Table 6.

Cooling tower efficiency at different flow paths.

Case study Flow path Equivalent length(m) Tmax inlet(°C) Tmax outlet(°C) Cooling tower range(°C) Cooling tower efficiency (%)
1 Spiral coil 1 & finned tube 18 42 37.3 4.7 22
2 Spiral coil 2 & finned tube 12 42 37.3 4.7 22
3 Spiral coil 3 & finned tube 8 42 37.3 4.7 22
4 Spiral coil 1 & 2 in series flow 30 42 37.3 4.7 22
5 Spiral coil 2 & 3 in series flow 20 37.5 32 5.5 33
6 Spiral coil 1 & 3 in series flow 26 41 36.7 4.3 22
7 Spiral coil 1 & 2 in parallel flow 15 42
8 Spiral coil 2 & 3 in parallel flow 10 42
9 Spiral coil 1 & 3 in parallel flow 13 42
10 Spiral coil 1 & 2 & 3 in series flow with finned coil 41 35.1 26.82 8.28 59
11 Spiral coil 1 & 2 & 3 in series flow without finned coil 38 35 27 8 57
12 Spiral coil 1 & 2 & 3 in parallel flow with finned coil 16 38.2 31.53 6.67 39

--: experiments were not stable, and data were not acceptable.