Skip to main content
Sage Choice logoLink to Sage Choice
. 2024 Dec 5;18(1):142–156. doi: 10.1177/19375867241302406

Baseline Study of Ultra-Clean Air Change Rate, Number, and Type of Microorganisms and Level of Particles During Trauma Surgery

JLA Lans 1,✉, NMC Mathijssen 2,3, PR Goswami 4, JJ van den Dobbelsteen 5, PG Luscuere 1, M van der Elst 5,6
PMCID: PMC11667956  PMID: 39633611

Abstract

Background: The objective of an operating room (OR) ultra-clean ventilation system is to eliminate or reduce the quantity of dust particles and colony-forming units per cubic meter of air (CFU/m3). To achieve this, ultra-clean goal high air change rates per hour are required to reduce the particle load and number of CFU/m3. Aim: To determine the air quality in an ultra-clean OR during surgery, in terms of the number and type of microorganism and quantity of dust particles in order to establish a benchmark. Methods: Number of CFUs and the quantity of dust particles were measured. For measuring the CFUs, sterile extraction hoses were positioned at the incision, the furthest away positioned instrument table, and the periphery. At these locations, air was extracted to determine the quantity of dust particles. Findings: The number of CFU/m3 and particles was on average at wound level ≤1 CFU/m3 resp. 852.679 particles, at instrument table ≤1 CFU/m3 resp. 3.797 particles and in the periphery ≤8 CFU/m3, resp. 4.355 particles. Conclusion: The number of CFUs in the ultra-clean area is below the defined ultra-clean level of ≤10 CFU/m3 for ultra-clean surgery. The quantity of dust particles measured during surgery was higher than the defined ISO 5.

Keywords: operating room, colony-forming units, infection prevention, ultra clean ventilation systems, instrument tables, surgical procedure

Introduction

The objective of an operating room (OR) ultra-clean ventilation (UCV) system is to eliminate or reduce the quantity of dust particles and colony-forming units per cubic meter of air (CFU/m3). To achieve this goal, high air change rates per hour (ACH) are required to reduce the particle load and number of CFU/m3 (Langvatn et al., 2020; Lans et al., 2022).

The Dutch Federation of Medical Specialists (FMS) recently introduced a guideline for air handling in operating and treatment rooms (Kennisinstituut van de federatie van medisch specialisten, 2022). Only major orthopedic implant surgeries and major spinal surgeries (e.g., scoliosis) should be performed in a Class 1+ (Kennisinstituut van de federatie van medisch specialisten, 2022) OR. A Class 1+ OR corresponds to a Class 1 (DIN 1946-4: 2018-09, 2018; SIS-TS, 2015) OR according to international standards, where ultra-clean (HTM-03-01 Part A, n.d.; SIS-TS, 2015) air is defined as air which contains ≤10 CFU/m3. Other surgeries (Kennisinstituut van de federatie van medisch specialisten, 2022) could be performed in a generic OR with conventional (mixing) ventilation (CV) system with an air change rate of ≥20 h−1. This is in line with the WHO (World Health Organization, 2016) and for generic surgery with other international standards (DIN 1946-4: 2018-09, 2018; HTM-03-01 Part A, n.d.; NF S 90 351, 2013; Schweizerischer Verein von Gebäudetechnik-Ingenieuren, 2015; SIS-TS 39(E):2015, 2015). Evidence of the relation between higher ACH and a reduction of the number of surgical site infections (SSI) at most types of surgeries is weak (Kennisinstituut van de federatie van medisch specialisten, 2022; World Health Organization, 2016). Therefore, in accordance with their guideline, the FMS recommends a lower number of air changes per hour. Previous studies, during real (Agodi et al., 2015; Knudsen et al., 2021; Tammelin et al., 2023) or simulated surgery (Marsault et al., 2021), defined the air quality in terms of CFUs and sometimes dust particles directly and only underneath the Unidirectional Air Flow (UDAF) system and did not determine the measured number and type of microorganism close to the wound site and at the instrument table or in the periphery.

To date, most ORs in Dutch hospitals are built as an ultra-clean (Lans et al., 2023) OR. Since the recent FMS recommendation to reduce the number of air changes per hour for most surgeries, there is a need for a primary benchmark regarding the number and type of microorganisms and dust particles measured during real surgery at the wound site, instrument table, and periphery, measured in an ultra-clean OR. The present baseline study can be used as a contribution to the existing body of work (Knudsen et al., 2021; Marsault et al., 2021; Pedersen et al., 2019; Romano, Milani, Ricci, et al., 2020; Scaltriti et al., 2007; Tammelin et al., 2023) leading to a benchmark.

Methods

The measurements were executed in an OR at Reinier de Graaf Hospital (Delft, the Netherlands) during 29 different types of surgeries. The OR in this study was equipped with a UDAF system and classified as an ultra-clean OR class 1+. The UDAF system introduces the air directly (and only) above the protected area (see Figure 1). The staff present during surgery wore modern scrub suits made out of 99% polyester and 1% carbon fibers (Ljungqvist et al., 2015). The source strength using this type of clothing was 2.9 (0.9–5.7) CFU/s per person (Ljungqvist et al., 2015). The surface of the UDAF was 10.5 m2, and the total air volume introduced was 11.340 m3/h, which was 71 air changes per hour (ACH).

Figure 1.

Figure 1.

Working principle Unidirectional Air Flow (UDAF).

Colony-Forming Unit Measurements

For the CFU measurements, sterile sample extraction hoses were positioned at three locations in the OR. The extraction hoses were positioned by the surgical staff at the location (<5 cm) of the incision, at the furthest away positioned instrument table from the surgical site and in the periphery close to an air extraction point (see Figure 2). The material of the sample tube was 1515 “python” neoprene hose dimensions Ø15 × 21(mm), temperature resistance: −20°C to +100°C. The maximum length of the sample hoses was 3 meters. Portable Lighthouse H100 active-air samplers were used for microbial air sampling, according to the slit principle. For 10 min, 100 dm3/min was sampled. Airborne bacteria-carrying particles were trapped via impaction on Tryptose Soy Agar cultivation plates. The plates were incubated aerobically for 2 × 24 h at 30–35°C. Directly after the incubation period, the hospital laboratory determined and reported the type of microorganism. The level of CFUs was assessed by means of the Swedish standard SIS—TS39:2015 (SIS-TS 39(E):2015, 2015). In contrary to other international standards (DIN 1946-4: 2018-09, 2018; Schweizerischer Verein von Gebäudetechnik-Ingenieuren, 2015), the focus in this standard (SIS-TS 39(E):2015, 2015) is on biological contamination and the use of microbiological methods for the assessment.

Figure 2.

Figure 2.

Photos of sample extraction hoses at the wound site (a), lighthouse 3016 handheld particle counters and portable lighthouse H100 active-air samplers during measurements at instrument table (b), and extraction point (c).

Particle Count Measurements

The quantity of dust particles was measured at three positions in the OR. The quantity of dust particles was measured by the surgical staff at the location (<5 cm) of the incision, at the furthest away positioned instrument table from the surgical site and in the periphery close to an air extraction point (see Figure 2). For the particle measurements, Lighthouse 3016 handheld particle-counters with a flow rate of 2.83 l/min (0.1 ft3/min) were used. Particles with a size of ≥0.5 μm were measured. The ISO level of particles was assessed by means of the ISO 14644-1(ISO, 2015) standard, at-rest situation. At-rest is the condition where the OR or clean zone is complete with equipment installed and operating in a manner agreed upon, but with no personnel present (ISO, 2015).

During all measurements, the number of staff present, door openings, activity level, and extra ordinary occasions were recorded.

Results

The number of CFU/m3 and particles during the surgeries was on average at wound level ≤1 CFU/m3 resp. 852,679 particles, at instrument table ≤1 CFU/m3 resp. 3,797 particles and in the periphery ≤8 CFU/m3, resp. 4,355 particles. The level of CFUs measured at the incision and instrument table was on average 0.5 resp. 0.7 CFU/m3. This is below the defined ≤10 CFU/m3 for ultra-clean surgery (SIS-TS 39(E):2015, 2015), see Table 1 for number of CFU/m3, type of microorganism, and quantity of dust particles measured.

Table 1.

Descriptives operating room. Number (CFU/m3) and type of microorganism and quantity of dust particles measured. All surgeries were performed in the same OR equipped with an UDAF and in total 71 air changes per hour.

Quantity particles, CFUs and measurement location
Wound Instrument table Periphery
Type of surgery [duration] Measurement cycle [10 min] Mean quantity particles [0.5μm] Mean level of CFU [CFU/m3] Type of microorganism Mean quantity particles [0.5μm] Mean level of CFU [CFU/m3] Type of microorganism Mean level of CFU [CFU/m3] Mean level of CFU [CFU/m3] Type of microorganism Remarks
Distal humeral fracture [105 min] 1 74,193 0 Not determined 2954 0 Not determined 1477 3 Not determined
2 23,532 1 Not determined 1092 0 Not determined 3853 3 Not determined
3 1413 0 Not determined 193 0 Not determined 1894 2 Not determined
4 32 0 Not determined 32 0 Not determined 514 4 Not determined
5 835 0 Not determined 1798 0 Not determined 449 4 Not determined
6 12,521 0 Not determined 1027 0 Not determined 0 20 Not determined
7 1702 2 Not determined 3403 0 Not determined 0 4 Not determined
8 385 0 Not determined 1926 1 Not determined 0 9 Not determined
9 88 0 Not determined 417 0 Not determined 0 5 Not determined
10 32 0 Not determined 4848 0 Not determined 0 11 Not determined
11 424 1 Not determined 3602 0 Not determined 0 13 Not determined
12 247 0 Not determined 2825 0 Not determined 1024 6 Not determined
13 4077 0 Not determined 424 0 Not determined 417 3 Not determined
14 64 0 Not determined 0 0 Not determined 1926 12 Not determined
Laparoscopic inguinal hernia repair [30 min] 1 7544 0 Not determined 1284 0 Not determined 3114 8 Not determined
2 2440 0 Not determined 803 2 Not determined 3853 8 Not determined
Open inguinal hernia repair [30 min] 3 69,634 0 Not determined 6967 0 Not determined 2215 17 Not determined
4 117,341 0 Not determined 0 3 Not determined 161 3 Not determined
5 67,419 0 Not determined 289 0 Not determined 1124 4 Not determined
Elbow fracture [30 min] 6 81,160 0 Not determined 2761 0 Not determined 4398 4 Not determined
7 59,907 0 Not determined 64 2 Not determined 3692 6 Not determined
Open inguinal hernia repair [30 min] 1 1,157,230 0 Not determined 264 0 Not determined 5072 15 Not determined
2 13,933 0 Not determined 0 0 Not determined 1637 26 Not determined
Laparoscopic inguinal hernia repair [30 min] 3 9471 0 Not determined 0 0 Not determined 1284 3 Not determined
4 54,545 0 Not determined 0 0 Not determined 1284 8 Not determined
Laparoscopic inguinal hernia repair [30 min] 5 4495 0 Not determined 0 0 Not determined 1637 2 Not determined
6 4559 0 Not determined 0 0 Not determined 1220 0 Not determined
Open inguinal hernia repair [45 min] 1 10,113 0 Not determined 32 2 Not determined 1188 3 Not determined
2 8540 0 Not determined 32 4 Not determined 1156 1 Not determined
3 5169 0 Not determined 10,017 3 Not determined 15,603 4 Not determined
Open inguinal hernia repair [30 min] 4 1,414,930 0 Not determined 3660 0 Not determined 2472 9 Not determined
5 161 0 Not determined 10,402 Not determined 5554 5 Not determined
Plate osteosynthesis clavicle fracture [30 min] 6 14,961 2 Not determined 0 2 Not determined 771 1 Not determined C-arm used during surgical procedure
7 2321 0 Not determined 3114 0 Not determined 11,301 2 Not determined
Laparoscopic inguinal hernia repair [30 min] 1 35,989 0 None 3371 0 None 1059 3 1× Staphylococcus caprae
1× Micrococcus luteus
1× Staphylococcus epidermidis
2 11,012 0 None 3307 1 1× Staphylococcus epidermidis 674 23 13× Staphylococcus epidermidis
8× Micrococcus luteus
2× Bacillus sp
Patellar fracture repair [45 min] 3 325,216 0 None 74,771 0 None 15,121 17 6× Micrococcus luteus
6× Staphylococcus epidermidis
1× Bacillus sp
4× Staphylococcus warneri
C-arm used during surgical procedure
4 1926 0 None 3307 0 None 0 3 1× Staphylococcus capitis
1× Micrococcus luteus
1× Staphylococcus epidermidis
5 8957 0 None 6325 0 None 963 10 5× Micrococcus luteus
3× Staphylococcus haemolyticus
2× Staphylococcus epidermidis
6 289,773 0 None 5532 0 None 1830 10 5× Micrococcus luteus
5× Staphylococcus haemolyticus
Ankle fracture fixation [45 min] 7 3,177,296 0 None 4225 2 2× Micrococcus luteus 5121 41 1× Bacillus sp
16× Micrococcus luteus
20× Staphylococcus epidermidis
4× Staphylococcus capitis
C-arm used during surgical procedure
8 78,976 0 None 2538 3 2× Corynebacterium sp
1× Micrococcus luteus
21,285 6 4× Micrococcus luteus
2× Staphylococcus warneri
Open inguinal hernia repair [90 min] 1 2,613,831 2 1× Micrococcus luteus
1× Staphylococcus hominis
128 0 None 83,118 3 Not determined
2 867 0 None 64 0 None 3018 6 Not determined
Laparoscopic inguinal hernia repair [90 min] 3 12,360 0 None 32 0 None 3178 10 Not determined
4 35,315 2 1× Micrococcus luteus
1× Staphylococcus epidermidis
7159 1 1× Staphylococcus warneri 9663 8 Not determined
Laparoscopic inguinal hernia repair [45 min] 5 1,148,947 0 None 5040 0 None 5458 2 Not determined
6 61,833 0 None 0 0 None 2921 3 Not determined
7 55,637 0 None 0 0 None 4697 4 Not determined
Removal of implants of the ankle [10 min] 1 5,648,228 0 None 22,345 0 None 15,057 7 Not determined
Ankle fracture fixation [50 min] 2 4,109,118 0 None 5426 0 1316 0 Not determined
3 2,278,310 0 6421 8 1× Staphylococcus epidermidis
7× Micrococcus luteus
2279 0 Not determined
4 7,045,822 5 3× Staphylococcus aureus
2× Staphylococcus pettenkoferi
18,010 10 1× Paracoccus yeei
3× Staphylococcus hominis
5× Kocuria rhizophila
1× Acinetobacter lwoffii
8861 2 Not determined
Laparoscopic inguinal hernia repair [45 min] 5 25,809,339 0 835 0 None 10,370 2 Not determined
6 2,689,437 1 1× Paenibacillus urinalis 96 0 None 13,869 5 Not determined
7 33,388 0 64 0 None 9278 1 Not determined
Removal of lipoma swelling [10 min] 1 318,185 0 None 193 0 11,879 21 1× Staphylococcus epidermidis
1× Moraxella osloensis
1× Micrococcus luteus
Removal of lipoma swelling [10 min] 2 9760 1 1× Moraxella osloensis 11,012 0 None 5394 19 1× Staphylococcus vitulinus
1× Staphylococcus hominis
1× Micrococcus luteus
1× Moraxella osloensis
Laparoscopic inguinal hernia repair [50 min] 3 8,857,047 0 None 5137 0 None 0 14 1× Staphylococcus epidermidis
1× Paracoccus yeei
1× Moraxella osloensis
1× Corynebacterium simulans
1× Micrococcus luteus
4 110,567 0 None 12,103 0 None 0 17 1× Staphylococcus hominis
1× Acinetobacter johnsonii
1× Staphylococcus warneri
5 14,415 None 3981 0 None 0 19 1× Staphylococcus epidermidis
1× Staphylococcus aureus
1× Staphylococcus hominis
1× Micrococcus luteus
6 1605 0 None 4495 0 None 0 12 1× Staphylococcus hominis
1× Moraxella osloensis
1× Mirococcus luteus
Laparoscopic inguinal hernia repair [35 min] 7 68,831 0 None 4141,4 0 None 417,4 7 1× Staphylococcus epidermidis
1× Micrococcus luteus
1× Moraxella osloensis
1× Kocuria rhizophila
8 33,581 1 1× Micrococcus luteus 4173,6 0 None 32,1 8 1× Staphylococcus hominis
1× Staphylococcus petrasii
1× Micrococcus luteus
1× Corynebacterium amycolatum
9 5522 1 1× Staphylococcus hominis 2889 0 None 0 9 1× Staphylococcus epidermidis
1× Micrococcus luteus
1× Moraxella osloensis
Ankle fracture fixation [10 min] 1 31,526 0 None 24,496 0 None 18,877,3 1 1× Staphylococcus epidermidis
Laparoscopic inguinal hernia repair [60 min] 2 321,813 0 None 257 0 None 995,2 1 1× Micrococcus luteus
3 7994 0 None 0 0 None 160,5 1 1× Staphylococcus epidermidis
4 13,323 0 None 0 0 None 545,8 5 1× Moraxella osloensis
2× Micrococcus luteus
1× Staphylococcus saprophyticus
1× P. scleromae
5 125,913 0 None 0 0 None 642,1 1 1× Staphylococcus warneri
6 36,631 0 None 482 0 None 385,3 3 2× Corynebacterium propinquum
1× Micrococcus luteus
7 33,196 1 1× Micrococcus luteus 0 0 None 1380,5 0 None
8 33,099 0 963 0 866,8 0 None
Laparoscopic inguinal hernia repair [30 min] 9 16,598 0 None 0 0 None 577,9 0 None
Clavicle plate removal/fracture [20 min] 1 0 3 1× Bacillus simplex
1× Micrococcus luteus
31× grams of positive rods not determinable
0 1 1× Micrococcus luteus 64,2 8 3× Staphylococcus epidermidis
3× Staphylococcus hominis
1× Micrococcus luteus
1× grams of positive rods not determinable
2 0 2 1× Cellulosimicrobium cellulans
1× Paenibacillus sp
0 1 1× Staphylococcus capitis 0 3 2× Staphylococcus hominis
1× Micrococcus luteus
Fracture fixation of ankle fracture [30 min] 3 56,680 10 4× Corynebacterium minutissimum
3× Staphylococcus epidermidis
1× Escherichia coli
1× Enterococcus casseliflavus
1× Bacillus pumilus
0 2 2× Micrococcus luteus 2439,9 20 3× Staphylococcus epidermidis
1× Staphylococcus warneri
3× Micrococcus luteus
9× Staphylococcus warneri
4 51,701 0 None 0 0 None 0 20 1× Staphylococcus haemolyticus
6× Staphylococcus saprophiticus
8× Micrococcus luteus
5 11,159 3 1× Escherichia coli
2× Staphylococcus capitis
0 0 None 0 46 4× Paracoccus yeei
26× Staphylococcus warneri
4× Micrococcus luteus
Laparoscopic inguinal hernia repair [20 min] 6 29,276 1 3× Micrococcus luteus 0 0 None n.a. 6 3× Staphylococcus epidermidis
3× Micrococcus luteus
7 181,588 0 None 0 4 2× Staphylococcus hominis
2× Micrococcus luteus
n.a. 4 2× Micrococcus luteus
1× Staphylococcus epidermidis
1× Staphylococcus capitis
Mean 852,679 0,5 3797 0,7 4355 7,9

Discussion

Reducing energy consumption in hospitals has a high priority (Friedericy et al., 2019; Zarzycka et al., 2019). One possibility to save energy is to reduce the ACH in the OR (Lans et al., 2024; Loomans et al., 2020). For new construction projects, the choice is sometimes made to lower OR classifications (Kennisinstituut van de federatie van medisch specialisten, 2022), to lower the ACH, and to modify the existing air handling installation fitted in existing ORs (Lans et al., 2024). The WHO (World Health Organization, 2016) and FMS (Kennisinstituut van de federatie van medisch specialisten, 2022) stated that existing research on OR ventilation systems is flawed and that there is only weak evidence that OR ventilation systems help to reduce the incidence of SSIs (Brandt et al., 2008; Breier et al., 2011; Weinstein & Bonten, 2017). Other studies declare the opposite (Langvatn et al., 2020; Surial et al., 2022; Whyte & Lytsy, 2019) and advise to use a UCV system for infection-prone surgeries (HTM-03-01 Part A, n.d.; NICE guideline, 2020; SIS-TS 39(E):2015, 2015), where artificial implants are used.

This baseline study has been performed to enable a comparison regarding the number of CFU/m3, type of microorganism, and quantity of dust particles in an ultra-clean (HTM-03-01 Part A, n.d.; SIS-TS 39(E):2015, 2015) OR. Since the recent FMS advice to reduce the ACH for most surgeries, it is important to have a benchmark regarding the number and type of microorganisms and particles measured during surgery at the wound site, instrument table, and periphery, measured in an OR Class 1+.

In this study, there was a broad variety of microorganisms cultured at different locations, often there was little correlation between types of organisms found during one operation at different locations or in subsequent uses of the OR. In general, it can be said that an overwhelming majority of the cultured bacteria are not known as primary pathogens, such as Staphylococcus aureus (Bode et al., 2010). The majority of cultured organisms in this study are known as colonizing bacteria of the human skin (Staphylococcus hominis, S. epidermidis, S. capitis) which could pose a risk for low-grade prosthetic infections but were found in this study distant from the operating table to form a risk to the patient. Determination of the type of microorganisms shows a paucity of primary pathogens, with the largest numbers of cultured bacteria members of human colonizers or environmental contaminants that occasionally participate in prosthetic infections, and in this study in an OR equipped with a UDAF, were found distant from the site of the surgery to form a threat in those special cases. Besides the known SSI prevention measures (Seidelman et al., 2023), an ever-increasing air change rate is a concept that is on most occasions already beyond a reasonable expectation dose/response effect as long as the six general strategies supported by randomized trials are followed for prevention of SSIs: avoiding razors for hair removal, decolonization with intranasal antistaphylococcal agents and antistaphylococcal skin antiseptics for high-risk procedures, use of chlorhexidine gluconate and alcohol-based skin preparation, maintaining normothermia to keep the body temperature warmer than 36 °C, perioperative glycemic control, and use of negative pressure wound therapy.

During the measurements, the UCV system did not meet the at-rest ISO class 5 (DIN 1946-4: 2018-09, 2018; Kennisinstituut van de federatie van medisch specialisten, 2022) standards at the measuring locations during surgery. This is consistent with previous studies (Marsault et al., 2021; Scaltriti et al., 2007). Our study showed that the desired ISO5 (DIN 1946-4: 2018-09, 2018; Kennisinstituut van de federatie van medisch specialisten, 2022; NF S 90 351, 2013) classification was exceeded on every measurement location despite the high ACH (Langvatn et al., 2020). The quantity of particles measured during surgery was on average ISO8 at the wound site and ISO6 at the instrument table and in the periphery (ISO, 2015). This is consistent with other studies (Landrin et al., 2005; Stålfelt et al., 2023).

When changing the air change rate in an existing OR or when building a new OR, the selection of the classification of the OR and ACH should depend on the type of the surgical procedure. As well the number of people present, the heat load in the OR, the clothing procedure (Ljungqvist et al., 2015) etc. are important criteria. The impact of reducing the ACH on the measured numbers of CFUs and particles cannot be determined without considering the aforementioned parameters.

This study has several limitations.

First, the impact on SSIs when reducing the air change rate (Lans et al., 2024) in the OR is not determined. To date, most ORs in Dutch hospitals are designed as ultra-clean ORs (FMS Class 1+). Changing from an UCV to a CV air supply system can have an effect on the use of surgical smoke and contaminant removal effectiveness (Romano, Milani, Gustén, et al., 2020). However, reducing the air change rate will decrease the energy consumption of the OR air handling installation (Gormley et al., 2017; Marsault et al., 2021). A study is recommended to evaluate the impact on the number of SSIs and cultured bacteria when reducing the ACH according to the FMS. This study is recommended despite the fact that the outcomes will be influenced by parameters such as number and the behavior of staff present (Humphreys, 2018; Wang et al., 2020), number of door openings (Perez et al., 2018; Roth et al., 2019; Smith et al., 2013), amount of air introduced (Lans et al., 2022), type of surgical clothing (Cao et al., 2021; Ljungqvist et al., 2015), and type of surgical procedures (Friedericy et al., 2024).

Secondly, the number of staff present, door openings, activity level, and extraordinary occasions has influence on the number of CFU during surgery. Although we recorded these, we did not assess the impact of those activities on we did not assess the impact of those activities or occasions on the number of CFUs or the quantity of dust particles (Perez et al., 2018; Roth et al., 2019; Smith et al., 2013; Teter et al., 2017).

Third, in the current study, we only examined one hospital OR location. It is recommended to conduct a similar study in other hospitals and ORs where room geometry (Memarzadeh & Jiang, 2004), the ACH (Langvatn et al., 2020; Lans et al., 2024), and type of UCV system vary (Lans et al., 2022). The merging of all these data will give a more comprehensive picture of whether it is needed to apply high ACH.

In conclusion, the level of CFUs in the ultra-clean surgical area is below the standards defined ultra-clean level for ultra-clean ORs. The quantity of dust particles measured during surgery was higher than the standards defined ISO5 (ISO, 2015) at-rest. Regarding the number of particles (≥0.5μm) during surgery ISO8 (ISO, 2015) levels were reached at the wound site and ISO6 (ISO, 2015) at the instrument table and in the periphery.

Implications for Practice

  • It is relevant to understand how air quality in the OR affects the patient's risk of developing a SSI and the risk to staff when exposed to surgical smoke and other harmful substances.

  • The design of the OR air handling installation and selection of the type of UCV system is important. The type of surgery should be considered when selecting the type of air handling and OR air supply system.

  • When an OR is equipped with an ultra-clean air supply system that is protecting only the surgical site it will leave, the periphery of the OR at risk for contamination.

  • All environmental parameters should be assessed to determine if a higher or lower ACH will benefit the asepsis of the OR.

Acknowledgments

The authors would like to thank the staff of the Reinier de Graaf hospital group, the Netherlands, for making the operating rooms available for the measurements and determine the type of microorganism.

Footnotes

The author(s) declared the following potential conflicts of interest with respect to the research, authorship, and/or publication of this article: J.L.A. Lans is CEO of Medexs BV, a company that supplies and install OR ventilation systems. All other authors report no conflict of interest relevant to this article.

Funding: The author(s) received no financial support for the research, authorship, and/or publication of this article.

References

  1. Agodi A., Auxilia F., Barchitta M., Cristina M. L., D’Alessandro D., Mura I., Nobile M., Pasquarella C., Avondo S., Bellocchi P., Canino R., Capozzi C., Casarin R., Cavasin M., Contegiacomo P., Deriu M. G., Evola F. R., Farsetti P., Grandi A., D'Alessandro D., Guareschi D., Longhitano A. M., Longo G., Malatesta R., Marenghi P., Marras F., Maso A., Mattaliano A. R., Montella M. T., Moscato U., Navone P., Romeo M. A., Rossi F., Ruffino M., Santangelo C., Sartini M., Sessa G., Tardivo S., Tranquilli Leali P., Torregrossa M. V., Vitali P. (2015). Operating theatre ventilation systems and microbial air contamination in total joint replacement surgery: Results of the GISIO-ISChIA study. Journal of Hospital Infection, 90(3), 213–219. 10.1016/j.jhin.2015.02.014 [DOI] [PubMed] [Google Scholar]
  2. Bode L. G. M., Kluytmans J. A. J. W., Wertheim H. F. L., Bogaers D., Vandenbroucke-Grauls C. M. J. E., Roosendaal R., Troelstra A., Box A. T. A., Voss A., van der Tweel I., van Belkum A., Verbrugh H. A., Vos M. C. (2010). Preventing surgical-site infections in nasal carriers of Staphylococcus aureus. New England Journal of Medicine, 362(1), 9–17. 10.1056/nejmoa0808939 [DOI] [PubMed] [Google Scholar]
  3. Brandt C., Hott U., Sohr D., Daschner F., Gastmeier P., Rüden H. (2008). Operating room ventilation with laminar airflow shows no protective effect on the surgical site infection rate in orthopedic and abdominal surgery. Annals of Surgery, 248(5), 695–700. 10.1097/SLA.0b013e31818b757d [DOI] [PubMed] [Google Scholar]
  4. Breier A.-C., Brandt C., Sohr D., Geffers C., Gastmeier P. (2011). Laminar airflow ceiling size: No impact on infection rates following hip and knee prosthesis. Infection Control & Hospital Epidemiology, 32(11), 1097–1102. 10.1086/662182 [DOI] [PubMed] [Google Scholar]
  5. Cao G., Pedersen C., Zhang Y., Drangsholt F., Radtke A., Langvatn H., Stenstad L.-I., Hans M., Skogås J. G. (2021). Can clothing systems and human activities in operating rooms with mixing 1 ventilation systems help achieve 10 CFU/m3 level during orthopaedic surgeries? Journal of Hospital Infection, 120, 110–116. 10.1016/j.jhin.2021.11.005 [DOI] [PubMed] [Google Scholar]
  6. DIN 1946-4: 2018-09. (2018). Ventilation and air conditioning—Part 4: Ventilation in buildings and rooms of health care.
  7. Friedericy H. J., Friedericy A. F., de Weger A., van Dorp E. L. A., Traversari R. A. A. L., van der Eijk A. C., Jansen F. W. (2024). Effect of unidirectional airflow ventilation on surgical site infection in cardiac surgery: Environmental impact as a factor in the choice for turbulent mixed air flow. Journal of Hospital Infection, 148, 51–57. 10.1016/j.jhin.2024.03.008 [DOI] [PubMed] [Google Scholar]
  8. Friedericy H. J., Weiland N. H. S., Van Der Eijk A. C., Jansen F. W. (2019). Steps for reducing the carbon footprint of the operating room. Nederlands Tijdschrift Voor Geneeskunde, 163(43), D4095. [PubMed] [Google Scholar]
  9. Gormley T., Markel T. A., Jones H., Greeley D., Ostojic J., Clarke J. H., Abkowitz M., Wagner J. (2017). Cost-benefit analysis of different air change rates in an operating room environment. American Journal of Infection Control, 45(12), 1318–1323. 10.1016/j.ajic.2017.07.024 [DOI] [PubMed] [Google Scholar]
  10. HTM-03-01 Part A. (n.d.). Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems Classification: Official Publications approval reference: PAR38.
  11. Humphreys H. (2018). Behaviours and rituals in the operating theatre. Do they really matter? Healthcare Infection Society, 1–27. 10.33325/ipc0006 [DOI] [Google Scholar]
  12. ISO. (2015). ISO 14644-1:2015 Classification of air cleanliness by particle concentration. Cleanrooms and Associated Controlled Environments, 2(2), 2–5. [Google Scholar]
  13. Kennisinstituut van de federatie van medisch specialisten. (2022). Luchtbehandeling in operatiekamers en behandelkamers.
  14. Knudsen R. J., Knudsen S. M. N., Nymark T., Anstensrud T., Jensen E. T., La Mia Malekzadeh M. J., Overgaard S. (2021). Laminar airflow decreases microbial air contamination compared with turbulent ventilated operating theatres during live total joint arthroplasty: A nationwide survey. Journal of Hospital Infection, 113, 65–70. 10.1016/j.jhin.2021.04.019 [DOI] [PubMed] [Google Scholar]
  15. Landrin A., Bissery A., Kac G. (2005). Monitoring air sampling in operating theatres: Can particle counting replace microbiological sampling? Journal of Hospital Infection, 61(1), 27–29. 10.1016/j.jhin.2005.03.002 [DOI] [PubMed] [Google Scholar]
  16. Langvatn H., Schrama J. C., Cao G., Hallan G., Furnes O., Lingaas E., Walenkamp G., Engesæter L. B., Dale H. (2020). Operating room ventilation and the risk of revision due to infection after total hip arthroplasty: Assessment of validated data in the Norwegian Arthroplasty Register. Journal of Hospital Infection, 105(2), 216–224. 10.1016/j.jhin.2020.04.010 [DOI] [PubMed] [Google Scholar]
  17. Lans J. L. A., Mathijssen N. M. C., Bode A., van den Dobbelsteen J. J., van der Elst M., Luscuere P. G. (2022). Operating room ventilation systems: Recovery degree, cleanliness recovery rate and air change effectiveness in an ultra-clean area. Journal of Hospital Infection, 122, 115–125. 10.1016/j.jhin.2021.12.018 [DOI] [PubMed] [Google Scholar]
  18. Lans J. L. A., Mathijssen N. M. C., Bode A., van den Dobbelsteen J. J., van der Elst M., Luscuere P. G. (2024). What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms? Journal of Hospital Infection, 147, 115–122. 10.1016/j.jhin.2024.02.007 [DOI] [PubMed] [Google Scholar]
  19. Lans J. L. A., Mathijssen N. M. C., Traversari A. A. L., Jacobs I. M., van den Dobbelsteen J. J., van der Elst M., Luscuere P. G. (2023). Capital and operational expenditures of different operating room air-handling installations with conventional or ultra-clean air supply systems. Journal of Building Engineering, 78, 107714. 10.1016/j.jobe.2023.107714 [DOI] [Google Scholar]
  20. Ljungqvist B., Reinmüller B., Gustén J., Nordenadler J. (2015). Clothing systems in operating rooms—A comparative study. Journal of the IEST, 58(1), 20–23. 10.17764/1098-4321.58.1.20 [DOI] [Google Scholar]
  21. Loomans M. G. L. C., Ludlage T. B. J., van den Oever H., Molenaar P. C. A., Kort H. S. M., Joosten P. H. J. (2020). Experimental investigation into cleanroom contamination build-up when applying reduced ventilation and pressure hierarchy conditions as part of demand controlled filtration. Building and Environment, 176, 106861. 10.1016/j.buildenv.2020.106861 [DOI] [Google Scholar]
  22. Marsault L. V., Ravn C., Overgaard A., Frich L. H., Olsen M., Anstensrud T., Nielsen J., Overgaard S. (2021). Laminar airflow versus turbulent airflow in simulated total hip arthroplasty: Measurements of colony-forming units, particles, and energy consumption. Journal of Hospital Infection, 115, 117–123. 10.1016/j.jhin.2021.06.009 [DOI] [PubMed] [Google Scholar]
  23. Memarzadeh F., Jiang Z. (2004). Effect of operation room geometry and ventilation system parameter variations on the protection of the surgical site. IAQ Conference. [Google Scholar]
  24. NF S 90 351. (2013). Health care institutions—Controlled environment areas—Requirements for airborne contamination control.
  25. NICE guideline. (2020). Joint replacement (primary): hip, knee and shoulder. www.nice.org.uk/guidance/ng157
  26. Pedersen C., Cao G., Drangsholt F., Stenstad L. I., Skogås J. G. (2019). Can we meet the requirement for ultra-clean operation room (10CFU/m3) with dilution ventilation? E3S Web of Conferences, 111, 01041. 10.1051/e3sconf/201911101041 [DOI] [Google Scholar]
  27. Perez P., Holloway J., Ehrenfeld L., Cohen S., Cunningham L., Miley G. B., Hollenbeck B. L. (2018). Door openings in the operating room are associated with increased environmental contamination. American Journal of Infection Control, 46(8), 954–956. 10.1016/j.ajic.2018.03.005 [DOI] [PubMed] [Google Scholar]
  28. Romano F., Milani S., Gustén J., Joppolo C. M. (2020). Surgical smoke and airborne microbial contamination in operating theatres: Influence of ventilation and surgical phases. International Journal of Environmental Research and Public Health, 17(15), 5395. 10.3390/ijerph17155395 [DOI] [PMC free article] [PubMed] [Google Scholar]
  29. Romano F., Milani S., Ricci R., Joppolo C. M. (2020). Operating theatre ventilation systems and their performance in contamination control: “at rest” and “in operation” particle and microbial measurements made in an Italian large and multi-year inspection campaign. International Journal of Environmental Research and Public Health, 17(19), 7275. 10.3390/ijerph17197275 [DOI] [PMC free article] [PubMed] [Google Scholar]
  30. Roth J. A., Juchler F., Dangel M., Eckstein F. S., Battegay M., Widmer A. F. (2019). Frequent door openings during cardiac surgery are associated with increased risk for surgical site infection: A prospective observational study. Clinical Infectious Diseases, 69(2), 290–294. 10.1093/cid/ciy879 [DOI] [PubMed] [Google Scholar]
  31. Scaltriti S., Cencetti S., Rovesti S., Marchesi I., Bargellini A., Borella P. (2007). Risk factors for particulate and microbial contamination of air in operating theatres. Journal of Hospital Infection, 66(4), 320–326. 10.1016/j.jhin.2007.05.019 [DOI] [PubMed] [Google Scholar]
  32. Schweizerischer Verein von Gebäudetechnik-Ingenieuren. (2015). SWKI VA105-01 Raumlufttechnische Anlagen in medizinisch genutzten Räumen SICC VA105-01. www.swki.ch
  33. Seidelman J. L., Mantyh C. R., Anderson D. J. (2023). Surgical site infection prevention: A review. JAMA, 329(3), 244. 10.1001/jama.2022.24075 [DOI] [PubMed] [Google Scholar]
  34. SIS-TS 39(E):2015. (2015). Swedish Standards Institute—Microbiological cleanliness in the operating room—Preventing airborne contamination—Guidance and fundamental requirements. www.sis.se
  35. Smith E. B., Raphael I. J., Maltenfort M. G., Honsawek S., Dolan K., Younkins E. A. (2013). The effect of laminar air flow and door openings on operating room contamination. Journal of Arthroplasty, 28(9), 1482–1485. 10.1016/j.arth.2013.06.012 [DOI] [PubMed] [Google Scholar]
  36. Stålfelt F., Svensson Malchau K., Björn C., Mohaddes M., Erichsen Andersson A. (2023). Can particle counting replace conventional surveillance for airborne bacterial contamination assessments? A systematic review using narrative synthesis. In American Journal of Infection Control, 51(12), 1417–1424. 10.1016/j.ajic.2023.05.004 [DOI] [PubMed] [Google Scholar]
  37. Surial B., Atkinson A., Külpmann R., Brunner A., Hildebrand K., Sicre B., Troillet N., Widmer A., Rolli E., Maag J., Marschall J. (2022). Better operating room ventilation as determined by a novel ventilation Index is associated with lower rates of surgical site infections. Annals of Surgery, 276(5), e353–e360. 10.1097/SLA.0000000000005670 [DOI] [PMC free article] [PubMed] [Google Scholar]
  38. Tammelin A., Kylmänen P., Samuelsson A. (2023). Comparison of number of airborne bacteria in operating rooms with turbulent mixing ventilation and unidirectional airflow when using reusable scrub suits and single-use scrub suits. Journal of Hospital Infection, 135, 119–124. 10.1016/j.jhin.2023.03.012 [DOI] [PubMed] [Google Scholar]
  39. Teter J., Guajardo I., Al-Rammah T., Rosson G., Perl T. M., Manahan M. (2017). Assessment of operating room airflow using air particle counts and direct observation of door openings. American Journal of Infection Control, 45(5), 477–482. 10.1016/j.ajic.2016.12.018 [DOI] [PubMed] [Google Scholar]
  40. Wang C., Sadeghian P., Sadrizadeh S. (2020). Effect of staff number on the Bacteria contamination in operating rooms with temperature controlled airflow ventilation and turbulent mixing ventilation. Proceedings of Building Simulation 2019: 16th Conference of IBPSA, 16, 747–753. 10.26868/25222708.2019.210960 [DOI] [Google Scholar]
  41. Weinstein R. A., Bonten M. J. M. (2017). Laminar airflow and surgical site infections: The evidence is blowing in the wind. The Lancet Infectious Diseases, 17(5), 472–473. 10.1016/S1473-3099(17)30060-9 [DOI] [PubMed] [Google Scholar]
  42. Whyte W., Lytsy B. (2019). Ultraclean air systems and the claim that laminar airflow systems fail to prevent deep infections after total joint arthroplasty. Journal of Hospital Infection, 103(1), e9–e15. 10.1016/j.jhin.2019.04.021 [DOI] [PubMed] [Google Scholar]
  43. World Health Organization. (2016). Global guidelines for the prevention of surgical site infection (WHO, Ed.; pp. 158–162). [PubMed] [Google Scholar]
  44. Zarzycka A., Haskoningdhv R., Maassen W., Zeiler W. (2019). Energy saving opportunities in operating theatres: a literature study. REHVA Journal, 2, 25–31. [Google Scholar]

Articles from Herd are provided here courtesy of SAGE Publications

RESOURCES