Table 6.
Cooling tower efficiency at different flow paths.
| Case study | Flow path | Equivalent length(m) | Tmax inlet(°C) | Tmax outlet(°C) | Cooling tower range(°C) | Cooling tower efficiency (%) |
|---|---|---|---|---|---|---|
| 1 | Spiral coil 1 & finned tube | 18 | 42 | 37.3 | 4.7 | 22 |
| 2 | Spiral coil 2 & finned tube | 12 | 42 | 37.3 | 4.7 | 22 |
| 3 | Spiral coil 3 & finned tube | 8 | 42 | 37.3 | 4.7 | 22 |
| 4 | Spiral coil 1 & 2 in series flow | 30 | 42 | 37.3 | 4.7 | 22 |
| 5 | Spiral coil 2 & 3 in series flow | 20 | 37.5 | 32 | 5.5 | 33 |
| 6 | Spiral coil 1 & 3 in series flow | 26 | 41 | 36.7 | 4.3 | 22 |
| 7 | Spiral coil 1 & 2 in parallel flow | 15 | 42 | – | – | – |
| 8 | Spiral coil 2 & 3 in parallel flow | 10 | 42 | – | – | – |
| 9 | Spiral coil 1 & 3 in parallel flow | 13 | 42 | – | – | – |
| 10 | Spiral coil 1 & 2 & 3 in series flow with finned coil | 41 | 35.1 | 26.82 | 8.28 | 59 |
| 11 | Spiral coil 1 & 2 & 3 in series flow without finned coil | 38 | 35 | 27 | 8 | 57 |
| 12 | Spiral coil 1 & 2 & 3 in parallel flow with finned coil | 16 | 38.2 | 31.53 | 6.67 | 39 |
--: experiments were not stable, and data were not acceptable.