Table 4. Ventilation rates in common spaces measured by Test 1 and Test 3.

Site Test type Space Name Area
(sq. ft.)
Max. Occupancy Measured ventilation (cfm/person) ASHRAE Ventilation requirement (cfm/person)
Site A Test 1 Cafeteria I 2,784 280 2.80 9.94
Test 1 Locker Room II 3,210 617 0.61 5.31
Test 3 Cafeteria I 2,784 280 2.49 9.94
Test 3 Office space 3,060 15 13.67 17.24
Site B Test 1 Training classroom 1,963 66 18.36 6.79
Test 1 Cafeteria II 4,466 290 5.20 10.27
Test 3 Locker Room 1,642 22 15.76 9.48
Test 3 Cafeteria I 7,865 ~100* 16.94 21.66
Site C Test 3 Cafeteria II 4,675 212 3.4 11.47
Test 3 Office space 1,440 12 11.66 12.2

*Approximated based on actual worker shift schedule observed by research team