Skip to main content
. 2025 Apr 8;15:11962. doi: 10.1038/s41598-025-96702-3

Table 2.

Results of ground electrode resistance measurements using the 4p method.

No Month Ground electrode resistance RE (Ω) Percentage deviation σE (%)
RE1 (Ω) RE2 (Ω) RE3 (Ω) REAVG,4p (Ω) σE1 (%) σE2 (%) σE3 (%)
1 July 0.200 0.205 0.207 0.204 1.961 0.490 1.471
2 August 0.119 0.121 0.120 0.120 0.833 0.833 0.000
3 September 0.135 0.136 0.136 0.136 0.735 0.000 0.000
4 October 0.845 0.852 0.847 0.848 0.354 0.472 0.118
5 November 0.845 0.842 0.840 0.842 0.356 0.000 0.238
6 December 0.450 0.456 0.449 0.452 0.442 0.885 0.664
7 January 0.465 0.470 0.471 0.469 0.853 0.213 0.426
8 February 0.360 0.364 0.367 0.364 1.099 0.000 0.824
9 March 0.745 0.747 0.747 0.746 0.134 0.134 0.134
10 April 0.871 0.922 0.878 0.890 2.135 3.596 1.348
11 May 0.135 0.139 0.138 0.137 1.460 1.460 0.730
12 June 0.118 0.121 0.115 0.118 0.000 2.542 2.542