anesthetic gases, disinfectant, hand sanitiser, pharmaceuticals and cleaning products [51] Pathology departments [52] |
Carcenogenic [51], Damage to liver, kidney and central nervous system, allergies, nausea, fatigue, emesis, dizziness [39,53,54], formaldehyde and benzene have been identified carcinogen [55,56,57,39] | Using low emitting products, Avoiding air fresheners, exhausting [58] Activated carbon filter [59,60] |
| Carbon monoxide (CO) | Parking areas, Outdoor air exchange [61]. | nausea, vomiting, chest pain, and confusion neurological problems [43,55,62,61] | Fe2O3 nanoparticles may oxidize carbon monoxide [63] |
| CO2 | Dry ice for preserving the cadaver [64], occupants | High concentrations leads to an increased respiratory rate, tachycardia, cardiac arrhythmias and impaired consciousness. More than 10 %, may cause convulsions, coma and death [39,55,65] | Ca-based CO2 Sorbents [66,67] CO2-based ventilation control [68] |
| Lead (Pb) | Hospital waste, Contaminated dust from outside [69] | Dangerous to children’s brains and nervous systems; exposure can disturb cardiac autonomic function as well [39,70] | Adsorption by Activated carbon [71]. |
| Anesthetic gaseous agents | Ambulatory operating room, and the burn unit, postanesthesia care units. leakage into the atmosphere due to ventilator circuit connections, exhaust valves, defects in plastic insufflation balloons, or ventilator connectors [72,73]. | Reproductive effects, spontaneous abortion, teratogenicity [74,75,72,73] | Photocatalytic oxidation can reduce isoflurane (Byproducts may release) [76]. Activated carbons, zeolites, metal-organic frameworks, aerogels, carbon nanotubes and activated alumina [77] |
| Antimicrobials biocides, sterilants, insecticides, herbicides, and fungicides) | Stored containers, disinfectants in hospitals [78] | Risk of cancers, Irritation to eye, nose and throat, damage to central nervous system, liver and kidney [39,79]. | Certified cleaning agents, Rinsing of surfaces when overuse, Indoor lights to degrade insecticides [80]. TiO2 photocatalysis for gaseous pesticides [81]. |
| Infectious respiratory aerosols, respiratory aerosols <5 μm Particulate Matters (PM 2.5) |
poorly ventilated spaces containing infectious individuals, medical wards polluted outdoor air exchange [82] |
Multiple and Immense effect on human health, respiratory disease Premature death, particularly cardiovascular diseases, endocrine malfunction, metabolic diseases [39,83]. | Portable air cleaner with HEPA filter [84,85] |
| SARS-CoV-2 droplets | Droplets from infected patients/staff’s mouth or nose cough, sneeze, speak, sing or breathe. Through aerosols Environmental surfaces [86] |
COVID-19 Infection associated illness | Portable Air Cleaners and Combining ventilation [[87], [88], [89]] |
| Polycyclic aromatic hydrocarbons | Parking vehicles near hospitals [90] | Mutagenic, Carcinogenic Naphthalene lesions, Tumors in the upper respiratory tract, hemolytic Anemia [55,91] |
Air filtration [92], zeolite filter [93] |
| Radon (naturally occurring radioactive gas) | In hospitals in basement rooms [94] | Carcinogen [95,96,97,94] | Activated charcoal [98] Appropriate intermittent ventilation [99] |
| Ozone (O3) | Possible byproducts of UV sterilization | Toxic. Ozone can also exacerbate chronic respiratory diseases such as asthma [43,55,96]. | Activated carbon-based filters, catalytic decomposition [100] |
In addition, bioaerosol composition and distribution in hospitals is complex. PM2.5 bioaerosols sampling showed Vibrio metschnikovii, Staphylococcus epidermidis, Staphylococcus haemolyticus, Fusarium pseudensiforme, and Aspergillus ruber are dominant species in hospitals [101].
These contaminates showed spatial variation in the hospital and influenced by temperature, relative humidity, ventilation system, and daily activities. Studies showed that total bacterial load may reach 134.3 CFU/m3 across the intensive care units (ICUs) [102]. Multi-antibiotics resistance methicillin-resistant Staphylococcus aureus (MRSA) concentration was found 95 CFU/m3 in pediatric wards [103].
Several studies observed that bacterial concentrations may exceeded WHO guidelines in obstetrics, pediatric, and surgical wards range 450–1585 CFU/m3, Fig. 2 [104].
Fig. 2.
Variation in microbial concentration in different wards.
A study in Singapore’s local hospital showed airborne bacteria such as normal skin microbiota, opportunistic Acinetobacter, and Flavobacterium spp 500 CFU/m3 in the air-conditioned lobby and pharmacy. However, in restricted wards, the maximum concentration of the same bacteria was 325 CFU/m3. Indoor levels of airborne bacteria were significantly correlated to relative humidity [105]. Similarly in a Portuguese hospital airborne microbial count exceeded the conformity criteria as the highest bacterial counts were 240–736 CFU/m3 (BC) and 27–933 CFU/m3 fungal load (FL) observed in emergency service sites. While Bacterial concentrations in the surgical wards range 99–495 CFU/m3 and the operating theater 12–170 CFU/m3 under recommended criteria while fungal levels were below 1 CFU/m3 in the operating theater, and range 1–32 CFU/m3 in the surgical wards. Most frequent (88 %) phenotype was Gram-positive cocci in all indoor environments which accounts Staphylococcus (51 %) and Micrococcus (37 %) and fungal prevalent genera were Penicillium (41 %) and Aspergillus (24 %), Fig. 3 [106].
Fig. 3.
Most Frequent bacterial species in Hospital atmosphere.
Studies showed an average 5–10 % of in-patients in hospital can be infected with nosocomial infection, mostly in intensive care and surgical units. Frequently observed nosocomial infections categories includes bacteraemia, catheter-associated urinary tract infection, gastrointestinal infection, nosocomial pneumonia and surgical wound infection [107].
However airborne respiratory viruses infections are also not less common. The load and dispersion of parainfluenza virus, respiratory syncytial virus, rhinovirus, and adenovirus were associated with the number of infected patients in wards. Air viral load is significantly higher (1.02 × 104 copies/mL) in 2-patient rooms compared to singly isolated patients (1.58 × 103 copies/mL) [108].
Airborne microbe’s frequency may be highest in respiratory patients' clinics and ICU units. In addition, the presence of some pathogens may be correlated. A noticeable correlation was found between SARS-CoV-2 concentration and the presence of airborne bacteria [109].Dissemination of airborne pathogens could be associated with several factors. A study found that serious antibiotic-resistant pathogens such as Clostridioides difficile can be intra-associated with hospital air, floor, and hospitalized patients [110].
Aerosol samples from different COVID-19-positive patients’ wards, rooms in long-term care homes experiencing outbreaks, and ICU rooms showed 1202 to 11939 copies/m3 of viral RNA in air, low concentrations of viral RNA in well-ventilated spaces, Fig. 2 [111].
Removal of hazardous airborne contaminates has been an important practice in healthcare settings [112]. Disinfection and air cleaning preventive measures had remarkable effectiveness to reduce HAI was observed during novel SARS-CoV-2 spread [113].
However, extensively used surface disinfectants/sterilants products such as bleach, glutaraldehyde, formaldehyde, hydrogen peroxide, and enzymatic cleaners have been proven hazardous to occupant’s health and environment. Several studies suggest that cleaning agents are associated with work-related asthma and skin irritations among hospital workers [114,115].
Hospitals may suffer from the overuse of cleaning agents and hazardous waste production, the largest contributor to environmental degradation. Healthcare waste is the fourth biggest contributor to mercury presence in the environment. Large countries like the United States produce around 6700 tons of waste daily [116]. So, cleaning and waste management have been routinely monitored aspect in hospitals in many countries [117].
Bioaerosol or microbial contaminants are often estimated in for of CFU/m3 to predict the overall indoor air hygiene in hospital wards. Indoor bacterial count of 9.6 × 102 cfu/m3, may increase the risk of respiratory infections development compared to the recommended cfu (≤500 cfu/m3) level by American Industrial Hygiene Association [118,2].
4. Routine disinfection and environmental cleaning in healthcare facilities
Environmental cleaning is crucial to prevent microbial contaminants in healthcare facilities. Common surfaces like floors, bathroom facilities, bed rails, furniture in patient rooms, and medical equipment could be reservoirs of highly contagious pathogens including multiple species of Acinetobacter, Clostridium difficile, methicillin-resistant Staphylococcus aureus (MRSA), and vancomycin-resistant enterococci (VRE). Environmental cleaning is a broad term that involves various disinfection and monitoring methods. Multiple cleaning agents and disinfection technologies are being used in health sectors.Commonly used surface disinfectants are sodium hypochlorite, quaternary ammonium compounds, peracetic acid, and liquid hydrogen peroxide. Methods like Ultraviolet light (UV-C) or fogging with hydrogen peroxide vapor for disinfection when patient rooms are empty [119]. Cold atmospheric pressure plasma and electrolyzed water (hypochlorous acid) are also being used for disinfection [120]. Other cleaning options such as self-cleaning or disinfecting floor tiles are also being considered in hospitals. Coating with several germicidal materials such as photocatalytic TiO₂ nanoparticles has shown interesting applications in the healthcare environment [121]. However, disinfectant selection should be according to occupational safety and environmental compatibility. For instance, some reusable medical equipment such as endoscopic devices can be damaged by peroxyacetic acid (PAA) solution [122].
4.1. Monitoring and risk assessment of biological contaminants
Regular air and surface monitoring are necessary to detect potential contaminants in healthcare settings. However, evidence-based risk analysis protocols are limited. Healthcare facilities may operate patient, pathogen, and surface risk assessment. Microbiological sampling is the most common practice to monitor the cleanliness in hospitals but delayed results cause hindrance. Advanced methods such as adenosine triphosphate (ATP) bioluminescence assays or ATP meters are gaining popularity in the hospital environment due to easy operation and quick results, ATP is an important energy source in every living contaminates but its routine use, remains controversial [123].
Significant variation can be seen in surface and air sampling methods. Basic surface sampling involves direct sampling (contact plates, dipslides, Petrifilms) and indirect sampling (swabs, sponges, wipes). Collected samples further culture on suitable media and investigates. While for specific pathogens specifically designed swabs and media are used. For instance, macrofoam swabs and tryptone soya broth media are used to collect and grow MRSA respectively, and a sponge swab and Brazier's CCEY agar are used for C. difficile. For viruses DNA or RNA-based methods are used. In addition, Matrix-assisted laser desorption ionization-time of flight (MALDI-TOF) mass spectrometry technique, PCR, qPCR, and Multiplex PCR can be used for accurate results [124].
For bioaerosol microbiological sampling, passive air monitoring and active air monitoring are two commonly used methods. In passive monitoring, standard Petri dishes with suitable media are exposed to the air, (also known as settle plates) in the investigation area for a few hours, that’s allows biological particle sedimentation in Petri dishes. These plates are incubated and results are expressed in CFU (Colony Forming Units)/plate/time or CFU/m2/hour. This method is also useful for valid risk assessment of harmful parts of the airborne pathogens in surgical wards. Active air monitoring involves a microbiological air sampler that allows a specific known volume of air through or over a particle collection object which can be a solid culture media plate or liquid or a nitrocellulose membrane filter. These media or filters are further processed for the microbial load quantity, measured in CFU/m3 of air. This method is preferred in controlled environments such as operating theatres where airborne pathogens concentration is supposed to be low [125].
Studies suggest that an air sampler can be an effective tool to collect a variety of airborne particles. Specifically designed air samplers including vacuum cleaner-based air samplers have been successfully used for SARS-CoV-2 sampling [[126], [127], [128]].
For chemical pollutants such as total volatile organic compounds (TVOC), nitrogen dioxide, particulate matter (PM2.5), and CO2. Sensors-based real-time air quality monitors were found useful [129,130].
4.2. Sanitary standards for biological contaminants
Bio-aerosols contain a range of tiny particles airborne particles (ranging from 0.001 to 100 μm) of bacteria, endotoxins, fungi, mycotoxins, and allergens. However, health risk-based standards for bio-aerosols are limited and have variations as there are no uniform international standards to determine acceptable bacterial loads in indoor air. A group of WHO experts suggest that total microbial load should not exceed 1000 CFU/m3 in common indoor environments. Whereas other researchers suggest 800 CFU/m3 maximum upper limit for ubiquitous bacterial aerosol. For fungi 150 CFU/m3 of mixed species may be acceptable but 50 CFU/m3 for single species of fungi warrants immediate examination [131,132].
The European Commission's sanitary standards for bacterial and fungal load in non-industrial premises have been considered helpful in several airborne pathogens investigations in healthcare facilities, Table 2 [133,134].
Table 2.
The European Commission's sanitary standards for biological contaminants in non-industrial premises.
In addition, for individual safety, medical face masks and respirators may provide significant personal protection against pathogens containing bio-aerosols including viruses [135]. Occupational Safety and Health Administration (OSHA) provided specific recommendations to protect high-risk workers in healthcare from infections like COVID-19 which involves the principles of ventilation, physical distancing, and face coverings. Medical masks must comply the international standards such as Food and Drug Administration (FDA) or American Society for Testing and Materials (ASTM) standards to ensure that the face mask or similar device has an acceptable level of filtration, biocompatibility, and breathing resistance [136].
5. Airborne droplets transmission control in different wards
Highly transmissible Pathogens control could be challenging in healthcare settings due to several constraints. For instance, to check the air hygiene Colony Forming Units (CFU) count found useful proposed standards to evaluate bacterial and fungal contamination. In most cases, a total aerobic colony forming units count of <2.5 or 5 CFU per cm2 and <1 CFU/cm2 of Staphylococcus aureus, Enterococcus species, etc. is recommended. However, no such standards apply to viral aerosol and in the emergency medical services [137].
According to the Healthcare Infection Control Practices Advisory Committee (HICPAC), the four classes of infection control: Standard Precautions, Droplet Precautions, Contact precautions, and airborne precautions are recommended to control airborne pathogens transmission.
Standard Precautions involve common hygiene practices to avoid contact with blood, body fluids, all secretions, nonintact skin, and mucous membranes. Infectious patients must be placed in a private room. Droplet precautions involve the prevention of coughing and sneezing droplets exposure from infected ones. Since droplets usually travel only 3 feet in the air face mask, private rooms are suggested to avoid exposure. Contact precautions involve skin-to-skin contact. Gloves and sterile patient care equipment can be dedicated to a single uses. Airborne precaution requires careful air handling and ventilation. Infected Patient's rooms should have negative air pressure and 6–12 ACH per hour and no air recirculated to other areas without significant filtration. Personal respiratory protection such as N95 respirators is suggested when entering the room [138].
5.1. Ventilation strategies
Increased ventilation mechanical or natural can reduce airborne transmission effectively. Appropriate air distribution and airflow patterns are important engineering intervening approaches against airborne droplets including respiratory infectious diseases COVID-19. Ventilation indices of air change effectiveness (ACE) or air change per hour (ACH) are the most commonly used parameters to evaluate indoor air recirculation [139,140,141].
Hospital ventilation conditions may influenced by different climate conditions and indoor designs. Usually, four types of hospital ward designs are preferred worldwide: bay wards, nightingale wards, racetrack wards, and hub and spoke units. The nightingale wards may cater to up to 30 adults or 24 children and is still widely used in many developing countries. Indoor conditions in operating rooms, isolation rooms, and nursing wards have specific HVAC guidelines; commonly recommended temperature, relative humidity, ACH, pressurization range, and worldwide variation thereof are given in Table 3 [142].
Table 3.
Worldwide HVAC guidelines for different wards in hospitals.
| Types of Wards | Temperature C | Relative Humidity | Recommended Minimum ACH (Indoor) | Suggested Air Pressure | References |
|---|---|---|---|---|---|
| Patients Room | 21–23 | 30–60 % | 6 | – | [142,143] |
| Pediatric& obstetrician wards | 22–26 | 30–60 % | 6 | – | [143] |
| Surgery Room | 17–27 | 30–55 % | 15–25 | Positive/neutral | [143,144] |
| General inpatients area and corridor | ≤24 | 30–60 % | 4 | – | [143] |
| Isolation wards with highly infectious patients like COVID-19 | – | – | 12–15 | Negative | [144] |
| ICU | 21–24 °C (Australia) 16–25 °C (India) 21–24 °C (UAE) 18–25 °C (UK) 21–24 °C (USA) |
30–60 % (Australia, UAE, USA) 40–60 % (UK) |
6 (Australia, India, UAE, USA) 10 (UK) |
Positive (Australia) Neutral (Germany) Neutral (India) Positive (UAE) Positive/Neutral(UK) Neutral(USA) |
[144] |
The ventilation efficiency can be increased with proper filtration of natural fresh air and by reducing the occupancy in patients' wards and concentration of exhaled aerosols [145,146].
Recirculated air should be filtered in wards, especially in isolation wards with highly infectious patients.
To minimize the risk of airborne contaminations spread medical facilities must require MERV 14 to 16 rating filters. These filters with MERV ≥17 are known as high-efficiency particulate air (HEPA) filters. A typical MERV 17 rating HEPA filter has an efficiency of 99.97 % against 0.3 μm size particles. However, in highly hygienic body implant areas MERV rating can be 20 with a filtration efficiency of 99.999 %. Microbial count expected below 0.1 CFU/m3 where HEPA filtration is employed. HEPA filters need regular monitoring every 6 months [144].
Multi-bed spaces like Nightingale wards are common in many countries. Contamination-free proper ventilation in large multi-bed wards could be challenging due to multiple openings. High ventilation rates are achievable in naturally ventilated hospitals. A nightingale ward showed that external wind 1–4 m/s speeds may lead to indoor ventilation rates as recommended for general wards (3.4–6.5 ACH). Extractor fans can also play a key role in maintaining air quality. However, a hybrid ventilation system with natural and mechanical ventilation may deliver the best year-round solution [147].
The location of an infected patient in hospital wards may affect infections like MERS-CoV, SARS-CoV, and H1N1 influenza virus spread risks to other occupants in the same hospital. It is observed that patients’ position near the corridor can exhaust the viral droplets into the corridor immediately, Fig. 5. Contrary infected patient's position in the inner part of the ward allows the virus particles to deposit on wall surfaces or other patients. Usually, 9 ACH and the installation of ultraviolet germicidal irradiation (UVGI) lamps can minimize the risk of highly infectious viral droplets [148].
Fig. 5.
Infected patients' positions and the risk of cross-contamination: Ward-1: Patient 1 position near air exhaust may reduce the risk of cross-contamination as infectious droplets eliminate swiftly. Ward-2: Patient 2's position facilitates longer traveling distances of infectious droplets, so the risk of cross-contamination and surface contamination may increase.
Toilets in the wards can also be the hub of virus transmission so must not be neglected strict infection control precautions including ventilation by opening any windows or by propping extractor fans can be increased. The movement of near infectious patient’s wards should be reduced as far as possible [149].
6. Air Filtration Strategies
The importance of ventilation in indoor pollutant dilution is discussed in the 4th section. Contamination-free ventilation systems are expected in hospitals. Studies show negative pressure, adaptive wall-based attachment ventilation with HEPA filters, adsorption filters, and UV radiation could be beneficial in a surge of COVID-19-like infection control. However, the concern of associated byproducts such as microplastics, and residues of degrading filters also increased [150,151].
6.1. Negative pressure wards significance in the surge of COVID-19-like diseases
In 2020, as many as 8000 medical personnel were infected 63 and physicians died from COVID-19 in Italy. The major cause of frontline medical system collapse is enclosed medical environments between patients and medical staff and an insufficient number of negative pressure isolation wards to admitting infected patients. Indoor air quality in medical spaces can be affected by external air pollution such as waste gasses, diesel exhaust, hydrocarbon particulate matter and ozone, and other pollutants directly generated indoors such as volatile organic compounds (VOCs) from indoor interior decoration, furnishings and carbon dioxide (CO2) exhaled by humans. CO2 concentration in indoor environments plays a key role in indicating indicators of indoor air quality; it is recommended that CO2 concentration in hospitals should be less than 600 ppm. Negative pressure isolation wards contain ventilation systems that are generally well planned, but the issue of nosocomial and air cross-contamination is primarily due to the factor of indoor air quality (IAQ). Negative pressure isolation wards usually contain well-planned ventilation systems to keep indoor environments healthy but are associated with emissions that create heat and air pollution in the environment. Negative pressure should be up to 8∼12 Pa in the wards and hallways to prevent contaminated air from entering other spaces. It has been tested that increasing the air change rate 54.5 and 40 times/hour and introducing fresh air to maintain CO2 concentration below 600 ppm can increase the efficiency of traditional negative pressure isolation wards. In addition, A velocity of 0.5 m/s for an air-jet curtain in negative pressure ward can also decrease the contamination and exposure of aerosol particles from the coughing patient, Fig. 6 [152,153] (see Fig. 7).
Fig. 6.
Negative Pressure ward with high pressure air curtain and filtered air supply.
Fig. 7.
Air cleaning Interventions combined with central HVAC system in Hospital (HEPA grade 14).
SARS-CoV-2 variants such as BF.7, BA.2, BA.2.75, BA.2.75.2, BQ, XBB, etc. concern have been continuous since the pandemic erupted. Most of these variants could accelerate the emergency admission in hospitals and posed substantial pressure in health care systems. New variants may acquire exclusive characteristics such as elevated immune evasion, additional spike mutations, and higher transmissibility. Amid the continuous episode of new variants recent variant JN.1 burgled the alarm once again as detected in 41 countries. Major Prevalence from 1.0 % to 9.9 % for Canada, 10.9 %–45.5 % for France, from 2.1 % to 19.9 % for the United States of America, from 1.4 % to 72.7 % for Singapore, from 1.8 % to 20.4 % for the United Kingdom, and from 1.8 % to 22.9 % for Sweden is observed. This variant is spreading rapidly and is anticipated to cause a surge in SARS-CoV-2 cases and overlap with other viral and bacterial infections, especially in countries entering the winter season [154,155]. So it is crucial to review and prepare hospital isolation wards with sufficient and more efficient negative pressure wards for unpredicted infection outbreaks [156].
6.2. Portable air purifiers and air filters
Recent findings show that air cleaners or mechanical ventilation equipped with a combination of pre-filters, High-Efficiency Particulate Air (HEPA) filters, and four-cylinder gas filter cartridges can reduces formaldehyde, odors, and TVOC, PM2.5 and improve indoor air quality in clinics [157,158]. Air purifiers used with HVAC systems in hospitals may enhance the indoor hygiene by reducing air contaminants [159]. Portable air purifiers can be a supplementary measure to reduce the exposure risk of multiple airborne indoor air pollutants in hospital settings, particularly when aerosol transmission control not possible by HVAC [[160], [161], [162], [163]].
HEPA filters with the highest MERV rating, ultra-low particulate air filters (ULPA), and ultraviolet air filtration ionizers, alone or in combination showed significant impact, ranging from 12 to 99 % on indoor bioaerosol and other pollutants. Research showed HEPA filter capacity can be increased by ultraviolet radiation, with coating material such as covered with tannic acid and air ionizers [164,165,166].
Highly infectious SARS-CoV-2 viral RNA in the air of intensive care units and corridors could be difficult to remove by conventional air cleaning method [167]. Airborne pathogenic bacteria, fungi, and viruses could be around 5–34 % of total indoor air pollution. Experiments show the highest bacterial (829–4980 CFU/m3) and fungal levels (90–920 CFU/m3) in OPDs while the lowest concentration in OTs [168]. Therefore, germicidal treatment of filtered air by ionization and UV radiation is suggested [169].
6.3. Bipolar air ionization, ultraviolet germicidal irradiation (UVGI) and electric precipitations
Air ionization has been a low-maintenance and effective technique to decrease several indoor air pollutants, especially, bipolar ionization which gain significant attention during the COVID-19 pandemic and was installed in many places including hospitals. Bipolar air ionizers produce both positive and negative ions that react with various airborne contaminants (Fig. 8) including volatile organic compounds, particulate matter, and airborne pathogens [170].
Fig. 8.
Air ions associated possible deactivation of airborne contaminates.
The evidence of bipolar air ionizers’ air cleaning efficacies is growing, and disinfection capacity against E.coli, S. typhimurium, and S. epidermidis is promising. Yet, the potential byproduct of O3 might be associated with some air ionization devices operation [171,172].
Ultraviolet germicidal irradiation (UVGI) or Ultraviolet C has been known for shorter wave length (100–280 nm) and highest disinfectant capacity than UV-A and UV-B rays. UVC usually absorb by pathogen nucleic acids (DNA, RNA), which halted their ability to replicate. A large number of pathogens have been found sensitive to UVC, although highly dependent on UVC dose. UVC disinfectant has shown 99.99 % germ eradication. UVC equipment has been successfully employed in hospitals wards for decontaminations [173]. Additionally, UVC and air ions combination may lead to higher inactivation against fastidious airborne pathogens [174].
Electrostatic precipitation (ESP) is an electric field-based technique that charged airborne pollutants in a gaseous medium, conventionally used in industries to manage the smoke and particulate pollutants. In the presence of an electric field charged pollutants are directed towards a metallic collection plate. However, compared to bipolar air ionization and HEPA, ESP may be considered less efficient when indoor pollution is high. Moreover, byproducts like ozone generation during corona discharge are still a challenging phenomenon [175].
7. Advanced HVAC system
Poorly designed HVAC may be responsible for to spread of nosocomial infections as a strong correlation is found between ventilation and air movement in buildings. Most conventional HVAC systems focus on air temperature and CO2. Though other parameters such as RH, negative pressure, air flow rate, laminar flow ceiling, and Local exhaust ventilation to remove anesthetic gases, special HVAC designs for OTs are recommended to enhance the HVAC performance [176].
Studies indicated that additional filtration and disinfectant amalgamation may enhance the HVAC capacity. For instance, air changes per hour (ACH), Table 1 [177], and the use of heat pipe heat exchangers with HVAC may increase the indoor contamination reduction. In addition, uses of HEPA or ULPA with central HVAC or within the room via portable air purifier, Laminar air flow at celling of emergency wards, controlled and constant relative humidity, UV light treatment of air stream, and displaced ventilation instead of mixed ventilation can enhance the indoor air quality and hygiene in hospitals [178].
8. Photocatalytic oxidation (PCO), plants and Trombe wall role to manage nearby outdoor air pollutants
Parking area near healthcare may be responsible to increase the exposure risk from parked vehicle emission. Photocatalytic oxidation (PCO) air cleaning technology has been considered a feasible and energy-efficient method to improve Air Quality. Photocatalysts such as TiO2 oxidation reactions can convert/breakdown the airborne pollutants into CO2 and water molecules. Photocatalytic oxidation can be useful to improve air quality in hospitals, especially to reduce hospital-borne pollutants such as anesthetic gas, and isoflurane [179]. Photocatalytic oxidation-based air cleaning systems' positive effects in hospitals and clinics are growing. Photocatalyst TiO2 nanoparticles and optical fibers were found effective in glutaraldehyde and Chloroform removal [180]. Another similar study also suggested that Photocatalyst TiO2, with plasma, and UV can remove the hazardous chloroform from hospitals [181].
Plants are the natural air cleaner and able to reduce decrease certain air pollutants by phytoremediation which involved dilution, absorption, filtration, and precipitation. Thus in certain areas, such as near hospital entrance and corridor, plants may increase the occupants comfort by reducing certain indoor air pollutants. However, indoor plants may posse potential health risks [182,183].
Substantial energy is consumed by buildings to maintain an indoor environment comfortable, especially thermal comfort. Trombe wall might be a sustainable solution to support and enhance HVAC system efficiency in certain regions [184]. The Trombe wall contains breathing wall panels that also filter air along with heat. Trombe walls facilitate a higher ventilation level for buildings associated with a large reaction area, thus improving indoor air quality by reducing energy consumption [185].
9. Organic pollutants abatement by passive removal materials (PRMs)
Indoor organic pollutant removal is not always possible through source control and ventilation. To overcome the issue of indoor air pollutants an energy-efficient method Passive removal materials (PRMs) have been proposed by various research. These materials efficiently remove organic pollutants without by-product formation and with minimal energy consumption [186,187].
These Materials usually are clay-based bricks, plasters, calcareous stone, activated carbon, mineral fibers or volcanic perlite, and manganese oxides. Studies showed that PRMs decomposed formaldehyde and ozone when employed as clay paint on walls, and ceiling tile panels in buildings at room temperature without mechanical intervention [[186], [188], [189], [190]].
Sorbent sinks made by activated carbon remove Volatile Organic Compounds (VOC) such as acetone and formic acid, acetic acid, toluene, and alpha-pinene from the air [[191], [192], [193]].
Nanomaterial-based biosorbents may also be used for viral droplets inactivation due to their broad-spectrum antiviral capabilities [194]. Nanomaterials may block the aerosol transmission route of the virus and deactivate viruses via the generation of ROS, physical contact, photo-thermal effects, catalytic oxidation, and metal ion release. Such nanomaterials can also be applied to building ventilation systems, air purifier filters, anti-viral fabrics, and anti-viral sprays [195,196].
However, PRM practicality and inactivation of SARS-CoV-2 in hospital wards remain the subject of extensive research.
10. Air cleaning Intervention in Emergency Health Vehicles
The potential health risk of in-cabin PM2.5 and other contaminants exposure in emergency vehicles for medical staff cannot be neglected. Emergency health vehicles or ambulances are an important part of health care facilities and a vulnerable source of many airborne microbial contaminants due to the exposure to patients’ secretions i.e. blood, excreta, respiratory droplets, medical waste etc. Ambulance-associated infections not only create a risk for patients and paramedical staff but also a significant financial burden on the entire healthcare system. Various internal parts of ambulance may be reservoir and responsible for contaminants dispersion, Fig. 9 (a). The most common difficult-to-treat ambulance-acquired infection is methicillin-resistant Staphylococcus aureus (MRSA) [197]. Airborne bacterial and fungal load is comparatively high when ambulances run with patients, indoor CFU can reach up to 468 ± 607 cfu/m3 for bacteria and 656 ± 612 cfu/m3 for fungi. However other air pollutants such as particulate can affect the indoor air quality of ambulances [198,199]. Disinfectants residues such as hydrogen peroxide mist can also affect the indoor air quality [200].
Fig. 9.
The potential reservoir of contaminants in ambulance cabin (a); air contaminants control with inbuilt HEPA and Air ionizer in cabin (Image is retrieved and modified from Zhou et al., 2022, https://www.mdpi.com/2071-1050/September%2014,%204900).
A recent pilot study shows that a vehicle's heating, ventilation, and air-conditioning (HVAC) system with filters with a high minimum efficiency reporting value (MERV) can reduce in-cabin pollutants, allergens, and airborne viral particles. In addition, portable air purifiers may efficiently remove PM2.5 by 42–74 %, less than the 15 μg/m3 threshold recommended by the WHO [201]. Ambulance services can be affected in highly polluted countries; a significant toxic effect of PM2.5 with hot and humid climate has been observed [202].
The technique such as negative pressure has been useful to check contamination spread. Negative pressure involved a fan with a high-efficiency filtration device (HEPA) to filter the air in the cabin and create low cabin pressure to minimize the highly contagious viral droplet exposure. Such filtration may minimize the viral contaminants exposure. Such filtration may minimize the viral contaminants exposure, but limitations like insufficient airflow, uncertain distribution of droplet particles, and patient coughs or sneezes during mask change may increase the risk to medical health workers [203]. A safe real-time germicidal and decontamination system could be helpful to minimize continuous exposure to biological and chemical contaminants during patient transportation. For instance, a bipolar ionization unit may be useful as an additional tool to reduce/deactivate airborne pathogens which managed to escape due to low airflow and HEPA malfunction, Fig. 9 (b).
A recent experiment showed that bipolar ionization and higher CADR of air cleaning devices were able to reduce environmental bioaerosols in public vehicle like tramps [204].Growing research is showing that bipolar air ionization may be a low-maintenance and effective air-cleaning intervention to abate a variety of biological (including Clostridioides difficile, Klebsiella pneumoniae, MRSA, carbapenemase-producing K. pneumoniae, and multi-drug-resistant S. aureus) and chemical contaminants [[205], [206], [207]]. Studies are adding evidence that appropriate ventilation with air-cleaning devices could lower the chance of occupants' associated airborne pathogens and tracer gas exposure [208].
11. Conclusion
The amalgamation of recent air cleaning technologies including increased ventilation, modified air filters with the highest MERV, bipolar air ionization, Passive Removal Materials, irradiation, negative air pressure, and specified HVAC standards for different wards may help to eliminate the risk of airborne contaminates and other indoor air pollutants in health care facilities. These strategies proposed a potential solution for unpredicted airborne COVID-19-like outbreaks. However, the practicality of these techniques may be subjected to further extensive research.
Funding
The current work was assisted financially to the Dean of Science and Research at the King Khalid University via the large group project under the grant number RGP.2/409/45.
CRediT authorship contribution statement
Nishant Gupta: Writing – original draft, Project administration, Methodology, Data curation, Conceptualization. N.S. Abd EL-Gawaad: Writing – review & editing, Resources, Investigation, Formal analysis. L.O. Mallasiy: Writing – review & editing, Visualization, Validation, Supervision.
Declaration of competing interest
Authors declare no conflict of interest.
Acknowledgments
Authors NG, NA and LO are grateful to the medical research department of River Engineering to provide basic facilities for this research. The authors extend their appreciation to the Deanship of Scientific Research at King Khalid University for the funding this work through large groups project under grant number RGP.2/409/45.
Contributor Information
Nishant Gupta, Email: micronishant@yahoo.in.
N.S. Abd EL-Gawaad, Email: nshat@kku.edu.sa.
L.O. Mallasiy, Email: lohosain@kku.edu.sa.
References
- 1.Dascalaki E.G., Lagoudi A., Balaras C.A., Gaglia A.G. Air quality in hospital operating rooms. Build. Environ. 2008 Nov 1;43(11):1945–1952. doi: 10.1016/j.buildenv.2007.11.015. [DOI] [Google Scholar]
- 2.Ana G.R., Fakunle G.A., Ogunjobi A.A. Indoor airborne microbial burden and risk of acute respiratory infections among children under five in Ibadan, Nigeria. Indoor Built Environ. 2015;24:308–314. doi: 10.1177/1420326X13499171. [DOI] [Google Scholar]
- 3.Aktar F., Tekin R., Güneş A., Ülgen C., Tan İ., Ertuğrul S., Köşker M., Balık H., Karabel D., Yolbaş I. Determining the independent risk factors and mortality rate of nosocomial infections in pediatric patients. BioMed Res. Int. 2016;2016 doi: 10.1155/2016/7240864. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 4.Nuckchady D.C. Incidence, risk factors, and mortality from hospital-acquired infections at a hospital in Mauritius. Cureus. 2021 Nov 28;13(11) doi: 10.7759/cureus.19962. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 5.Cevik M.A., Yilmaz G.R., Erdinc F.S., Ucler S., Tulek N.E. Relationship between nosocomial infection and mortality in a neurology intensive care unit in Turkey. J. Hosp. Infect. 2005 Apr;59(4):324–330. doi: 10.1016/j.jhin.2004.10.012. PMID: 15749321. [DOI] [PubMed] [Google Scholar]
- 6.Bonadonna L., Briancesco R., Coccia A.M., Meloni P., Rosa G., Moscato U. Microbial air quality in healthcare facilities. Int J Environ Res Public Health. 2021 Jun 9;18(12):6226. doi: 10.3390/ijerph18126226. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 7.Hiwar W., King M.F., Shuweihdi F., Fletcher L.A., Dancer S.J., Noakes C.J. What is the relationship between indoor air quality parameters and airborne microorganisms in hospital environments? A systematic review and meta-analysis. Indoor Air. 2021 Sep;31(5):1308–1322. doi: 10.1111/ina.12846. [DOI] [PubMed] [Google Scholar]
- 8.Ponsford M.J., Ward T.J.C., Stoneham S.M., Dallimore C.M., Sham D., Osman K., Barry S.M., Jolles S., Humphreys I.R., Farewell D. A systematic review and meta-analysis of inpatient mortality associated with nosocomial and community COVID-19 exposes the vulnerability of immunosuppressed adults. Front. Immunol. 2021 Oct 6;12 doi: 10.3389/fimmu.2021.744696. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 9.Tran V.V., Park D., Lee Y.C. Indoor air pollution, related human diseases, and recent trends in the control and improvement of indoor air quality. Int J Environ Res Public Health. 2020 Apr 23;17(8):2927. doi: 10.3390/ijerph17082927. PMID: 32340311; PMCID: PMC7215772. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 10.Jarvis W., Gray L., Culver D., et al. Nosocomial infection mortality on pediatric services in the United States, 1975-1983. Pediatr. Res. 1984;18(Suppl 4):278. doi: 10.1203/00006450-198404001-01111. [DOI] [Google Scholar]
- 11.World Health Organization Global report on infection prevention and control. https://www.who.int/publications/i/item/9789240051164
- 12.Jung C.C., Wu P.C., Tseng C.H., Su H.J. Indoor air quality varies with ventilation types and working areas in hospitals. Build. Environ. 2015;85:190–195. doi: 10.1016/j.buildenv.2014.11.026. [DOI] [Google Scholar]
- 13.Lomboy M.F., Quirit L.L., Molina V.B., Dalmacion G.V., Schwartz J.D., Suh H.H., Baja E.S. Characterization of particulate matter 2.5 in an urban tertiary care hospital in the Philippines. Build. Environ. 2015;92:432–439. doi: 10.1016/j.buildenv.2015.05.018. Oct 1. [DOI] [Google Scholar]
- 14.Śmiełowska M., Marć M., Zabiegała B. Indoor air quality in public utility environments—a review. Environ. Sci. Pollut. Control Ser. 2017;24:11166–11176. doi: 10.1007/s11356-017-8567-7. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 15.Feng Z., Wei F., Li H., Yu C.W. Evaluation of indoor disinfection technologies for airborne disease control in hospital. Indoor Built Environ. 2021;30:727–731. doi: 10.1177/1420326X211002948. [DOI] [Google Scholar]
- 16.Dillon CF, Dillon MB. Multiscale Airborne infectious disease transmission. Applied and Environmental Microbiology 202; 87: 02314-20. DOI: 10.1128/AEM.02314-20. [DOI] [PMC free article] [PubMed]
- 17.Taushiba A., Dwivedi S., Zehra F., Shukla P.N., Lawrence A.J. Assessment of indoor air quality and their inter-association in hospitals of northern India-a cross-sectional study. Air Qual Atmos Health. 2023;16(5):1023–1036. doi: 10.1007/s11869-023-01321-4. Epub 2023 Mar 4. PMID: 37213469. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 18.Zhang J., Day D. In: Air Pollution and Health Effects. Molecular and Integrative Toxicology. Nadadur S., Hollingsworth J., editors. Springer; London: 2015. Urban air pollution and health in developing countries. [DOI] [Google Scholar]
- 19.Obenza A., Cruz P., Buttner M., Woodard D. Microbial contamination on ambulance surfaces: a systematic literature review. J. Hosp. Infect. 2022;122:44–59. doi: 10.1016/j.jhin.2021.12.020. [DOI] [PubMed] [Google Scholar]
- 20.Saran S., Gurjar M., Baronia A., Sivapurapu V., Ghosh P.S., Raju G.M., Maurya I. Heating, ventilation and air conditioning (HVAC) in intensive care unit. Crit. Care. 2020 May 6;24(1):194. doi: 10.1186/s13054-020-02907-5. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 21.Wu H.T., Li Q.S., Dai R.C., Liu S., Wu L., Mao W., Ji C.H. Effects of air-conditioning systems in the public areas of hospitals: a scoping review. Epidemiol. Infect. 2021 Jan;149:e201. [Google Scholar]
- 22.Rebmann T. Management of patients infected with airborne-spread diseases: an algorithm for infection control professionals. Am. J. Infect. Control. 2005 Dec;33(10):571–579. doi: 10.1016/j.ajic.2005.05.015. PMID: 16330305; PMCID: PMC7119117. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 23.Ather B., Mirza T.M., Edemekong P.F. StatPearls [Internet]. Treasure Island (FL) StatPearls Publishing; 2024 Jan. Airborne precautions. 2023 mar 13. PMID: 30285363. [PubMed] [Google Scholar]
- 24.Palmisani J., Di Gilio A., Viana M., de Gennaro G., Ferro A. Indoor air quality evaluation in oncology units at two European hospitals: low-cost sensors for TVOCs, PM2. 5 and CO2 real-time monitoring. Build. Environ. 2021;205 doi: 10.1016/j.buildenv.2021.108237. [DOI] [Google Scholar]
- 25.Sangkharat K., Fisher P., Thomas G.N., Thornes J., Pope F.D. The impact of air pollutants on ambulance dispatches: a systematic review and meta-analysis of acute effects. Environ. Pollut. 2019 Nov;254(Pt A) doi: 10.1016/j.envpol.2019.06.065. Epub 2019 Jun 20. PMID: 31419665. [DOI] [PubMed] [Google Scholar]
- 26.Moscato U., Borghini A., Teleman A.A. In: Indoor Air Quality in Healthcare Facilities. SpringerBriefs in Public Health. Capolongo S., Settimo G., Gola M., editors. Springer; Cham: 2017. HVAC management in health facilities. [DOI] [Google Scholar]
- 27.Joppolo C.M., Romano F. In: Indoor Air Quality in Healthcare Facilities. SpringerBriefs in Public Health. Capolongo S., Settimo G., Gola M., editors. Springer; Cham: 2017. HVAC system design in healthcare facilities and control of aerosol contaminants: issues, tools, and experiments. [DOI] [Google Scholar]
- 28.Kelkar U., Bal A.M., Kulkarni S. Fungal contamination of air conditioning units in operating theatres in India. J. Hosp. Infect. 2005 May;60(1):81–84. doi: 10.1016/j.jhin.2004.10.011. [DOI] [PubMed] [Google Scholar]
- 29.Dubey S., Rohra H., Taneja A. Assessing effectiveness of air purifiers (HEPA) for controlling indoor particulate pollution. Heliyon. 2021;7 doi: 10.1016/j.heliyon.2021.e07976. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 30.Guo J., Xiong Y., Kang T., Xiang Z., Qin C. Bacterial community analysis of floor dust and HEPA filters in air purifiers used in office rooms in ILAS, Beijing. Sci. Rep. 2020;10:6417. doi: 10.1038/s41598-020-63543-1. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 31.Morawska L., Tang J.W., Bahnfleth W., Bluyssen P.M., Boerstra A., Buonanno G., Cao J., Dancer S., Floto A., Franchimon F., Haworth C., Hogeling J., Isaxon C., Jimenez J.L., Kurnitski J., Li Y., Loomans M., Marks G., Marr L.C., Mazzarella L., Melikov A.K., Miller S., Milton D.K., Nazaroff W., Nielsen P.V., Noakes C., Peccia J., Querol X., Sekhar C., Seppänen O., Tanabe S.I., Tellier R., Tham K.W., Wargocki P., Wierzbicka A., Yao M. How can airborne transmission of COVID-19 indoors be minimised? Environ. Int. 2020 Sep;142 doi: 10.1016/j.envint.2020.105832. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 32.Lee H.J., Lee K.H., Kim D.K. Evaluation and comparison of the indoor air quality in different areas of the hospital. Medicine (Baltim.) 2020;99 doi: 10.1097/MD.0000000000023942. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 33.El-Sharkawy M.F., Noweir M.E. Indoor air quality levels in a university hospital in the eastern province of Saudi arabia. J Family Community Med. 2014;21:39–47. doi: 10.4103/2230-8229.128778. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 34.Mohammadyan M., Keyvani S., Bahrami A., Yetilmezsoy K., Heibati B., Godri Pollitt K.J. Assessment of indoor air pollution exposure in urban hospital microenvironments. Air Quality, Atmosphere & Health. 2019;12:151–159. doi: 10.1007/s11869-018-0637-6. [DOI] [Google Scholar]
- 35.Zhang Z.F., Zhang X., Zhang X.M., Liu L.Y., Li Y.F., Sun W. Indoor occurrence and health risk of formaldehyde, toluene, xylene and total volatile organic compounds derived from an extensive monitoring campaign in Harbin, a megacity of China. Chemosphere. 2020;250 doi: 10.1016/j.chemosphere.2020.126324. [DOI] [PubMed] [Google Scholar]
- 36.Ab Manan N., Noor Aizuddin A., Hod R. Effect of air pollution and hospital admission: a systematic review. Ann Glob Health. 2018;84:670–678. doi: 10.9204/aogh.2376. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 37.Scarlett H.P., Postlethwait E., Delzell E., Sathiakumar N., Oestenstad R.K. Asbestos in public hospitals: are employees at risk? J. Environ. Health. 2012 Jan-Feb;74(6):22–26. http://www.jstor.org/stable/26329340 [PubMed] [Google Scholar]
- 38.Taghizadeh F., Jafari A.J., Gholami M., Kermani M., Arfaeinia H., Mohammadi S.…Shahsavani A. Monitoring of airborne asbestos fibers in an urban ambient air of Shahryar City, Iran: levels, spatial distribution, seasonal variations, and health risk assessment. Environ. Sci. Pollut. Control Ser. 2019;26:6450–6459. doi: 10.1007/s11356-018-4029-0. [DOI] [PubMed] [Google Scholar]
- 39.US EPA Indoor air quality (IAQ) https://www.epa.gov/indoor-air-quality-iaq/publications-about-indoor-air-quality
- 40.OSHA. Indoor Air Quality. Chrome extension://efaidnbmnnnibpcajpcglclefindmkaj/https://www.osha.gov/sites/default/files/publications/3430indoor-air-quality-sm.pdf (accessed November 21, 2022).
- 41.Peña-Castro M., Montero-Acosta M., Saba M. A critical review of asbestos concentrations in water and air, according to exposure sources. Heliyon. 2023 Apr 25;9(5) doi: 10.1016/j.heliyon.2023.e15730. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 42.Chung J.Y., Yu S.D., Hong Y.S. Environmental source of arsenic exposure. J Prev Med Public Health. 2014 Sep;47(5):253–257. doi: 10.3961/jpmph.14.036. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 43.CDC Chapter 5: indoor air pollutants and toxic materials. https://www.cdc.gov/nceh/publications/books/housing/cha05.htm
- 44.Bundschuh J., Schneider J., Alam M.A., Niazi N.K., Herath I., Parvez F.…Mukherjee A. Seven potential sources of arsenic pollution in Latin America and their environmental and health impacts. Sci. Total Environ. 2021;780 doi: 10.1016/j.scitotenv.2021.146274. [DOI] [PubMed] [Google Scholar]
- 45.Wang Y., Yu J., Wang Z., Liu Y., Zhao Y. A review on arsenic removal from coal combustion: advances, challenges and opportunities. Chem. Eng. J. 2021 Jun 15;414 [Google Scholar]
- 46.Alka S., Shahir S., Ibrahim N., Ndejiko M.J., Vo D.V., Abd Manan F. Arsenic removal technologies and future trends: a mini review. J. Clean. Prod. 2021 Jan 1;278 [Google Scholar]
- 47.Abu-Rub L.I., Johar A.A., Al Mana H., Abdelrahman H.A., Althani A.A., Qotba H., Yassine H.M., Eltai N.O. Bacterial indoor air contaminations in hospitals in MENA region: a systematic review. Int. J. Environ. Health Res. 2023 Dec;33(12):1218–1232. doi: 10.1080/09603123.2022.2083087. [DOI] [PubMed] [Google Scholar]
- 48.Qian H., Li Y., Seto W.H., Ching P., Ching W.H., Sun H.Q. Natural ventilation for reducing airborne infection in hospitals. Build. Environ. 2010 Mar;45(3):559–565. doi: 10.1016/j.buildenv.2009.07.011. Epub 2009 Jul 23. PMID: 32288008. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 49.Qian H., Li Y., Nielsen P.V., Hyldgaard C.E. Dispersion of exhalation pollutants in a two-bed hospital ward with a downward ventilation system. Build. Environ. 2008 Mar 1;43(3):344–345. [Google Scholar]
- 50.Zia H., Singh R., Seth M., Ahmed A., Azim A. Engineering solutions for preventing airborne transmission in hospitals with resource limitation and demand surge. Indian J. Crit. Care Med. 2021 Apr;25(4):453–460. doi: 10.5005/jp-journals-10071-23792. PMID: 34045813. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 51.Riveron T.P., Wilde M.J., Ibrahim W., Carr L., Monks P.S., Greening N.J., Gaillard E.A., Brightling C.E., Siddiqui S., Hansell A.L., Cordell R.L. Characterisation of volatile organic compounds in hospital indoor air and exposure health risk determination. Build. Environ. 2023 Jun 8 doi: 10.1016/j.buildenv.2023.110513. [DOI] [Google Scholar]
- 52.Wang H., Feng D., He Y., Jin X., Fu S. Comprehensive interventions to reduce occupational hazards among medical staff in the pathology department of five primary hospitals. BMC Publ. Health. 2023 Oct 31;23(1):2136. doi: 10.1186/s12889-023-16948-2. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 53.Dumas O., Despreaux T., Perros F., Lau E., Andujar P., Humbert M., Montani D., Descatha A. Respiratory effects of trichloroethylene. Respir. Med. 2018;134:47–53. doi: 10.1016/j.rmed.2017.11.021. [DOI] [PubMed] [Google Scholar]
- 54.Kharel M., Chalise S., Chalise B., Sharma K.R., Gyawali D., Paudyal H., Neupane B.B. Assessing volatile organic compound level in selected workplaces of Kathmandu Valley. Heliyon. 2021;7 doi: 10.1016/j.heliyon.2021.e08262. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 55.WHO WHO guidelines for indoor air quality: household fuel combustion. https://www.who.int/publications-detail-redirect/9789241548885 [PubMed]
- 56.Bahadar H., Mostafalou S., Abdollahi M. Current understandings and perspectives on non-cancer health effects of benzene: a global concern. Toxicol. Appl. Pharmacol. 2014;276:83–94. doi: 10.1016/j.taap.2014.02.012. [DOI] [PubMed] [Google Scholar]
- 57.Ban J., Su W., Zhong Y., Liu C., Li T. Ambient formaldehyde and mortality: a time series analysis in China. Sci. Adv. 2022;8 doi: 10.1126/sciadv.abm4097. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 58.Dikmen Ç.B., Gültekin A.B. Sustainable indoor air quality (IAQ) in hospital buildings. Survival and Sustainability: Environmental concerns in the 21st Century. 2011:557–565. [Google Scholar]
- 59.Abadi M.B., Shirkhanloo H., Rakhtshah J. Air pollution control: the evaluation of TerphApm@ MWCNTs as a novel heterogeneous sorbent for benzene removal from air by solid phase gas extraction. Arab. J. Chem. 2020 Jan 1;13(1):1741–1751. [Google Scholar]
- 60.Gallego E., Roca F.J., Perales J.F., Guardino X. Experimental evaluation of VOC removal efficiency of a coconut shell activated carbon filter for indoor air quality enhancement. Build. Environ. 2013 Sep 1;67:14–25. [Google Scholar]
- 61.Yau Y.H., Phuah K.S. Indoor air quality study in four Malaysian hospitals for centralized and non-centralized ACMV systems. Air Qual Atmos Health. 2023;16:375–390. doi: 10.1007/s11869-022-01280-2. [DOI] [Google Scholar]
- 62.Kleinman M.T. Carbon monoxide. Environmental Toxicants: Human Exposures and Their Health Effects. 2020:455–486. doi: 10.1002/9781119438922.ch12. [DOI] [Google Scholar]
- 63.Li P., Miser D.E., Rabiei S., Yadav R.T., Hajaligol M.R. The removal of carbon monoxide by iron oxide nanoparticles. Applied Catalysis B: Environmental. 2003 Jun 30;43(2):151–162. [Google Scholar]
- 64.Oyama I., Tajima Y., Ojima T., Iida A. Exposure to high concentrations of carbon dioxide during transporting a cadaver preserved with dry ice inside an ambulance vehicle. Forensic Toxicol. 2023;41(1):179–182. doi: 10.1007/s11419-022-00644-8. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 65.Langford N.J. Carbon dioxide poisoning. Toxicol. Rev. 2005;24:229–235. doi: 10.2165/00139709-200524040-00003. [DOI] [PubMed] [Google Scholar]
- 66.Salaudeen S.A., Acharya B., Dutta A. CaO-based CO2 sorbents: a review on screening, enhancement, cyclic stability, regeneration and kinetics modelling. J. CO2 Util. 2018 Jan 1;23:179–199. [Google Scholar]
- 67.Gall E.T., Sonat C., Nazaroff W.W., Unluer C. Investigating CO2 removal by Ca-and Mg-based sorbents with application to indoor air treatment. Build. Environ. 2016 Dec 1;110:161–172. [Google Scholar]
- 68.Shin M.S., Rhee K.N., Lee E.T., Jung G.J. Performance evaluation of CO2-based ventilation control to reduce CO2 concentration and condensation risk in residential buildings. Build. Environ. 2018 Sep 1;142:451–463. [Google Scholar]
- 69.Hamid N., Pei D.S. Reservoir Ecotoxicology. Springer; Cham: 2023. Main sources and distribution of pollutants in the reservoir. [DOI] [Google Scholar]
- 70.Park S.K., O'Neill M.S., Vokonas P.S., Sparrow D., Wright R.O., Coull B., Nie H., Hu H., Schwartz J. Air pollution and heart rate variability: effect modification by chronic lead exposure. Epidemiology. 2008;19:111–120. doi: 10.1097/EDE.0b013e31815c408a. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 71.Bhave P.P., Yeleswarapu D. Removal of indoor air pollutants using activated carbon—a review. Global Challenges in Energy and Environment: Select Proceedings of ICEE. 2018. 2020:65–75. [Google Scholar]
- 72.Norton P., Pinho P., Xará D., Pina F., Norton M. Assessment of anesthetic gases in a central hospital. Porto Biomed J. 2020 Jul 17;5(4):e076. doi: 10.1097/j.pbj.0000000000000076. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 73.Kiani F., Jorfi S., Soltani F., Ghanbari S., Rezaee R., Mohammadi M.J. Exposure to anesthetic gases in the operating rooms and assessment of non-carcinogenic risk among health care workers. Toxicol Rep. 2023 Jun 10;11:1–8. doi: 10.1016/j.toxrep.2023.06.007. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 74.Yao Y., Pan J., Liu Z., Meng X., Wang W., Kan H., Wang W. Ambient nitrogen dioxide pollution and spreadability of COVID-19 in Chinese cities. Ecotoxicol. Environ. Saf. 2021;208 doi: 10.1016/j.ecoenv.2020.111421. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 75.Vîrghileanu M., Săvulescu I., Mihai B.-A., Nistor C., Dobre R. Nitrogen dioxide (NO2) pollution monitoring with sentinel-5P satellite imagery over europe during the coronavirus pandemic outbreak. Rem. Sens. 2020;12:3575. doi: 10.3390/rs12213575. [DOI] [Google Scholar]
- 76.Whyte H.E., Raillard C., Subrenat A., Héquet V. Photocatalytic oxidation of isoflurane, an anesthetic gas: the influence of operating parameters. Chem. Eng. J. 2018 Nov 15;352:441–449. [Google Scholar]
- 77.Ang T.N., Baroutian S., Young B.R., Hyland M.M., Taylor M., Burrell R. Adsorptive separation of volatile anaesthetics: a review of current developments. Separ. Purif. Technol. 2019 Mar 18;211:491–503. [Google Scholar]
- 78.Gilden R.C. Pesticides use in hospitals: health protection, health hazards, and viable alternatives. Nurs. Adm. Q. 2010 Oct-Dec;34(4):320–326. doi: 10.1097/NAQ.0b013e3181f56330. [DOI] [PubMed] [Google Scholar]
- 79.Kim K.H., Kabir E., Jahan S.A. Exposure to pesticides and the associated human health effects. Sci. Total Environ. 2017;1(575):525–535. doi: 10.1016/j.scitotenv.2016.09.009. [DOI] [PubMed] [Google Scholar]
- 80.Oudejans L., Mysz A., Snyder E.G., Wyrzykowska-Ceradini B., Nardin J., Tabor D., Starr J., Stout I.I.D., Lemieux P. Remediating indoor pesticide contamination from improper pest control treatments: persistence and decontamination studies. J. Hazard Mater. 2020 Oct 5;397 doi: 10.1016/j.jhazmat.2020.122743. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 81.Sleiman M., Ferronato C., Chovelon J.M. Photocatalytic removal of pesticide dichlorvos from indoor air: a study of reaction parameters, intermediates and mineralization. Environ. Sci. Technol. 2008 Apr 15;42(8):3018–3024. doi: 10.1021/es702425q. [DOI] [PubMed] [Google Scholar]
- 82.84. Butler M.J., Sloof D., Peters C., Conway Morris A., Gouliouris T., Thaxter R., Keevil V.L., Beggs C.B. Impact of supplementary air filtration on aerosols and particulate matter in a UK hospital ward: a case study. J. Hosp. Infect. 2023 May;135:81–89. doi: 10.1016/j.jhin.2023.02.006. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 83.Hamanaka R.B., Mutlu G.M. Particulate matter air pollution: effects on the cardiovascular system. Front. Endocrinol. 2018;9:680. doi: 10.3389/fendo.2018.00680. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 84.Shiue A., Hu S.C., Tseng C.H., Kuo E.H., Liu C.Y., Hou C.T., Yu T. Verification of air cleaner on-site modeling for PM2. 5 and TVOC purification in a full-scale indoor air quality laboratory. Atmos. Pollut. Res. 2019 Jan 1;10(1):209–218. [Google Scholar]
- 85.Huang C.H., Xiang J., Austin E., Shirai J., Liu Y., Simpson C., Karr C.J., Fyfe-Johnson A.L., Larsen T.K., Seto E. Impacts of using auto-mode portable air cleaner on indoor PM2. 5 levels: an intervention study. Build. Environ. 2021 Jan 15;188 [Google Scholar]
- 86.Galbadage T., Peterson B.M., Gunasekera R.S. Does COVID-19 spread through droplets alone? Front. Public Health. 2020 Apr 24;8:163. doi: 10.3389/fpubh.2020.00163. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 87.Rodríguez M., Palop M.L., Seseña S., Rodríguez A. Are the Portable Air Cleaners (PAC) really effective to terminate airborne SARS-CoV-2? Sci. Total Environ. 2021 Sep 1;785 doi: 10.1016/j.scitotenv.2021.147300. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 88.Blocken B., Van Druenen T., Ricci A., Kang L., Van Hooff T., Qin P., Xia L., Ruiz C.A., Arts J.H., Diepens J.F., Maas G.A. Ventilation and air cleaning to limit aerosol particle concentrations in a gym during the COVID-19 pandemic. Build. Environ. 2021 Apr 15;193 doi: 10.1016/j.buildenv.2021.107659. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 89.Dai H., Zhao B. Reducing airborne infection risk of COVID-19 by locating air cleaners at proper positions indoor: analysis with a simple model. Build. Environ. 2022 Apr 1;213 doi: 10.1016/j.buildenv.2022.108864. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 90.85. Alexandrino, Katiuska and Sanchez, Nazly and Viteri, Fausto, Levels and Sources of Polycyclic Aromatic Hydrocarbons (Pahs) Near Hospitals and Schools Using Leaves and Barks of Sambucus Nigra and Acacia Melanoxylon. 10.2139/ssrn.4383642. [DOI] [PMC free article] [PubMed]
- 91.Idowu O., Semple K.T., Ramadass K., O'Connor W., Hansbro P., Thavamani P. Beyond the obvious: environmental health implications of polar polycyclic aromatic hydrocarbons. Environ. Int. 2019;123:543–557. doi: 10.1016/j.envint.2018.12.051. [DOI] [PubMed] [Google Scholar]
- 92.Sadiktsis I., Nilsson G., Johansson U., Rannug U., Westerholm R. Removal of polycyclic aromatic hydrocarbons and genotoxic compounds in urban air using air filter materials for mechanical ventilation in buildings. Science and Technology for the Built Environment. 2016 Apr 2;22(3):346–355. [Google Scholar]
- 93.Parker J.K., Lignou S., Shankland K., Kurwie P., Griffiths H.D., Baines D.A. Development of a zeolite filter for removing polycyclic aromatic hydrocarbons (PAHs) from smoke and smoked ingredients while retaining the smoky flavor. J. Agric. Food Chem. 2017 Feb 18;66(10):2449–2458. doi: 10.1021/acs.jafc.6b05399. [DOI] [PubMed] [Google Scholar]
- 94.De Maria L., Sponselli S., Caputi A., Delvecchio G., Giannelli G., Pipoli A., Cafaro F., Zagaria S., Cavone D., Sardone R., et al. Indoor radon concentration levels in healthcare settings: the results of an environmental monitoring in a large Italian university hospital. Int. J. Environ. Res. Publ. Health. 2023;20(6):4685. doi: 10.3390/ijerph20064685. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 95.Minina V.I., Sinitsky M.Y., Druzhinin V.G., Fucic A., Bakanova M.L., Ryzhkova A.V., Savchenko Y.A., Timofeeva A.A., Titov R.A., Voronina E.N., Volobaev V.P., Titov V.A. Chromosome aberrations in peripheral blood lymphocytes of lung cancer patients exposed to radon and air pollution. Eur. J. Cancer Prev. 2018;27:6–12. doi: 10.1097/CEJ.0000000000000270. [DOI] [PubMed] [Google Scholar]
- 96.Chen T.M., Gokhale J., Shofer S., Kuschner W.G. Outdoor air pollution: nitrogen dioxide, sulfur dioxide, and carbon monoxide health effects. Am. J. Med. Sci. 2007;333:249–256. doi: 10.1097/MAJ.0b013e31803b900f. [DOI] [PubMed] [Google Scholar]
- 97.Khaniabadi Y.O., Polosa R., Chuturkova R.Z., Daryanoosh M., Goudarzi G., Borgini A.…Naserian P. Human health risk assessment due to ambient PM10 and SO2 by an air quality modeling technique. Process Saf. Environ. Protect. 2017;111:346–354. doi: 10.1016/j.psep.2017.07.018. [DOI] [Google Scholar]
- 98.Zhou Q., Zhao G., Xiao D., Qiu S., Lei Q., Kearfott K.J. Prediction of radon removal efficiency for a flow-through activated charcoal system and radon mitigation characteristics. Radiat. Meas. 2018 Dec 1;119:112–120. [Google Scholar]
- 99.Wang B., Song T., Li J., Zhang X., Li Y., Han X., Yang X. Design on intermittent ventilation strategy for radon removal in underground space. J. Environ. Radioact. 2022 Nov 1;253 doi: 10.1016/j.jenvrad.2022.107007. [DOI] [PubMed] [Google Scholar]
- 100.Namdari M., Lee C.S., Haghighat F. Active ozone removal technologies for a safe indoor environment: a comprehensive review. Build. Environ. 2021 Jan 1;187 [Google Scholar]
- 101.Chen L., Song Z., Zhou X., Yang G., Yu G. Pathogenic bacteria and fungi in bioaerosols from specialized hospitals in Shandong province, East China. Environ. Pollut. 2024 Jan 15;341 doi: 10.1016/j.envpol.2023.122922. [DOI] [PubMed] [Google Scholar]
- 102.AlRayess S., Sleiman A., Alameddine I., Abou Fayad A., Matar G.M., El-Fadel M. Airborne bacterial and PM characterization in intensive care units: correlations with physical control parameters. Air Qual Atmos Health. 2022;15(10):1869–1880. doi: 10.1007/s11869-022-01222-y. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 103.Śmiełowska M., Marć M., Zabiegała B. Indoor air quality in public utility environments—a review. Environ. Sci. Pollut. Control Ser. 2017;24:11166–11176. doi: 10.1007/s11356-019-06557-1. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 104.Ashuro Z., Diriba K., Afework A., Husen Washo G., Shiferaw Areba A., G/Meskel Kanno G., Hareru H.E., Kaso A.W., Tesfu M. Assessment of microbiological quality of indoor air at different hospital sites of dilla university: a cross-sectional study. Environ. Health Insights. 2022 May 18;16 doi: 10.1177/11786302221100047. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 105.Obbard J.P., Fang L.S. Airborne concentrations of bacteria in a hospital environment in Singapore. Water, Air, Soil Pollut. 2003;144:333–341. doi: 10.1023/A:1022973402453. [DOI] [Google Scholar]
- 106.Verde S.C., Almeida S.M., Matos J., Guerreiro D., Meneses M., Faria T., Botelho D., Santos M., Viegas C. Microbiological assessment of indoor air quality at different hospital sites. Res. Microbiol. 2015 Sep 1;166(7) doi: 10.1016/j.resmic.2015.03.004. 557-6. [DOI] [PubMed] [Google Scholar]
- 107.Breathnach A.S. Nosocomial infections and infection control. Medicine. 2013;41:649–653. doi: 10.1016/j.mpmed.2013.08.010. [DOI] [Google Scholar]
- 108.Wong S.C., Chan V.W., AuYeung C.H., Chen J.H., Yip C.C., So S.Y., Li X., Lung D.C., Tsang A.M., To K.K., Yuen K.Y., Cheng V.C. Air dispersal of respiratory viruses other than severe acute respiratory coronavirus virus 2 (SARS-CoV-2) and the implication on hospital infection control. Infect. Control Hosp. Epidemiol. 2023 May;44(5):768–773. doi: 10.1017/ice.2022.186. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 109.Hemati S., Mobini G.R., Heidari M., Rahmani F., Soleymani Babadi A., Farhadkhani M., Nourmoradi H., Raeisi A., Ahmadi A., Khodabakhshi A., Sadeghi M., Bagheri M., Validi M., Taghipour S., Mohammadi-Moghadam F. Simultaneous monitoring of SARS-CoV-2, bacteria, and fungi in indoor air of hospital: a study on Hajar Hospital in Shahrekord, Iran. Environ. Sci. Pollut. Res. Int. 2021 Aug;28(32):43792–43802. doi: 10.1007/s11356-021-13628-9. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 110.Aliramezani A., Talebi M., Golbabaei F., Baghani A., Marjani M., Afhami S., Hajabdolbaghi M., Boroumand M.A., Kuijper E.J., Douraghi M. Characterization of Clostridioides difficile isolates recovered from hospitalized patients and the hospitals environment and air: a multicenter study. Anaerobe. 2019 Oct;59:154–158. doi: 10.1016/j.anaerobe.2019.06.012. [DOI] [PubMed] [Google Scholar]
- 111.Mallach G., Kasloff S.B., Kovesi T., Kumar A., Kulka R., Krishnan J., Robert B., McGuinty M., den Otter-Moore S., Yazji B., Cutts T. Aerosol SARS-CoV-2 in hospitals and long-term care homes during the COVID-19 pandemic. PLoS One. 2021 Sep 30;16(9) doi: 10.1371/journal.pone.0258151. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 112.Wang Z., Kowal S.F., Carslaw N., Kahan T.F. Photolysis‐driven indoor air chemistry following cleaning of hospital wards. Indoor Air. 2020;30:1241–1255. doi: 10.1111/ina.12702. [DOI] [PubMed] [Google Scholar]
- 113.Bonsignore M., Hohenstein S., Kodde C., Leiner J., Schwegmann K., Bollmann A.…Nachtigall I. Burden of hospital-acquired SARS-CoV-2 infections in Germany: occurrence and outcomes of different variants. J. Hosp. Infect. 2022;129:82–88. doi: 10.1016/j.jhin.2022.08.004. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 114.Garrido A.N., House R., Lipszyc J.C., Liss G.M., Holness D.L., Tarlo S.M. Cleaning agent usage in healthcare professionals and relationship to lung and skin symptoms. J. Asthma. 2021;59(4):673–681. doi: 10.1080/02770903.2021.1871740. [DOI] [PubMed] [Google Scholar]
- 115.Mwanga H.H., Dumas O., Migueres N., Le Moual N., Jeebhay M.F. Airway diseases related to the use of cleaning agents in occupational settings. J. Allergy Clin. Immunol. Pract. 2024 doi: 10.1016/j.jaip.2024.02.036. Mar 2:S2213-2198(24)00214-9. [DOI] [PubMed] [Google Scholar]
- 116.Blass A.P., da Costa S.E., de Lima E.P., Borges L.A. Measuring environmental performance in hospitals: a practical approach. J. Clean. Prod. 2017 Jan 20;142:279–289. [Google Scholar]
- 117.Dancer S.J. The role of environmental cleaning in the control of hospital-acquired infection. J. Hosp. Infect. 2009 Dec;73(4):378–385. doi: 10.1016/j.jhin.2009.03.030. Epub 2009 Sep 1. PMID: 19726106. [DOI] [PubMed] [Google Scholar]
- 118.Yousefzadeh A., Maleki A., Athar S.D., Darvishi E., Ahmadi M., Mohammadi E.…Kashefi H. Evaluation of bio-aerosols type, density, and modeling of dispersion in inside and outside of different wards of educational hospital. Environ. Sci. Pollut. Control Ser. 2022:1–15. doi: 10.1007/s11356-021-16733-x. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 119.Leas B.F., Sullivan N., Han J.H., et al. Agency for Healthcare Research and Quality (US); Rockville (MD): 2015 Aug. Environmental Cleaning for the Prevention of Healthcare-Associated Infections [Internet]https://www.ncbi.nlm.nih.gov/books/NBK316172 (Technical Briefs, No. 22.) Background. Available from: [PubMed] [Google Scholar]
- 120.Boyce J.M. Modern technologies for improving cleaning and disinfection of environmental surfaces in hospitals. Antimicrob. Resist. Infect. Control. 2016;5:10. doi: 10.1186/s13756-016-0111-x. Published 2016 Apr 11. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 121.Shakeri A., Yip D., Badv M., Imani S.M., Sanjari M., Didar T.F. Self-cleaning ceramic tiles produced via stable coating of TiO₂ nanoparticles. Materials. 2018;11(6):1003. doi: 10.3390/ma11061003. Published 2018 Jun 13. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 122.Amini Tapouk F., Nabizadeh R., Mirzaei N., Hosseini Jazani N., Yousefi M., Valizade Hasanloei M.A. Comparative efficacy of hospital disinfectants against nosocomial infection pathogens. Antimicrob. Resist. Infect. Control. 2020;9(1):115. doi: 10.1186/s13756-020-00781-y. Published 2020 Jul 22. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 123.Assadian O., Harbarth S., Vos M., Knobloch J.K., Asensio A., Widmer A.F. Practical recommendations for routine cleaning and disinfection procedures in healthcare institutions: a narrative review. J. Hosp. Infect. 2021;113:104–114. doi: 10.1016/j.jhin.2021.03.010. [DOI] [PubMed] [Google Scholar]
- 124.Rawlinson S., Ciric L., Cloutman-Green E. How to carry out microbiological sampling of healthcare environment surfaces? A review of current evidence. J. Hosp. Infect. 2019;103(4):363–374. doi: 10.1016/j.jhin.2019.07.015. [DOI] [PubMed] [Google Scholar]
- 125.Napoli C., Marcotrigiano V., Montagna M.T. Air sampling procedures to evaluate microbial contamination: a comparison between active and passive methods in operating theatres. BMC Publ. Health. 2012;12:594. doi: 10.1186/1471-2458-12-594. Published 2012 Aug 2. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 126.Stern R.A., Koutrakis P., Martins M.A.G., et al. Characterization of hospital airborne SARS-CoV-2. Respir. Res. 2021;22(1):73. doi: 10.1186/s12931-021-01637-8. Published 2021 Feb 26. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 127.Ang A.X., Luhung I., Ahidjo B.A., et al. Airborne SARS-CoV-2 surveillance in hospital environment using high-flowrate air samplers and its comparison to surface sampling. Indoor Air. 2022;32(1) doi: 10.1111/ina.12930. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 128.de Man P., Ortiz M.A., Bluyssen P.M., et al. Airborne SARS-CoV-2 in home and hospital environments investigated with a high-powered air sampler. J. Hosp. Infect. 2022;119:126–131. doi: 10.1016/j.jhin.2021.10.018. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 129.Lee H.J., Lee K.H., Kim D.K. Evaluation and comparison of the indoor air quality in different areas of the hospital. Medicine (Baltim.) 2020 Dec 24;99(52) doi: 10.1097/MD.0000000000023942. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 130.Palmisani J., Di Gilio A., Viana M., de Gennaro G., Ferro A. Indoor air quality evaluation in oncology units at two European hospitals: low-cost sensors for TVOCs, PM2. 5 and CO2 real-time monitoring. Build. Environ. 2021 Nov 1;205 [Google Scholar]
- 131.Kim K.H., Kabir E., Jahan S.A. Airborne bioaerosols and their impact on human health. J. Environ. Sci. (China) 2018 May;67:23–35. doi: 10.1016/j.jes.2017.08.027. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 132.Yousefzadeh A., Maleki A., Athar S.D., Darvishi E., Ahmadi M., Mohammadi E., Tang V.T., Kalmarzi R.N., Kashefi H. Evaluation of bio-aerosols type, density, and modeling of dispersion in inside and outside of different wards of educational hospital. Environ. Sci. Pollut. Res. Int. 2022 Feb;29(10):14143–14157. doi: 10.1007/s11356-021-16733-x. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 133.Gizaw Z., Gebrehiwot M., Yenew C. High bacterial load of indoor air in hospital wards: the case of University of Gondar teaching hospital, Northwest Ethiopia. Multidiscip Respir Med. 2016 Jul 5;11:24. doi: 10.1186/s40248-016-0061-4. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 134.Fekadu S., Getachewu B. Microbiological assessment of indoor air of teaching hospital wards: a case of jimma university specialized hospital. Ethiop J Health Sci. 2015 Apr;25(2):117–122. doi: 10.4314/ejhs.v25i2.3. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 135.Sterr C.M., Dick A., Schellenberger L., Zirbes J., Nonnenmacher-Winter C., Günther F. High level bioaerosol protection against infective aerosols: how medical face masks compare against respirators. Can. J. Infect Dis. Med. Microbiol. 2022:6978661. doi: 10.1155/2022/6978661. Oct 22;2022. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 136.National Academies of Sciences . In: Frameworks for Protecting Workers and the Public from Inhalation Hazards. Yost O.C., Downey A., Samet J., editors. National Academies Press (US); Washington (DC): 2022. Engineering, and medicine; health and medicine division; board on health sciences policy; committee on respiratory protection for the public and workers without respiratory protection programs at their workplaces.https://www.ncbi.nlm.nih.gov/books/NBK580372/ Feb 10. 3, Respiratory Protection in the Workplace. Available from: [PubMed] [Google Scholar]
- 137.Vikke H.S., Giebner M., Kolmos H.J. Prehospital infection control and prevention in Denmark: a cross-sectional study on guideline adherence and microbial contamination of surfaces. Scand. J. Trauma Resuscitation Emerg. Med. 2018 Dec;26:1–7. doi: 10.1186/s13049-018-0541-y. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 138.Kowalski W. CRC Press; 2011 Dec 7. Hospital Airborne Infection Control. [Google Scholar]
- 139.Stockwell R.E., Ballard E.L., O'Rourke P., Knibbs L.D., Morawska L., Bell S.C. Indoor hospital air and the impact of ventilation on bioaerosols: a systematic review. J. Hosp. Infect. 2019 Oct 1;103(2):175–184. doi: 10.1016/j.jhin.2019.06.016. [DOI] [PubMed] [Google Scholar]
- 140.Qian H., Zheng X. Ventilation control for airborne transmission of human exhaled bio-aerosols in buildings. J. Thorac. Dis. 2018 Jul;10(Suppl 19):S2295–S2304. doi: 10.21037/jtd.2018.01.24. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 141.Lu Y., Niu D., Zhang S., Chang H., Lin Z. Ventilation indices for evaluation of airborne infection risk control performance of air distribution. Build. Environ. 2022 Aug 15;222 doi: 10.1016/j.buildenv.2022.109440. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 142.Yau Y.H., Chandrasegaran D., Badarudin A. The ventilation of multiple-bed hospital wards in the tropics: a review. Build. Environ. 2011 May;46(5):1125–1132. doi: 10.1016/j.buildenv.2010.11.013. Epub 2010 Nov 27. PMID: 32288016; PMCID: PMC7116949. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 143.Khodakarami J., Nasrollahi N. Thermal comfort in hospitals–A literature review. Renew. Sustain. Energy Rev. 2012 Aug 1;16(6):4071–4077. [Google Scholar]
- 144.Saran S., Gurjar M., Baronia A., et al. Heating, ventilation and air conditioning (HVAC) in intensive care unit. Crit. Care. 2020;24:194. doi: 10.1186/s13054-020-02907-5. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 145.Lomas K.J., Ji Y. Resilience of naturally ventilated buildings to climate change: advanced natural ventilation and hospital wards. Energy Build. 2009 Jun 1;41(6):629–653. [Google Scholar]
- 146.Zhang S., Ai Z., Lin Z. Occupancy-aided ventilation for both airborne infection risk control and work productivity. Build. Environ. 2021 Jan 15;188 doi: 10.1016/j.buildenv.2020.107506. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 147.Gilkeson C.A., Camargo-Valero M.A., Pickin L.E., Noakes C.J. Measurement of ventilation and airborne infection risk in large naturally ventilated hospital wards. Build. Environ. 2013 Jul 1;65:35–48. [Google Scholar]
- 148.Yu H.C., Mui K.W., Wong L.T., Chu H.S. Ventilation of general hospital wards for mitigating infection risks of three kinds of viruses including Middle East respiratory syndrome coronavirus. Indoor Built Environ. 2017 Apr;26(4):514–527. [Google Scholar]
- 149.Dancer S.J. Reducing the risk of COVID-19 transmission in hospitals: focus on additional infection control strategies. Surgery. 2021 Nov 1;39(11):752–758. doi: 10.1016/j.mpsur.2021.10.003. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 150.Zhang Y., Han O., Li A., Hou L., Olofsson T., Zhang L., Lei W. Adaptive wall-based attachment ventilation: a comparative study on its effectiveness in airborne infection isolation rooms with negative pressure. Engineering (Beijing) 2022 Jan;8:130–137. doi: 10.1016/j.eng.2020.10.020. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 151.Pertegal V., Cañizares P., Rodrigo M.A., Sáez C., Lacasa E. Bioaerosol disinfection using electro-ozonizers integrated into duct systems for hospital indoor air purification, using Klebsiella pneumoniae as an airborne bacterial model. Chem. Eng. J. 2023 Dec 1;477 doi: 10.1016/j.cej.2023.147058. [DOI] [Google Scholar]
- 152.Weng C.L., Kau L.J. Planning and design of a full-outer-air-intake natural air-conditioning system for medical negative pressure isolation wards. J Healthc Eng. 2021 Mar 25;2021 doi: 10.1155/2021/8872167. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 153.Wang Fujen, Chaerasari Citra, Rakshit Dibakar, Permana Indra, Kusnandar Performance improvement of a negative-pressurized isolation room for infection control. Healthcare. 2021;9(8):1081. doi: 10.3390/healthcare9081081. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 154.Chakraborty C., Bhattacharya M., Chopra H., Islam M.A., Saikumar G., Dhama K. The SARS-CoV-2 Omicron recombinant subvariants XBB, XBB. 1, and XBB. 1.5 are expanding rapidly with unique mutations, antibody evasion, and immune escape properties–an alarming global threat of a surge in COVID-19 cases again? Int. J. Surg. 2023 Apr;109(4):1041. doi: 10.1097/JS9.0000000000000246. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 155.World Health Organization N.1 initial risk evaluation 13 december 2023. https://www.who.int/activities/tracking-SARS-CoV-2-variants
- 156.Miller S.L., Clements N., Elliott S.A., Subhash S.S., Eagan A., Radonovich L.J. Implementing a negative-pressure isolation ward for a surge in airborne infectious patients. Am. J. Infect. Control. 2017 Jun 1;45(6):652–659. doi: 10.1016/j.ajic.2017.01.029. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 157.Hallier C., Williams D.W., Potts A.J., Lewis M.A. A pilot study of bioaerosol reduction using an air cleaning system during dental procedures. Br. Dent. J. 2010;209:E14. doi: 10.1038/sj.bdj.2010.975. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 158.Tzoutzas I., Maltezou H.C., Barmparesos N., Tasios P., Efthymiou C., Assimakopoulos M.N., Tseroni M., Vorou R., Tzermpos F., Antoniadou M., Panis V., Madianos P. Indoor air quality evaluation using mechanical ventilation and portable air purifiers in an academic dentistry clinic during the COVID-19 pandemic in Greece. Int J Environ Res Public Health. 2021 Aug 23;18(16):8886. doi: 10.3390/ijerph18168886. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 159.Arıkan I., Genç Ö., Uyar C., Tokur M.E., Balcı C., Perçin Renders D. Effectiveness of air purifiers in intensive care units: an intervention study. J. Hosp. Infect. 2022 Feb;120:14–22. doi: 10.1016/j.jhin.2021.10.011. [DOI] [PubMed] [Google Scholar]
- 160.Zhao B., Liu Y., Chen C. Air purifiers: a supplementary measure to remove airborne SARS-CoV-2. Build. Environ. 2020 Jun 15;177 doi: 10.1016/j.buildenv.2020.106918. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 161.Cooper E., Wang Y., Stamp S., Burman E., Mumovic D. Use of portable air purifiers in homes: operating behaviour, effect on indoor PM2. 5 and perceived indoor air quality. Build. Environ. 2021 Mar 15;191 doi: 10.1016/j.buildenv.2021.107621. [DOI] [Google Scholar]
- 162.Juaristi M., Krarti M. Review of adaptive opaque façades and laboratory tests for the dynamic thermal performance characterization. Build. Environ. 2023 Dec;20 doi: 10.1016/j.buildenv.2023.111123. [DOI] [Google Scholar]
- 163.Lee J.H., Rounds M., McGain F., Schofield R., Skidmore G., Wadlow I., Kevin K., Stevens A., Marshall C., Irving L., Kainer M., Buising K., Monty J. Effectiveness of portable air filtration on reducing indoor aerosol transmission: preclinical observational trials. J. Hosp. Infect. 2022 Jan;119:163–169. doi: 10.1016/j.jhin.2021.09.012. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 164.Alvarenga M.O.P., Dias J.M.M., Lima B.J.L.A., Gomes A.S.L., Monteiro G.Q.M. The implementation of portable air-cleaning technologies in healthcare settings - a scoping review. J. Hosp. Infect. 2023;132:93–103. doi: 10.1016/j.jhin.2022.12.004. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 165.Buising K.L., Schofield R., Irving L., Keywood M., Stevens A., Keogh N., Skidmore G., Wadlow I., Kevin K., Rismanchi B., Wheeler A.J., Humphries R.S., Kainer M., Monty J., McGain F., Marshall C. Use of portable air cleaners to reduce aerosol transmission on a hospital coronavirus disease 2019 (COVID-19) ward. Infect. Control Hosp. Epidemiol. 2022;43:987–992. doi: 10.1017/ice.2021.284. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 166.Mallakpour S., Azadi E., Hussain C.M. Fabrication of air filters with advanced filtration performance for removal of viral aerosols and control the spread of COVID-19. Adv. Colloid Interface Sci. 2022 May 1;303 doi: 10.1016/j.cis.2022.102653. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 167.Razzini K., Castrica M., Menchetti L., Maggi L., Negroni L., Orfeo N.V., Pizzoccheri A., Stocco M., Muttini S., Balzaretti C.M. SARS-CoV-2 RNA detection in the air and on surfaces in the COVID-19 ward of a hospital in Milan, Italy. Sci. Total Environ. 2020;742 doi: 10.1016/j.scitotenv.2020.140540. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 168.Hassan A., Zeeshan M. Microbiological indoor air quality of hospital buildings with different ventilation systems, cleaning frequencies and occupancy levels. Atmos. Pollut. Res. 2022;13 doi: 10.1016/j.apr.2022.101382. [DOI] [Google Scholar]
- 169.Dancer S.J. Hospital cleaning in the 21st century. Eur. J. Clin. Microbiol. Infect. Dis. 2011;30:1473–1481. doi: 10.1007/s10096-011-1250-x. [DOI] [PubMed] [Google Scholar]
- 170.Ratliff K.M., Oudejans L., Archer J., Calfee W., Gilberry J.U., Hook D.A., Schoppman W.E., Yaga R.W., Brooks L., Ryan S. Large-scale evaluation of microorganism inactivation by bipolar ionization and photocatalytic devices. Build. Environ. 2023;227 doi: 10.1016/j.buildenv.2022.109804. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 171.Nunayon S.S., Zhang H.H., Jin X., Lai A.C. Experimental evaluation of positive and negative air ions disinfection efficacy under different ventilation duct conditions. Build. Environ. 2019;158:295–301. doi: 10.1016/j.buildenv.2019.05.027. [DOI] [Google Scholar]
- 172.Zeng Y., Heidarinejad M., Stephens B. Evaluation of an in-duct bipolar ionization device on particulate matter and gas-phase constituents in a large test chamber. Build. Environ. 2022;213 doi: 10.1016/j.buildenv.2022.108858. [DOI] [Google Scholar]
- 173.Lindblad M., Tano E., Lindahl C., Huss F. Ultraviolet-C decontamination of a hospital room: amount of UV light needed. Burns. 2020;46:842–849. doi: 10.1016/j.burns.2019.10.004. [DOI] [PubMed] [Google Scholar]
- 174.Nunayon S.S., Zhang H.H., Chan V., Kong R.Y.C., Lai A.C.K. Study of synergistic disinfection by UVC and positive/negative air ions for aerosolized Escherichia coli, Salmonella typhimurium, and Staphylococcus epidermidis in ventilation duct flow. Indoor Air. 2022;32 doi: 10.1111/ina.12957. [DOI] [PubMed] [Google Scholar]
- 175.Pellegrin B., Berne P., Giraud H., Roussey A. Exploring the potential of electrostatic precipitation as an alternative particulate matter filtration system in aircraft cabins. Indoor Air. 2022;32 doi: 10.1111/ina.12990. [DOI] [PubMed] [Google Scholar]
- 176.Reijula J., Holopainen R., Kähkönen E., Reijula K., Tommelein I.D. Intelligent HVAC systems in hospitals. Intell. Build. Int. 2013;5:101–119. doi: 10.1080/17508975.2013.778192. [DOI] [Google Scholar]
- 177.Pirouz B., Palermo S.A., Naghib S.N., Mazzeo D., Turco M., Piro P. The role of HVAC design and windows on the indoor airflow pattern and ACH. Sustainability. 2021;13:7931. doi: 10.3390/su1314793. [DOI] [Google Scholar]
- 178.Sodiq A., Khan M.A., Naas M., Amhamed A. Addressing COVID-19 contagion through the HVAC systems by reviewing indoor airborne nature of infectious microbes: will an innovative air recirculation concept provide a practical solution? Environ. Res. 2021;199 doi: 10.1016/j.envres.2021.111329. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 179.Whyte H.E., Raillard C., Subrenat A., Héquet V. Photocatalytic oxidation of isoflurane, an anesthetic gas: the influence of operating parameters. Chem. Eng. J. 2018;352:441–449. doi: 10.1016/j.cej.2018.07.059. [DOI] [Google Scholar]
- 180.Abidi M., Hajjaji A., Bouzaza A., Lamaa L., Peruchon L., Brochier C., Rtimi S., Wolbert D., Bessais B., Assadi A.A. Modeling of indoor air treatment using an innovative photocatalytic luminous textile: reactor compactness and mass transfer enhancement. Chem. Eng. J. 2022;430 doi: 10.1016/j.cej.2021.132636. [DOI] [Google Scholar]
- 181.Zadi T., Assadi A.A., Nasrallah N., Bouallouche R., Tri P.N., Bouzaza A., Azizi M.M., Maachi R., Wolbert D. Treatment of hospital indoor air by a hybrid system of combined plasma with photocatalysis: case of trichloromethane. Chem. Eng. J. 2018;349:276–286. doi: 10.1016/j.cej.2018.05.073. [DOI] [Google Scholar]
- 182.El-Tanbouly R., Hassan Z., El-Messeiry S. The role of indoor plants in air purification and human health in the context of COVID-19 pandemic: a proposal for a novel line of inquiry. Front. Mol. Biosci. 2021;8 doi: 10.3389/fmolb.2021.709395. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 183.Moslehian A.S., Roös P.B., Gaekwad J.S., Van Galen L. Potential risks and beneficial impacts of using indoor plants in the biophilic design of healthcare facilities: a scoping review. Build. Environ. 2023 doi: 10.1016/j.buildenv.2023.110057. [DOI] [Google Scholar]
- 184.Xiao L., Qin L.L., Wu S.Y. Proposal and application of comprehensive thermal comfort evaluation model in heating seasons for buildings with solar Trombe wall. Appl. Therm. Eng. 2022;213 doi: 10.1016/j.applthermaleng.2022.118774. [DOI] [Google Scholar]
- 185.Liu G., Xiao M., Zhang X., Gal C., Chen X., Liu L., Pan S., Wu J., Tang L., Clements-Croome D. A review of air filtration technologies for sustainable and healthy building ventilation. Sustain. Cities Soc. 2017;32:375–396. doi: 10.1016/j.scs.2017.04.011. [DOI] [Google Scholar]
- 186.Shayegan Z., Bahri M., Haghighat F. A review on an emerging solution to improve indoor air quality: application of passive removal materials. Build. Environ. 2022 Jul 1;219 [Google Scholar]
- 187.Malayeri M., Bahri M., Haghighat F., Shah A. Impact of air distribution on indoor formaldehyde abatement with/without passive removal material: a CFD modeling. Build. Environ. 2022 Mar 15;212 [Google Scholar]
- 188.Cros C.J., Morrison G.C., Siegel J.A., Corsi R.L. Long-term performance of passive materials for removal of ozone from indoor air. Indoor Air. 2012 Feb;22(1):43–53. doi: 10.1111/j.1600-0668.2011.00734.x. [DOI] [PubMed] [Google Scholar]
- 189.Sekine Y., Nishimura A. Removal of formaldehyde from indoor air by passive type air-cleaning materials. Atmospheric environment. 2001 Apr 1;35(11) [Google Scholar]
- 190.Bahri M., Schleibinger H., Render W., Naboka O. Removal performance of formaldehyde by ceiling tiles as sorptive passive panels. Build. Environ. 2019 Aug 1;160 [Google Scholar]
- 191.Smedemark S.H., Ryhl-Svendsen M., Toftum J. Removal of organic acids from indoor air in museum storage rooms by active and passive sorption techniques. Stud. Conserv. 2020 Jul 3;65(5):251–261. [Google Scholar]
- 192.Lamplugh A., Nguyen A., Montoya L.D. Optimization of VOC removal using novel, low-cost sorbent sinks and active flows. Build. Environ. 2020 Jun 1;176 [Google Scholar]
- 193.Alexandra S. Adsorbent media for the sustainable removal of organic air pollutants from museum display cases. Heritage Science. 2020 Dec 1;8(1) [Google Scholar]
- 194.Sellaoui L., Badawi M., Monari A., Tatarchuk T., Jemli S., Dotto G.L., Bonilla-Petriciolet A., Chen Z. Make it clean, make it safe: a review on virus elimination via adsorption. Chem. Eng. J. 2021 May 15;412 doi: 10.1016/j.cej.2021.128682. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 195.Li R., Cui L., Chen M., Huang Y. Nanomaterials for airborne virus inactivation: a short review. Aerosol Science and Engineering. 2021 Mar;5:1. 1. [Google Scholar]
- 196.Li R, Cui L, Chen M, Huang Y. Nanomaterials for Airborne Virus Inactivation: A Short Review. Aerosol Science and Engineering. 2021;5(1):1–11. doi: 10.1007/s41810-020-00080-4. [DOI] [Google Scholar]
- 197.Alrazeeni D., Al Sufi M.S. Nosocomial infections in ambulances and effectiveness of ambulance fumigation techniques in Saudi Arabia. Phase I study. Saudi Med. J. 2014;35:1354–1360. [PMC free article] [PubMed] [Google Scholar]
- 198.Luksamijarulkul P., Pipitsangjan S. Microbial air quality and bacterial surface contamination in ambulances during patient services. Oman Med. J. 2015;30:104–110. doi: 10.5001/omj.2015.23. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 199.Lin Y.K., Cheng C.P., Kim H., Wang Y.C. Risk of ambulance services associated with ambient temperature, fine particulate and its constituents. Sci. Rep. 2021;11:1651. doi: 10.1038/s41598-021-81197-5. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 200.Estienney M., Daval-Frerot P., Aho-Glélé L.S., Piroth L., Stabile P., Gerbet J.Y., Rouleau R., de Rougemont A., Belliot G. Use of a hydrogen peroxide nebulizer for viral disinfection of emergency ambulance and hospital waiting room. Food Environ Virol. 2022;14:217–221. doi: 10.1007/s12560-022-09519-y. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 201.Zhang Y., Liu Y., Li S., Xu R., Yu P., Ramos C., Ebrahimifakhar A., Guo Y. Efficiency of portable air purification on public buses: a pilot study. Environ. Pollut. 2023 Jul 15;329 doi: 10.1016/j.envpol.2023.121696. [DOI] [PubMed] [Google Scholar]
- 202.Lin Y.K., Cheng C.P., Kim H., Wang Y.C. Risk of ambulance services associated with ambient temperature, fine particulate and its constituents. Sci. Rep. 2021 Jan 18;11(1):1651. doi: 10.1038/s41598-021-81197-5. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 203.Zhou S., Zhang L. Research on airflow optimization and infection risk assessment of medical cabin of negative-pressure ambulance. Sustainability. 2022;14:4900. doi: 10.3390/su14094900. [DOI] [Google Scholar]
- 204.Baselga M., Alba J.J., Schuhmacher A.J. Impact of needle-point bipolar ionization system in the reduction of bioaerosols in collective transport. Sci. Total Environ. 2023;10 doi: 10.1016/j.scitotenv.2022.158965. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 205.Abhijith K.V., Kukadia V., Kumar P. Investigation of air pollution mitigation measures, ventilation, and indoor air quality at three schools in London. Atmos. Environ. 2022;289 doi: 10.1016/j.atmosenv.2022.119303. [DOI] [Google Scholar]
- 206.Lee S.G., Hyun J., Lee S.H., Hwang J. One-pass antibacterial efficacy of bipolar air ions against aerosolized Staphylococcus epidermidis in a duct flow. J. Aerosol Sci. 2014;69:71–81. doi: 10.1016/j.jaerosci.2013.12.005. [DOI] [Google Scholar]
- 207.Kanesaka I., Katsuse A.K., Takahashi H., Kobayashi I. Evaluation of a bipolar ionization device in inactivation of antimicrobial-resistant bacteria, yeast, Aspergillus spp. and human coronavirus. J. Hosp. Infect. 2022;1(126):16–20. doi: 10.1016/j.jhin.2022.04.004. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 208.Melikov A.K., Dzhartov V. Advanced air distribution for minimizing airborne cross-infection in aircraft cabins. HVAC R Res. 2013;19:926–933. doi: 10.1080/10789669.2013.818468. [DOI] [Google Scholar]