Table 2.
Fire spacing indicator scoring of high-rise building
| Building category | Fire spacing with other high-rise buildings (m) | Fire spacing with other types of buildings (m) | Actual risk condition | Value range | |||
|---|---|---|---|---|---|---|---|
| Classes 1 and 2 | Class 3 | Class 4 | |||||
| High-rise building | Main body | ≥ 13 | ≥ 9 | ≥ 11 | ≥ 14 | Safe | 80 ~ 100 |
| Annex | ≥ 9 | ≥ 6 | ≥ 7 | ≥ 9 | |||
| Main body | 12 ~ 13 | 8 ~ 9 | 10 ~ 11 | 13 ~ 14 | Normal | 60 ~ 79 | |
| Annex | 8 ~ 9 | 5 ~ 6 | 6 ~ 7 | 8 ~ 9 | |||
| Main body | 10 ~ 12 | 6 ~ 8 | 8 ~ 10 | 12 ~ 13 | Dangerous | 45 ~ 59 | |
| Annex | 6 ~ 8 | 3 ~ 5 | 4 ~ 6 | 6 ~ 8 | |||
| Main body | < 10 | < 6 | < 8 | < 12 | Very dangerous | 0 ~ 44 | |
| Annex | < 6 | < 3 | < 4 | < 6 | |||
The range values include the lower limit but not the upper limit (value range excluded)