Table 2.

All the decay coefficients upstream and downstream of the fire source.

Test V(m/s) Pool size (m) kup kdo Test V(m/s) Pool size (m) kup kdo
1 0 0.15 × 0.15 0.687 1.011 10 0 0.20 × 0.20 0.703 1.128
2 0.36 0.660 1.008 11 0.36 0.723 1.144
3 1.14 0.428 1.052 12 1.14 0.407 1.081
4 2.03 0.465 0.961 13 2.03 0.451 1.307
5 2.79 0.540 1.162 14 2.79 0.482 1.187
6 3.53 0.882 1.731 15 3.53 0.552 1.724
7 4.31 1.079 2.033 16 4.31 1.018 1.648
8 4.97 1.246 2.178 17 4.97 1.314 2.277
9 5.61 1.514 2.226 18 5.61 1.433 2.403
Test V(m/s) Pool size (m) kup kdo Test V(m/s) Pool size (m) kup kdo
19 0 0.23 × 0.23 0.739 1.217 24 3.53 0.23 × 0.23 0.701 1.814
20 0.36 0.742 1.306 25 4.31 0.876 1.954
21 1.14 0.758 1.336 26 4.97 1.158 2.156
22 2.03 0.446 1.121 27 5.61 1.379 2.367
23 2.79 0.457 1.474