Impact of Wildfire Smoke PM2.5 on Indoor Air Quality of Public Buildings on a University Campus

Rowshon Afroz †, Jarred Alonzo †, Sohaib Omar †, Chu-Wen Cheng †, Stephanie R Schneider ‡, Ran Zhao †,*
PMCID: PMC11998926  PMID: 40242286

Abstract

graphic file with name ea4c00342_0008.jpg

With increasing wildfire events impacting many regions worldwide, understanding and mitigating the effects of wildfire smoke on indoor air quality (IAQ) in public buildings are essential for protecting occupant health. This study investigated the impact of wildfire smoke on the IAQ across 24 campus buildings in Alberta, Canada, representing public spaces with varied ventilation systems. Using a network of low-cost sensors to monitor indoor PM2.5, the study identified significant spikes during wildfire smoke events, with 71% of buildings exceeding the Canadian Ambient Air Quality Standards daily limit of 27 μg/m3. The buildings had mechanical ventilation systems with filters with different Minimum Efficiency Reporting Value (MERV) ratings. MERV13 filters were found to be more efficient at capturing PM2.5 particles, resulting in lower indoor/outdoor PM2.5 ratios (0.12 ± 0.07) compared to MERV8 filters (0.28 ± 0.14). Buildings with air change rates (ACH) ranging from 5 to 15 per hour exhibited different infiltration patterns, with higher ACH generally leading to elevated indoor PM2.5 concentrations during wildfire events. This highlights the need to balance ventilation and pollutant infiltration by optimizing ACH rates and filtration efficiency to reduce indoor PM2.5. The trajectory-fire interception method, combined with satellite data, enhanced the identification of wildfire-influenced periods, contributing to a better understanding of smoke infiltration dynamics. These findings underscore that even advanced filtration and ventilation systems alone may not ensure a healthy IAQ during extreme pollution. Real-time pollutant measurements are crucial for effective IAQ management. The findings offer valuable insights for building administrators and policymakers, helping them develop strategies to mitigate the effects of wildfire smoke and to support healthier indoor environments during wildfire seasons.

Keywords: Indoor air quality, low-cost sensor, PM2.5, wildfire smoke, infiltration, building ventilation

Short abstract

This study examined the effectiveness of filtration systems in diverse buildings during wildfire events by analyzing indoor and outdoor PM2.5 levels. Although buildings with higher-efficiency filters showed reductions in outdoor pollutant infiltration, indoor PM2.5 levels still rose during wildfire periods. These findings underscore the importance of balanced ventilation strategies and targeted filtration improvements to enhance indoor air quality under varying outdoor pollution conditions.

1. Introduction

Air pollution remains a significant global health concern, contributing to morbidity and mortality worldwide.1 In 2019, poor air quality, including household and ambient pollution, caused an estimated 6.7 million deaths globally.2 Given that most people spend almost 90% of their time indoors,3,4 IAQ is vital for occupant health. While buildings are generally considered protections against outdoor pollutants, IAQ can still be degraded by outdoor pollutants through infiltration.5 Outdoor pollutants arise from sources including transportation, heating, energy production, construction, industrial combustion, agriculture, and wildfire emissions.6−8 Among these, wildfires have become a growing concern, significantly contributing to air pollution and raising global alarms due to their widespread impacts on human health and the environment.9−11

Wildfires are known as large, uncontrolled vegetation fires caused by natural processes or human activities.12−14 It is a major natural hazard in North America, with significant interannual variability in both the number of fires and the total area burned.8,15,16 Each year, millions of hectares of forest are impacted by wildfires, leading to numerous community evacuations due to the direct threat of fire or the indirect impact of heavy smoke.17 In Canada, wildfire activity varies greatly across regions and seasons. According to a 2016 Canadian Interagency Forest Fire Centre report, Canada experienced an average of 7,000 wildfires annually over the past decade, burning about 2.6 million hectares yearly.18 However, the 2023 wildfire season saw 6,000 fires burning approximately 18.5 million hectares, which is more than double the previous record set in 1989.19

Wildfire smoke contains a complex mixture of air pollutants (including carbon monoxide, nitrogen oxides, methane, polycyclic aromatic hydrocarbons, volatile organic compounds, and particulate matter); notably up to 90% of the mass of these particles is made up of PM2.5 (fine particulate matter less than 2.5 μm in diameter).20−22 As a critical parameter for assessing IAQ and a key measure of overall air quality, PM2.5 has an overwhelming impact during wildfire smoke events, making it the central focus of our study. Additionally, PM2.5 is the highest health concern,23 given its association with various health issues, including respiratory problems, cardiovascular disease, and neurological effects.21,24−26 PM2.5 is widely used as a measure of overall air quality.27 During wildfire events, PM2.5 concentrations are significantly increased and may exceed the guideline levels established by regulatory agencies to protect the environment and human health. Recent studies have identified wildfires as the leading contributor to PM2.5 exposure in Canada, accounting for 17.1% of the total population-weighted exposure,28 with wildfire emissions generating over a third of all PM2.5.29 Short-term exposures to wildfire-related PM2.5 during the 2013–2015 and 2017–2018 wildfire seasons were linked to 54–250 acute cardiorespiratory deaths in Canada, while long-term exposures were associated with 570–2500 deaths due to chronic diseases.21 Furthermore, pollutants in indoor spaces have a much greater impact on human exposure than equivalent outdoor levels, given the length of time that humans spend indoors.30,31

Outdoor PM2.5 generated from wildfires can infiltrate indoor environments, even with windows and doors closed, through ventilation systems and other openings, thereby compromising IAQ.32 Once indoors, wildfire-related PM2.5 can persist for up to 8 to 10 h, further elevating the health risks.5 Beyond using technologies for source control and air cleaning, building ventilation systems play a crucial role in removing indoor pollutants.3 Studies from recent decades indicate that several strategies can effectively reduce the level of indoor particle exposure. Buildings with efficient ventilation systems or efficient air change rates per hour (ACH) are particularly effective in limiting outdoor particle infiltration and preventing indoor pollutant buildup.33,34 An effective approach is the use of mechanical ventilation systems, especially those with high-efficiency filtration in Heating, ventilation, and air conditioning systems, which are designed to introduce fresh outdoor air and dilute indoor pollutants.35,36 The removal efficiency largely depends on the filter, i.e., its minimum efficiency reporting values (MERV).37

Currently, there is a strong movement and active discussions to mandate and legislate IAQ standards in public buildings, which are centrally controlled and managed.38 While recommendations to reduce PM2.5 exposure during wildfire events include staying indoors, keeping windows and doors closed, and enhancing filtration, occupants of public buildings can rely on only the strategies implemented in the buildings. Keeping a high ACH is also considered as an effective way to keep occupants safe from indoor pollutants and virus transmission.38 However, during wildfire smoke events, where outdoor air is significantly more polluted, ventilation is also recognized as the main mechanism leading to the infiltration of outdoor air pollutants.39 Under such circumstances, the benefits of keeping a high ACH may be less advantageous and more complicated.30,40 Public buildings are also significantly different from each other and are likely impacted differently by wildfire smoke. University campus buildings, which span a wide variety of purposes, ages, structures, and ventilation schemes, are excellent representations of public buildings found in the surrounding region.

Assessing wildfire smoke impacts presents a significant challenge, as smoke episodes are often sporadic, short-lived, and characterized by highly variable concentrations across both space and time.23,41 Reference-grade instruments for IAQ monitoring are often costly and complex, limiting their use in everyday indoor settings. Additionally, these monitoring efforts are usually conducted in a limited number of locations, failing to capture the heterogeneity across various public buildings. In contrast, recent advancements in sensor technology have led to low-cost air quality sensors (LCS), which offer benefits such as affordability, portability, and the ability to capture detailed spatiotemporal data.42−44 Studies have demonstrated that LCS is effective for monitoring wildfire smoke, tracking its indoor infiltration, and assessing the performance of building ventilation systems, thus providing crucial information for guiding indoor activities.45−48

This study aims to provide a comprehensive assessment of the wildfire-generated PM2.5 impact on IAQ across various building settings. Through the deployment of an LCS network across multiple campus buildings in Alberta, Canada, this research presents a unique demonstration of wildfire PM2.5 infiltration into Canadian indoor environments. Using the campus as a representative sample of public buildings, this study holds broader implications for public facilities in wildfire-prone regions. Specifically, this study aimed to determine the indoor-to-outdoor (I/O) ratios of PM2.5 in various campus buildings to elucidate any correlation between building use, ventilation schemes (i.e., MERV and ACH), and I/O ratios. This work aligns with recent movements,38 which advocate for more stringent IAQ standards in public buildings.

2. Methods and Materials

2.1. IAQ Monitoring Device

Custom-built LCS were deployed in the buildings to measure indoor PM2.5 concentrations. Each LCS contains a PM sensor (SDS011) that operates on light scattering principles, with a measurement range of 0 to 999.9 μg/m3.49 The sensors record data every 30 s, and through a microcontroller (ESP8266),50,51 the real-time data are aggregated, visualized, analyzed, and stored to ThingSpeak, an IoT analytics platform.52 To ensure the accuracy and reliability of PM2.5 measurements, the sensors were calibrated against the optical particle counter (Grimm OPC, 11-C). Calibration was conducted both before (precampaign) and after (postcampaign) sensor deployment. The calibration process involved collocating all sensors in an unoccupied office with the door and windows closed to maintain controlled conditions. A fan was used to homogenize the air, while an ultrasonic humidifier generated aerosol particles for measurement. Both the sensors and the Grimm OPC simultaneously recorded PM2.5 data for comparison. Relative humidity is known to influence PM measurement when it is above 75%53−56 causing hygroscopic particle growth and overestimation of concentrations. In our study, during calibration and operation (throughout the study), RH levels remained well below 75%, which should cause minimal bias. Therefore, any potential impact of RH on the reported PM2.5 data can be avoided. Sensor performance was evaluated using the slope and coefficient of determination (R2), according to the United States Environmental Protection Agency (US EPA), which have recommended values of 1.0 ± 0.35 and ≥0.70, respectively.57 Calibration results (slope and R2) indicated that the sensors closely aligned with the Grimm OPC readings and met the US EPA recommended limits when PM2.5 concentrations were below 100 μg/m3 (Figure S1). However, at concentrations above 100 μg/m3, the sensors consistently overestimated PM2.5 level (Figure S2). To address this, a sensor-specific correction factor, derived from the calibration data, was applied only when the sensor readings exceeded 100 μg/m3. Additionally, the sensors and OPC were operated together in an office during real wildfire events to further assess their performance. The comparison yielded good agreement, with an R2 value of 0.96 ± 0.01 between the LCS and the OPC. Additional details about the LCS configuration and quality control procedures have been reported in our previous work.42

2.2. Study Location

This study was conducted in Alberta, Western Canada, where the area burned during the 2023 wildfire season was ten times more than the five-year average,58 underscoring the severity of wildfire events in the region. A 2021 report indicated that wildfires were responsible for 91% of PM2.5 exceedances across the province,59 emphasizing the need to assess air quality management during such critical times. Therefore, the study was carried out from May to October 2023, a period recognized as the most active for wildfires in Canada. We installed 28 LCS units in 24 diverse buildings (Table S1) to enhance our understanding of IAQ during wildfire events. Our goal was to cover as many campus buildings as possible, ensuring representation from various structures, and we aimed to recruit at least one participant from each building. These participants were either full-time employees or students, with sensors typically placed in offices and common areas.

Furthermore, multiple sensors were deployed in selected buildings to evaluate the representativeness of a single LCS reading for the entire building (B#12 and B#13) across different floors to assess location-based similarities or variations. The study buildings included a variety of facilities, such as laboratories, libraries, offices, student residences (offices), administrative buildings, gyms, an auditorium, and hospitals, representing a wide spectrum of public buildings. All buildings were equipped with mechanical ventilation systems to ensure effective air quality management in these diverse environments. These HVAC systems utilized filters rated at MERV values of 7, 8, and 13, with ACH ranging from 5 to 15 air changes per hour. The centrally operated buildings in this study were equipped with fixed or nonoperable windows, offering limited flexibility for window operation. To correlate building characteristics with indoor PM2.5 and I/O ratios, information on ventilation filter types and air exchange rates was gathered from the university’s Facility and Operations.

2.3. Community Engagement

The study used multiple methods to share information and encourage participation, including collaboration with the Office of Health, Safety, and Environment and engagement with campus communities. To accommodate different schedules and preferences, recruitment was flexible, using both online platforms and door-to-door visits. A consent process was followed for participants regarding their participation in this project. Leveraging the Internet-of-Things (IoT) technology incorporated in the LCS, real-time IAQ data were also displayed on a Web site to keep the campus community informed about the impact of wildfire smoke on their IAQ.

2.4. Data Analysis

Continuous indoor PM2.5 data were collected using LCS, while hourly averaged outdoor PM2.5 data were obtained from a regulatory monitoring station that used a Teledyne API T640 instrument for PM2.5 measurements, located 3.7 km from the study site. Time-resolved indoor (I) and outdoor (O) PM2.5 concentrations were compared to evaluate the percentage changes in PM levels (ΔPM2.5) using the following formula:60

2.4. 1

The variation in PM2.5 provided insights into the effectiveness of building envelopes and ventilation systems in mitigating outdoor PM2.5 infiltration. To assess the impact of wildfire smoke on indoor PM2.5, the indoor/outdoor (I/O) ratios were calculated for each building using the equation48

2.4. 2

Previous studies also suggested calculating the infiltration factor (Fin) to better understand outdoor PM2.5 infiltration; it is given by the equation48

2.4. 3

where Fin represents the infiltration factor of ambient PM2.5, Ci is the indoor concentration, Co is the outdoor concentration, and Cs accounts for contributions from indoor sources. Potential sources of PM2.5 include indoor activities, such as cooking, cleaning, and other routine activities, as well as infiltration of outdoor pollutants.61−63 However, the majority of the buildings studied, including offices, research facilities, and administrative spaces, had minimal indoor PM2.5 generation, indicating that outdoor infiltration was the primary contributor. Given the minimal indoor sources, this study assumed that the I/O ratio was equivalent to Fin, an approach supported by previous research.64,65 PM2.5 data are analyzed using Igor Pro 8. Additionally, principal component analysis (PCA) and ANOVA tests were conducted in Python to evaluate statistical relationships and uncover patterns among PM2.5 levels, MERV filter types, and building air exchange rates. PCA was performed to reduce the data complexity. Before running PCA, we standardized the data, normalizing each feature to a mean of 0 and a standard deviation of 1, to ensure comparability across scales. This analysis transformed the data into a set of new variables, or components, with the first few components capturing most of the variance. These components allowed us to explore trends related to PM2.5 levels, filter types, and building characteristics, helping us identify factors influencing air quality in buildings with different ventilation systems.

2.5. Identifying Wildfire Period

Wildfires occur broadly across Western Canada and the United States neighboring these provinces from May to September. Typically, larger wildfires are at least a few hundred kilometers from the city (and campus) and are not directly threatening the area. We have added a map (Figure S3) showing hot spots detected in the study area in Alberta from May to September, 2023. The trajectory-fire interception method (TFIM) was used to identify instances of wildfire influence in the ambient air quality data.66 Briefly, the method quantifies the number of interceptions between back trajectories of air masses obtained from the hybrid single-particle Lagrangian integrated trajectory (HYSPLIT) model and satellite observations of fire hotspots to identify time periods in which the ambient air quality measurements have been influenced by wildfires. We then defined a threshold with a wildfire-influenced period that is considered to occur if the interception count is ≥50. This threshold was determined based on both the number of interceptions and local PM2.5 measurements. The TFIM used here has been modified from the original version published by Schneider et al. (2021) in two ways. First, the Moderate Resolution Imaging Spectroradiometer (MODIS) hotspot data are not comparable to our previous study as one of the satellites is out of orbit. Therefore, hotspot data from the Visible Infrared Imaging Radiometer Suite (VIIRS) satellites were used instead. VIIRS had a higher resolution (∼375 m/pixel) than MODIS (∼1000 m/pixel), which resulted in the observation of smaller fires.67 Second, the HYSPLIT back-trajectories were calculated with the 12-km North American Mesoscale Forecast System (NAM-12) instead of the 32-km North American Regional Reanalysis (NARR) model, as the 3-h NARR data set was discontinued for HYSPLIT in 2019.

3. Results and Discussion

3.1. Sensor Agreement in Building-Wide IAQ

In this study, multiple LCS were deployed in different areas of the same building to assess the IAQ and evaluate the consistency of the PM2.5 measurements. Two sensors were deployed in one building (B#12), while in another building (B#13), four sensors were installed on different floors. B#12 and B#13 were selected due to the availability of participants, allowing for the deployment of multiple sensors and a comprehensive evaluation of PM2.5 levels across various floors. Additionally, their similar usage and adjacent locations provided a comparable setting for assessing indoor air quality under consistent environmental conditions. It is important to note that indoor PM2.5 concentrations varied between buildings, with B#13 showing higher concentrations than B#12. This discrepancy is attributed to the difference in MERV filter ratings (MERV 13 in B#12 vs MERV 8 in B#13), which is discussed in detail in later sections. Despite the variation in sensor placement, the recorded hourly averaged PM2.5 levels exhibited reasonable agreement within each building (Figure S4), suggesting minimal spatial variation in PM2.5 concentrations. B#13, for instance, exhibited a relative standard deviation (RSD) of 28 ± 23% between four sensors (Figure S5), although one sensor experienced technical issues that occasionally led to abnormal indoor PM2.5 measurements and affected the RSD. In particular, RSD was elevated mostly during periods with low PM2.5 concentrations. This indicates that the variation between sensors in the same building largely comes from the fluctuation in background PM2.5 at their specific locations. Facing a significant influence from wildfire smoke infiltration, sensors located in the same building responded very similarly to each other. Consequently, the findings suggest that even a single sensor could reasonably represent the IAQ for an entire building under similar conditions. In buildings with centrally controlled HVAC systems and minimal indoor pollutant sources, PM2.5 concentrations tend to be relatively homogeneous. This applies to many public buildings, such as those studied in this work. However, in buildings with independently ventilated areas or significant localized pollutant sources, a single sensor may not adequately capture PM2.5 levels throughout the entire building. For instance, in our previous work,42 in which sensors were deployed in student residences, PM2.5 levels were highly variable across rooms as the result of localized sources (cooking and humidifier use).

This finding is significant, as it demonstrates that comprehensive IAQ monitoring can be achieved with fewer sensors, reducing the cost and complexity of large-scale deployments. The agreement among sensors also increases confidence in the accuracy of the data, particularly when assessing exposure to pollutants during outdoor air quality events like wildfires. Overall, the results suggest that individual sensors can serve as adequate indicators of building-wide IAQ, making them practical and efficient tools for monitoring indoor environments.

3.2. Indoor–Outdoor PM2.5 Variation

Figure 1 presents the hourly averages of the PM2.5 concentration time series, comparing indoor measurements from the LCS network (average of all LCS) and outdoor measurements from a regulatory monitoring station collected from May to September 2023. The data reveal that outdoor PM2.5 concentrations closely follow the patterns of indoor levels, with a R2 of 0.86. This high R2 value demonstrates a strong positive correlation, highlighting the significant influence of outdoor particles on the indoor environment.

Figure 1.

Figure 1

Comparison of the hourly averaged PM2.5 concentrations indoors and outdoors during the wildfire season (May–September 2023). The indoor data (shown in brown) represent the average across the entire LCS network, while the outdoor data (shown in black) come from the regulatory monitoring station. The shaded areas represent the standard deviation derived from averaging the sensor data.

The study also reveals that both indoor and outdoor PM2.5 levels experienced spikes at various times, likely due to wildfire events. During these periods, outdoor PM2.5 concentrations exceeded 500 μg/m3, while indoor levels reached over 100 μg/m3, underscoring the substantial infiltration of outdoor particles into indoor spaces. However, indoor PM2.5 concentrations were consistently lower than outdoor levels; the building effectively reduced particle concentration, with PM2.5 reduction ranging from 19% to 98% (see eq 1). The indoor PM levels and their variation largely depend on factors such as the building’s ventilation type (natural or mechanical), ventilation filter type, ventilation rate, etc.4,37,68−70 These findings underscore the importance of evaluating and understanding the building performance and the effectiveness of ventilation systems in protecting against outdoor pollutant infiltration.

3.3. Wildfire and Non-Wildfire Periods

Between May and September 2023, TFIM was used to identify wildfire-influenced and non-wildfire-influenced periods to assess the impact of wildfires on PM2.5 concentrations. Hourly averaged outdoor PM2.5 data were analyzed and categorized by interception counts (Figure 2). As described in Section 2.3, periods with more than 50 interceptions were labeled as wildfire-influenced (in brown), while those with fewer than 50 interceptions were considered non-wildfire-influenced (in green).

Figure 2.

Figure 2

Hourly averaged ambient PM2.5 measurements by the regulatory monitoring station: wildfire-influenced periods (brown) and non-wildfire-influenced periods (green). Data shown in this figure are from after adjustments made with the Alberta Wildfire Status Dashboard.

Overall, the fire-influenced periods identified by TFIM showed good agreement with events with elevated PM2.5 levels. However, there were instances where elevated PM2.5 concentrations occurred without any corresponding interceptions and cases where interceptions were recorded despite relatively low outdoor PM2.5 levels. To address these inconsistencies, the TFIM results were further validated using the Alberta Wildfire Status Dashboard, enhancing the accuracy of the wildfire influence assessment. The data shown in Figure 2 reflect the adjustment made by this validation. This dashboard served as a crucial tool for verifying the periods identified through TFIM, ensuring that the classification accurately reflected actual wildfire events.

The integration of the TFIM with satellite observations offers a comprehensive framework for differentiating wildfire-influenced from non-wildfire-influenced periods. Identifying these periods is essential, as wildfires cause significant spikes in both outdoor and indoor PM2.5 levels. This methodology not only improves our understanding of air quality variations during wildfire events but also highlights the critical role of timely data measurement. By pinpointing wildfire-influenced periods, this study provides a focused analysis of daily indoor PM2.5 exposure (Section 3.4), which is crucial for evaluating potential health impacts. Additionally, understanding the temporal trends of wildfire-related air quality degradation enables the development of more targeted air quality management strategies and more effective public health advisories during wildfire seasons.

3.4. PM2.5 and I/O: Fire vs Non-Fire Periods

To evaluate the impact of wildfire smoke on IAQ, we compared hourly averaged indoor and outdoor PM2.5 levels during wildfire (red) and non-wildfire (green) periods, as shown in Figure 3. On non-wildfire days, indoor PM2.5 averaged 3.84 μg/m3 (max: 22.08 μg/m3, standard deviation (SD): 3.78 μg/m3), while outdoor levels averaged 22.27 μg/m3 (max: 131.44 μg/m3, SD: 16.95 μg/m3). While during wildfire events, indoor PM2.5 rose to an average of 8.42 μg/m3 (max: 81.20 μg/m3, SD: 11.55 μg/m3), and the outdoor average surged to 49.22 μg/m3 (max: 498.46 μg/m3, SD: 66.03 μg/m3). These findings indicate substantial infiltration of outdoor PM2.5 during wildfire events, challenging the IAQ in all building types. We observed a large SD in the PM2.5 concentration, particularly during wildfire periods, likely due to differences in building characteristics. Key factors include variations in the MERV ratings and ACH rates of the building’s ventilation system. While specific data were unavailable, the literature indicates that infiltration through windows, doors, and structural cracks or leaks may also affect the I/O ratio.71,72

Figure 3.

Figure 3

Comparison of hourly averaged indoor and outdoor PM2.5 concentrations during wildfire (red dots) and non-wildfire periods (green dots).

To further understand wildfire smoke impacts on IAQ, we calculated the I/O PM2.5 ratios across 28 sensors during both wildfire and non-wildfire periods (Figure S6). The I/O ratios were generally low (less than 0.4), suggesting that buildings provide some buffer against outdoor PM2.5 levels. Generally, the I/O ratio offers valuable insight into the relationship between indoor and outdoor particle concentrations. When the I/O ratio is <1, it indicates that indoor concentrations were typically lower than outdoor levels. Conversely, an I/O ratio >1 suggests that indoor sources dominate, and even in highly polluted outdoor environments, indoor concentrations can be higher. This can be attributed to factors such as poor ventilation, inadequate filtration efficiency, or the accumulation of pollutants indoors.73,74 In cases where the I/O ratio exceeds 1, it is recommended to identify and address indoor PM2.5 sources in order to improve air quality.30 A linear correlation analysis between wildfire and non-wildfire I/O ratios produced a slope of 1.06 ± 0.09, suggesting a strong, nearly 1:1 relationship between PM2.5 infiltration in both conditions. This slope indicates that while I/O ratios were comparable during wildfire and non-wildfire events, wildfire conditions led to higher absolute concentrations indoors, as previously shown in the PM2.5 concentration data (Figure 3).

3.5. Daily Exposure to PM2.5

During wildfire events, ground-level PM2.5 concentrations can significantly increase, often exceeding the recommended limits established by regulatory agencies to protect both human health and the environment. This study examined the rise in indoor PM2.5 concentrations, particularly during wildfire episodes. While Health Canada has not set a specific maximum exposure limit for indoor PM2.5, it recommends maintaining indoor levels below outdoor concentrations.40 For this study, the Canadian Ambient Air Quality Standards (CAAQS) exposure limit was used to assess the daily exposure. Figure 4 presents the daily average PM2.5 concentrations recorded by sensors from May to September 2023, compared to the CAAQS daily average limit of 27 μg/m3.75 The solid bars indicate the number of days when PM2.5 levels exceeded the CAAQS limit (data are also presented in Table S1), while striped bars represent days when levels were below it.

Figure 4.

Figure 4

Number of days the sensors exceeded or fell below the daily average recommended exposure limit set by CAAQS, with solid bars representing days when daily averaged PM2.5 levels exceeded the limit and striped bars indicating days when levels were below it.

Our analysis revealed that 71% of the studied buildings experienced exceedances of the CAAQS limit, regardless of ventilation type or filter grade (including both MERV13 and MERV8 filters). These exceedances were primarily observed during wildfire smoke episodes, when outdoor PM2.5 concentrations were significantly elevated, as depicted in Figure S7. For instance, in May and July, the wildfire impact on IAQ was severe, as at that time the outdoor concentration reached around 500 μg/m3 (Figure S7), resulting in 13 to 15 buildings surpassing the daily recommended limit. Notably, during periods of heightened wildfire activities, most sensors were more likely to exceed the CAAQS limit. On wildfire-affected days, when indoor PM2.5 levels exceeded the recommended limit, concentrations ranged from 29.5 to 85.5 μg/m3 (Figure S8).

While exceedances were widespread, Figure 4 also highlights clear differences in building performance, with some experiencing a higher number of exceedances, while others had fewer. While outdoor PM2.5 levels were the primary driver, factors such as ventilation efficiency, building design, and operational conditions likely influenced infiltration rates. The difference in exceedances between the buildings also suggests that ventilation rates, infiltration pathways, and overall building integrity played a more decisive role in determining indoor PM2.5 levels. Additionally, occupancy patterns and door and window usage likely contributed to the variability of elevated concentrations. Sensor placement in public spaces and high-traffic buildings, where doors opened frequently, likely experienced greater smoke infiltration than in controlled environments like offices or research laboratories. The study also attempted to analyze indoor PM2.5 behavior based on the year the buildings were built but did not find any conclusive results. This suggests that building age alone may not be a strong descriptor of variations in indoor PM2.5 levels. These findings highlight the complexity of IAQ management during wildfire episodes. While many of these factors were beyond our control in this study, a more detailed analysis of these factors in future studies could provide valuable insights for mitigating wildfire smoke infiltration and improving IAQ resilience in public buildings.

In a recent Policy Forum article published on Science, Morawska, and over 40 coauthors suggested the implementation of a more stringent PM2.5 standard in public buildings: 15 μg/m3 per hour.38 This is both a smaller value and also averaged over a shorter period of time. If this standard is considered, significantly more exceedances will be recorded during the measurement period. Our study shows a serious challenge that wildfire infiltration poses on the management of IAQ in public buildings and spaces, making it very difficult to meet the IAQ PM2.5 standards currently being discussed and debated.

3.6. Building Characteristics

As mentioned earlier, the study buildings were equipped with HVAC systems utilizing different MERV-rated filters and various air exchange rates. MERV is a standard developed by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). The MERV scale, which ranges from 1 to 16, measures the overall effectiveness of air filters capturing airborne particles.37,76−78 Filters with higher MERV ratings are more effective at trapping smaller particles. This study investigated how these factors (i.e., filter efficiency and air exchange rates) impact IAQ, specifically indoor PM2.5 concentrations.

3.6.1. Air Filtration System

In our study, a majority of buildings were equipped with either MERV8 or MERV13 filters, while a few had mixed filtration systems. To accurately evaluate the impact of each filter type, we focused solely on buildings with either MERV8 or MERV13 filters. We compared the I/O ratios (see eq 2) of hourly averaged PM2.5 data between buildings with MERV13 filters and those with MERV8 filters, as shown in Figure 5. The data revealed that averaged I/O ratios were higher for buildings with MERV8 filters, ranging from 0.28 ± 0.14, compared with MERV13 filters, which exhibited ratios of 0.12 ± 0.07. The lower I/O ratios observed in buildings with MERV13 filters indicate that these higher-efficiency filters more effectively remove particles from air penetrating indoors compared with MERV8 filters, resulting in reduced indoor PM2.5 levels.

Figure 5.

Figure 5

Comparison of the I/O ratio of hourly averaged PM2.5 between buildings with MERV13 filters (averaged from 19 sensors) and those with MERV8 filters (averaged from 6 sensors). The shaded areas in both traces represent the standard deviation.

This finding aligns with ASHRAE standards, which suggest that MERV13 filters can capture particles in the 0.3–1.0 μm range with 50% efficiency and in the 1.0–3.0 μm range with 85% efficiency, whereas MERV8 filters are less effective, capturing 0% of particles in the 0.3–1.0 μm range and 20% in the 1.0–3.0 μm range, respectively.37,78 Given that wildfire smoke particles primarily fall within 2.5 μm or smaller,79 MERV8 filters provide less protection against smoke infiltration. This limited filtration efficiency highlights the vulnerability of indoor environments to fine particulate matter during wildfire events, particularly when HVAC systems are not equipped with higher-efficiency filters.

These findings are particularly concerning for public buildings, such as schools, offices, and healthcare facilities, where people are exposed to IAQ daily. Since higher MERV ratings typically indicate more effective filtration, it is recommended to consider using or upgrading to a MERV13 or higher-rated filter, provided the HVAC system can accommodate it.36,80 Prioritizing air filtration improvements in these spaces can protect vulnerable populations and align with health guidelines to protect public health.

The two-component PCA analysis, shown in Figure 6, reveals distinct PM2.5 patterns between buildings with MERV8 and MERV13 air filter types, demonstrating how filtration systems and building characteristics influence PM2.5 levels. All six sensors from MERV8 buildings were found to be separated from the MERV13 clusters, indicating different PM2.5 characteristics in the MERV8 buildings. Most MERV13 buildings clustered together, exhibiting similar PM2.5 behavior, while two MERV13 sensors behaved differently, suggesting distinct PM2.5 profiles or influencing factors. The principal components 1 (PC1) and 2 (PC2) account for 45.3% and 10.6%, respectively, which represent the source of variation in PM2.5 levels across buildings. PCA analysis captures the primary differences in PM2.5 levels, likely driven by the greater filtration efficiency of MERV13 filters compared to MERV8. While no statistically significant difference in PM2.5 levels was observed between the two groups of sensors from buildings with MERV13 (19 sensors) and MERV8 (6 sensors) filters, significant differences (p < 0.05) were identified when comparing the individual PM2.5 measurements across all 24 sensors. This suggests that variations in PM2.5 levels between buildings are influenced by several factors along with the types of filters used. It is assumed that other secondary factors, such as the building’s ACHs, sensor placement, indoor activities, building functions, and building characteristics, could contribute to a further variation of PM2.5 concentration between buildings.

Figure 6.

Figure 6

PCA score plot of the first two principal components of the data set comprising the individual component samples. The principal components 1 and 2 account for 45.3% and 10.6%, respectively. PCA analysis is done on hourly averaged PM2.5 in buildings with either MERV13 or MERV8 filters, and their data were color-coded based on the filter type. Data were collected from May to September 2023.

3.6.2. Building’s Air Exchange Rate

ACH of a building can significantly affect indoor pollutant levels and is typically expressed as changes per hour (h–1).33 To understand the impact of ACH, this study analyzed both I/O ratios and indoor PM2.5 levels for 11 buildings equipped with MERV13 filters and a mixed indoor-outdoor air circulation system. Besides that, these buildings had ACH values ranging from 5 to 15 air changes per hour. Furthermore, two conditions were considered: outdoor PM2.5 concentrations below 50 μg/m3 (representing relatively clean air) and above 50 μg/m3 (indicating polluted air), to assess the impact of ACH under different outdoor pollution levels, as illustrated in Figure 7. A threshold of 50 μg/m3 was selected as a reasonable upper limit for relatively clean air, as the outdoor hourly averaged PM2.5 concentration during the non-wildfire period was 22.27 ± 16.95 μg/m3. This threshold helped distinguish relatively clean conditions from polluted ones, allowing for a meaningful assessment of ACH performance under different outdoor pollution levels. After comparing I/O data across the buildings, we found that those with ACHs between 5–9 had I/O ratios of 0.10 ± 0.03 and 0.10 ± 0.02, regardless of outdoor air quality. In contrast, buildings with ACHs in the 10–15 range showed higher I/O ratios of 0.24 ± 0.01 and 0.32 ± 0.02, also independent of outdoor air quality. Figure S9 also shows similar trends in indoor PM2.5 levels. The figure illustrates that all studied buildings had indoor PM2.5 concentrations below 20 μg/m3 when outdoor PM2.5 levels were less than 50 μg/m3. However, when outdoor PM2.5 concentrations exceeded 50 μg/m3, buildings ACH with 10–15 exhibited elevated indoor PM2.5 levels, ranging from 22 to 60 μg/m3.

Figure 7.

Figure 7

Comparison of the I/O ratio of hourly averaged PM2.5 in buildings with MERV13 filters and air exchange rates ranging from 5 to 15. Data were collected from May to September 2023, with outdoor PM2.5 measurements obtained from government monitoring stations.

A statistically significant difference (P < 0.05) was found between the I/O ratios of those 11 buildings, which indicates the variations of PM2.5 levels between the buildings. PCA analysis was also used to highlight the variance in I/O ratios across different ACH categories and two outdoor PM2.5 conditions (Figures S10A and S10B). The PCA results revealed distinct patterns in how the buildings with varying ACH responded to outdoor PM2.5 concentrations. Buildings ACH with 5–9 behaved similarly under both outdoor PM2.5 conditions, except for one outlier (building with 5 h–1). This outlier showed different behavior when outdoor PM2.5 was less than 50 μg/m3, with I/O ratios slightly higher than others in this group. In contrast, the buildings with ACH 10–15 exhibited distinct behavior compared to other buildings.

Generally, indoor pollutant concentrations decrease when increasing the ACH unless outdoor pollutant concentrations are high.34 The buildings (ACH with 5–9) maintained lower indoor PM2.5 levels across both outdoor conditions, indicating that lower ACH may help limit the ingress of outdoor pollutants. These buildings also displayed stable I/O ratios, suggesting they were less affected by outdoor PM levels than buildings with higher ACH. On the other hand, buildings (ACH with 10–15) experienced higher I/O ratios across both outdoor PM2.5 conditions, with significantly more pronounced differences when outdoor PM2.5 concentrations exceeded 50 μg/m3. This suggests that while a higher ACH is beneficial for removing indoor-generated pollutants, it can also allow more outdoor pollutants to enter the building, particularly in areas affected by poor outdoor air quality, such as those impacted by wildfires, heavy smog, traffic, or industrial activities. In such cases, decreasing the ACH may help reduce the infiltration of outdoor contaminants.40,71

However, if ACH is low or insufficient, it may restrict the ventilation needed to dilute indoor-generated pollutants, potentially leading to their accumulation and elevated indoor levels. Therefore, healthy indoor air can only be provided when accounting for both pollution from outdoor air and also pollutants generated indoors, underscoring the need for a balanced ACH. It has been shown that adjusting ventilation systems results in significant reductions in traffic-related pollutants indoors.81 Overall, optimizing ventilation strategies, especially in urban or wildfire-prone areas, requires a balance between adequate air exchange and effective filtration to ensure that both indoor and outdoor pollutants are controlled to achieve optimal IAQ.

4. Implication

Improving IAQ is essential for creating healthier living and working environments, especially since we spend a significant portion of our lives indoors. This study underscores the substantial impact of wildfire smoke on IAQ across various buildings equipped with mechanical ventilation systems, which differ in filtration efficiency (MERV13 vs MERV8) and ACH. Utilizing LCS to measure PM2.5, the research delves into the specific challenges and potential solutions related to wildfire smoke infiltration into campus buildings in a Canadian university, which represent a wide variety of public buildings in wildfire-affected regions.

The findings demonstrate a strong correlation between indoor and outdoor PM levels, highlighting the infiltration of pollutants into indoor spaces. Effective building ventilation systems were shown to reduce indoor pollution, indicating that improving building-level ventilation and filtration can significantly enhance the IAQ and protect occupant health. Buildings equipped with MERV13 filters exhibited lower I/O ratios for PM2.5, confirming the superior performance of these filters in reducing the infiltration of outdoor particles compared to MERV8 filters. Additionally, buildings with MERV13 filters and mixed air systems showed varied I/O ratios based on their ACH, with those having ACHs between 10 and 15 experiencing higher indoor PM2.5 levels than buildings with ACHs between 5 and 9. This suggests that higher ACH, while beneficial for removing indoor-generated pollutants, can introduce more outdoor pollutants, particularly during poor outdoor air quality conditions like wildfires.

The study also revealed that 71% of the examined buildings had indoor PM2.5 levels exceeding the daily average CAAQS exposure limit of 27 μg/m3. These exceedances occurred regardless of ventilation type, with the highest levels recorded during wildfire smoke episodes. During these events, daily average indoor PM2.5 concentrations ranged from 29.5 to 85.5 μg/m3, as measured by the sensors. These findings suggest that even high-efficiency filtration systems, such as those with MERV13 filters, may struggle to maintain healthy IAQ during extreme pollution events such as wildfires.

Our study highlights the critical role of MERV and ACH in controlling indoor PM2.5 levels. However, the study also suggests that additional factors, such as occupancy patterns, operational conditions, building age, and the use of doors and windows, could contribute to variations in PM2.5 levels, which were beyond the scope of this study. These findings underscore the complexity of IAQ management and the need for a comprehensive approach that extends beyond ventilation and filtration alone.

Furthermore, while effective ventilation with proper indoor-outdoor air exchange is generally a feasible solution for addressing the buildup of indoor pollutants, the heavy influx of wildfire-generated PM2.5 necessitates additional strategies. Enhancing building envelope tightness, incorporating advanced filtration technologies, and adjusting ACH are required to protect indoor environments from wildfire smoke infiltration and maintain a healthy indoor atmosphere.

Finally, the real-time data obtained from the LCS provided critical insights into how wildfire smoke impacts air quality over time, enabling a deeper understanding of its influence on indoor environments. This study offers valuable guidance to researchers, building administrators, and the broader scientific community in developing strategies to mitigate the effects of wildfire smoke on IAQ. With this knowledge, it could be possible to design more effective approaches to managing air quality, issuing timely public health warnings during wildfire seasons, and ultimately protecting individuals from the harmful effects of wildfire smoke.

Acknowledgments

The author would like to thank the University of Alberta Campus Sustainability Grant Program for their support through the Campus Sustainability Grant. The project was also partially supported by NSERC (RGPIN2018-03814), the Government of Canada’s Environmental Damages Fund under its Climate Action and Awareness Fund, and the Canada Foundation for Innovation (35212). JA thanks the Undergraduate Research Initiative for its Research Stipend. SO thanks the ELITE Program for Black Youth for the summer internship. The authors are also sincerely grateful to the Health, Safety, and Environment Department, University Student Residence Services, and the campus community for their invaluable assistance and participation in this project.

Supporting Information Available

The Supporting Information is available free of charge at https://pubs.acs.org/doi/10.1021/acsestair.4c00342.

  • Evaluation of LCS sensor performance and correction factor application; analysis of building characteristics; mapping of fire hotspots detected by VIIRS satellites; sensor agreement across building-wide indoor PM2.5 measurements; I/O ratio of PM2.5 during fire and non-fire days; daily average concentration of indoor PM2.5 on fire days; impact of building’s ACH on indoor PM2.5 and I/O ratio (PDF)

The authors declare no competing financial interest.

Special Issue

Published as part of ACS ES&T Airspecial issue “John H. Seinfeld Festschrift”.

Supplementary Material

ea4c00342_si_001.pdf (3.8MB, pdf)

References

  1. Cohen A. J.; Brauer M.; Burnett R.; Anderson H. R.; Frostad J.; Estep K.; Balakrishnan K.; Brunekreef B.; Dandona L.; Dandona R.; et al. Estimates and 25-year trends of the global burden of disease attributable to ambient air pollution: an analysis of data from the Global Burden of Diseases Study 2015. Lancet 2017, 389, 1907–1918. 10.1016/S0140-6736(17)30505-6. [DOI] [PMC free article] [PubMed] [Google Scholar]
  2. Fuller R.; Landrigan P. J.; Balakrishnan K.; Bathan G.; Bose-O’Reilly S.; Brauer M.; Caravanos J.; Chiles T.; Cohen A.; Corra L.; et al. Pollution and health: a progress update. Lancet Planetary Health 2022, 6, e535–e547. 10.1016/S2542-5196(22)00090-0. [DOI] [PMC free article] [PubMed] [Google Scholar]
  3. Wu W.; Jin Y.; Carlsten C. Inflammatory health effects of indoor and outdoor particulate matter. Journal of Allergy and Clinical Immunology 2018, 141, 833–844. 10.1016/j.jaci.2017.12.981. [DOI] [PubMed] [Google Scholar]
  4. Baeza_Romero M. T.; Dudzinska M. R.; Amouei Torkmahalleh M.; Barros N.; Coggins A. M.; Ruzgar D. G.; Kildsgaard I.; Naseri M.; Rong L.; Saffell J.; Scutaru A. M.; Staszowska A.; et al. A review of critical residential buildings parameters and activities when investigating indoor air quality and pollutants. Indoor Air 2022, 32, e13144 10.1111/ina.13144. [DOI] [PMC free article] [PubMed] [Google Scholar]
  5. Shrestha P. M.; Humphrey J. L.; Carlton E. J.; Adgate J. L.; Barton K. E.; Root E. D.; Miller S. L. Impact of outdoor air pollution on indoor air quality in low-income homes during wildfire seasons. International Journal of Environmental Research and Public Health 2019, 16, 3535. 10.3390/ijerph16193535. [DOI] [PMC free article] [PubMed] [Google Scholar]
  6. Karri R. R.; Vera T.; Hassan S. K. M.; Khoder M. I.; Dehghani M. H.; Mubarak N. M.; Ravindran G. Classification, sources, and occurrence of outdoor air pollutants: a comprehensive overview. Health and Environmental Effects of Ambient Air Pollution 2024, 1–34. 10.1016/B978-0-443-16088-2.00002-8. [DOI] [Google Scholar]
  7. Air pollutant emissions. Canadian Environmental Sustainability Indicators. https://www.canada.ca/en/environment-climate-change/services/environmental-indicators/air-pollutant-emissions.html. Accessed January 28, 2025.
  8. Jones M. W.; Abatzoglou J. T.; Veraverbeke S.; Andela N.; Lasslop G.; Forkel M.; Smith A. J.; Burton C.; Betts R. A.; van der Werf G. R. Global and regional trends and drivers of fire under climate change. Reviews of Geophysics 2022, 60, e2020RG000726 10.1029/2020RG000726. [DOI] [Google Scholar]
  9. Kinney P. L. Climate change, air quality, and human health. American Journal of Preventive Medicine 2008, 35, 459–467. 10.1016/j.amepre.2008.08.025. [DOI] [PubMed] [Google Scholar]
  10. Fann N.; Fulcher C. M.; Baker K. The recent and future health burden of air pollution apportioned across US sectors. Environ. Sci. Technol. 2013, 47, 3580–3589. 10.1021/es304831q. [DOI] [PubMed] [Google Scholar]
  11. Liu J. C.; Mickley L. J.; Sulprizio M. P.; Yue X.; Peng R. D.; Dominici F.; Bell M. L. Future respiratory hospital admissions from wildfire smoke under climate change in the Western US. Environmental Research Letters 2016, 11, 124018. 10.1088/1748-9326/11/12/124018. [DOI] [Google Scholar]
  12. Menezes L. S.; de Oliveira A. M.; Santos F. L.; Russo A.; de Souza R. A.; Roque F. O.; Libonati R. Lightning patterns in the Pantanal: Untangling natural and anthropogenic-induced wildfires. Science of the total environment 2022, 820, 153021. 10.1016/j.scitotenv.2022.153021. [DOI] [PubMed] [Google Scholar]
  13. Nagy R. C.; Fusco E.; Bradley B.; Abatzoglou J. T.; Balch J. Human-related ignitions increase the number of large wildfires across US ecoregions. Fire 2018, 1, 4. 10.3390/fire1010004. [DOI] [Google Scholar]
  14. Kirchmeier-Young M. C.; Gillett N. P.; Zwiers F. W.; Cannon A. J.; Anslow F. Attribution of the influence of human-induced climate change on an extreme fire season. Earth's Future 2019, 7, 2–10. 10.1029/2018EF001050. [DOI] [PMC free article] [PubMed] [Google Scholar]
  15. Tao T.Climate trends and anomalies and their impact on forest fire size and frequency from 1986 to 2020 in Canada. Ph.D. Thesis, University of Alberta, 2024. [Google Scholar]
  16. Wotton B. M.; Nock C. A.; Flannigan M. D. Forest fire occurrence and climate change in Canada. International Journal of Wildland Fire 2010, 19, 253–271. 10.1071/WF09002. [DOI] [Google Scholar]
  17. Beverly J. L.; Bothwell P. Wildfire evacuations in Canada 1980–2007. Natural Hazards 2011, 59, 571–596. 10.1007/s11069-011-9777-9. [DOI] [Google Scholar]
  18. Canadian Interagency Forest Fire Centre . Canada Report 2016. https://www.ciffc.ca/sites/default/files/2019-03/2016_canada_report_2017_05_15_v02.pdf. Accessed October 24, 2024.
  19. Canada’s record-breaking wildfires in 2023: A fiery wake-up call. September 7, 2023. https://natural-resources.canada.ca/simply-science/canadas-record-breaking-wildfires-2023-fiery-wake-call/25303. Accessed August 21, 2024.
  20. Munoz-Alpizar R.; Pavlovic R.; Moran M. D.; Chen J.; Gravel S.; Henderson S. B.; Ménard S.; Racine J.; Duhamel A.; Gilbert S.; et al. Multi-year (2013–2016) PM2. 5 wildfire pollution exposure over North America as determined from operational air quality forecasts. Atmosphere 2017, 8, 179. 10.3390/atmos8090179. [DOI] [Google Scholar]
  21. Matz C. J.; Egyed M.; Xi G.; Racine J.; Pavlovic R.; Rittmaster R.; Henderson S. B.; Stieb D. M. Health impact analysis of PM2. 5 from wildfire smoke in Canada (2013–2015, 2017–2018). Science of The Total Environment 2020, 725, 138506. 10.1016/j.scitotenv.2020.138506. [DOI] [PubMed] [Google Scholar]
  22. Wildfire Smoke Impacts on Residential Indoor Air Quality.. https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=934224. Accessed August 21, 2024.
  23. Rappold A. G.; Reyes J.; Pouliot G.; Cascio W. E.; Diaz-Sanchez D. Community vulnerability to health impacts of wildland fire smoke exposure. Environ. Sci. Technol. 2017, 51, 6674–6682. 10.1021/acs.est.6b06200. [DOI] [PMC free article] [PubMed] [Google Scholar]
  24. Mortimer K.; Gordon S. B.; Jindal S. K.; Accinelli R. A.; Balmes J.; Martin II W. J. Household air pollution is a major avoidable risk factor for cardiorespiratory disease. Chest 2012, 142, 1308–1315. 10.1378/chest.12-1596. [DOI] [PMC free article] [PubMed] [Google Scholar]
  25. DeFlorio-Barker S.; Crooks J.; Reyes J.; Rappold A. G. Cardiopulmonary effects of fine particulate matter exposure among older adults, during wildfire and non-wildfire periods, in the United States 2008–2010. Environ. Health Perspect. 2019, 127, 037006. 10.1289/EHP3860. [DOI] [PMC free article] [PubMed] [Google Scholar]
  26. Liu J. C.; Wilson A.; Mickley L. J.; Dominici F.; Ebisu K.; Wang Y.; Sulprizio M. P.; Peng R. D.; Yue X.; Son J.-Y.; et al. Wildfire-specific fine particulate matter and risk of hospital admissions in urban and rural counties. Epidemiology 2017, 28, 77–85. 10.1097/EDE.0000000000000556. [DOI] [PMC free article] [PubMed] [Google Scholar]
  27. Aguilera R.; Luo N.; Basu R.; Wu J.; Clemesha R.; Gershunov A.; Benmarhnia T. A novel ensemble-based statistical approach to estimate daily wildfire-specific PM2.5 in California (2006–2020). Environ. Int. 2023, 171, 107719. 10.1016/j.envint.2022.107719. [DOI] [PMC free article] [PubMed] [Google Scholar]
  28. Meng J.; Martin R. V.; Li C.; van Donkelaar A.; Tzompa-Sosa Z. A.; Yue X.; Xu J.-W.; Weagle C. L.; Burnett R. T. Source contributions to ambient fine particulate matter for Canada. Environ. Sci. Technol. 2019, 53, 10269–10278. 10.1021/acs.est.9b02461. [DOI] [PubMed] [Google Scholar]
  29. Rittmaster R.; Adamowicz W.; Amiro B.; Pelletier R. Economic analysis of health effects from forest fires. Canadian Journal of Forest Research 2006, 36, 868–877. 10.1139/x05-293. [DOI] [Google Scholar]
  30. Guidance for fine particulate matter (PM2.5) in residential indoor air. August 7, 2012. https://www.canada.ca/en/health-canada/services/publications/healthy-living/guidance-fine-particulate-matter-pm2-5-residential-indoor-air.html. Accessed September 16, 2022.
  31. Nazaroff W. W. Inhalation intake fraction of pollutants from episodic indoor emissions. Building and Environment 2008, 43, 269–277. 10.1016/j.buildenv.2006.03.021. [DOI] [Google Scholar]
  32. Kaduwela A. P.; Kaduwela A. P.; Jrade E.; Brusseau M.; Morris S.; Morris J.; Risk V. Development of a low-cost air sensor package and indoor air quality monitoring in a California middle school: Detection of a distant wildfire. J. Air Waste Manage. Assoc. 2019, 69, 1015–1022. 10.1080/10962247.2019.1629362. [DOI] [PubMed] [Google Scholar]
  33. Hänninen O. O.; Lebret E.; Ilacqua V.; Katsouyanni K.; Künzli N.; Srám R. J.; Jantunen M. Infiltration of ambient PM2. 5 and levels of indoor generated non-ETS PM2. 5 in residences of four European cities. Atmos. Environ. 2004, 38, 6411–6423. 10.1016/j.atmosenv.2004.07.015. [DOI] [Google Scholar]
  34. González-Martín J.; Kraakman N. J. R.; Pérez C.; Lebrero R.; Muñoz R. A state–of–the-art review on indoor air pollution and strategies for indoor air pollution control. Chemosphere 2021, 262, 128376. 10.1016/j.chemosphere.2020.128376. [DOI] [PubMed] [Google Scholar]
  35. Tran V. V.; Park D.; Lee Y.-C. Indoor air pollution, related human diseases, and recent trends in the control and improvement of indoor air quality. International Journal of Environmental Research and Public Health 2020, 17, 2927. 10.3390/ijerph17082927. [DOI] [PMC free article] [PubMed] [Google Scholar]
  36. Wildfires and Indoor Air Quality (IAQ). December 11, 2018. https://www.epa.gov/indoor-air-quality-iaq/wildfires-and-indoor-air-quality-iaq. Accessed July 21, 2022.
  37. ANSI/ASHRAE Standard 52.2-2017, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size. https://www.ashrae.org/File%20Library/Technical%20Resources/COVID-19/52_2_2017_COVID-19_20200401.pdf. Accessed June 18, 2024.
  38. Morawska L.; et al. Mandating indoor air quality for public buildings. Science 2024, 383, 1418–1420. 10.1126/science.adl0677. [DOI] [PubMed] [Google Scholar]
  39. Hänninen O.; Goodman P. Book chapter: Outdoor air as a source of indoor pollution. Issues in Environmental Science and Technology 2019, 35–65. 10.1039/9781788016179-00035. [DOI] [Google Scholar]
  40. Ventilation and the indoor environment. April 19, 2018. https://www.canada.ca/en/health-canada/services/publications/healthy-living/ventilation-indoor-environment.html. Accessed September 17, 2024.
  41. Evidence Review: Exposure measures for wildfire smoke surveillance, Provincial Health Services Authority British Colombia Centre for Disease Control, 2014. http://www.bccdc.ca/resource-gallery/Documents/Guidelines%20and%20Forms/Guidelines%20and%20Manuals/Health-Environment/WFSG_EvidenceReview_Smokesurveillance_FINAL_v2_edstrs.pdf.
  42. Afroz R.; Guo X.; Cheng C.-W.; Delorme A.; Duruisseau-Kuntz R.; Zhao R. Investigation of indoor air quality in university residences using low-cost sensors. Environmental Science: Atmospheres 2023, 3, 347–362. 10.1039/D2EA00149G. [DOI] [Google Scholar]
  43. Tryner J.; Phillips M.; Quinn C.; Neymark G.; Wilson A.; Jathar S. H.; Carter E.; Volckens J. Design and testing of a low-cost sensor and sampling platform for indoor air quality. Building and environment 2021, 206, 108398. 10.1016/j.buildenv.2021.108398. [DOI] [PMC free article] [PubMed] [Google Scholar]
  44. Hagan D. H.; Kroll J. H. Assessing the accuracy of low-cost optical particle sensors using a physics-based approach. Atmospheric Measurement Techniques 2020, 13, 6343–6355. 10.5194/amt-13-6343-2020. [DOI] [PMC free article] [PubMed] [Google Scholar]
  45. Stampfer O.; Zuidema C.; Allen R. W.; Fox J.; Sampson P.; Seto E.; Karr C. J. Practical considerations for using low-cost sensors to assess wildfire smoke exposure in school and childcare settings. Journal of Exposure Science & Environmental Epidemiology 2024, 1–12. 10.1038/s41370-024-00677-8. [DOI] [PMC free article] [PubMed] [Google Scholar]
  46. Nguyen P. D.; Martinussen N.; Mallach G.; Ebrahimi G.; Jones K.; Zimmerman N.; Henderson S. B. Using low-cost sensors to assess fine particulate matter infiltration (PM2. 5) during a wildfire smoke episode at a large inpatient healthcare facility. International Journal of Environmental Research and Public Health 2021, 18, 9811. 10.3390/ijerph18189811. [DOI] [PMC free article] [PubMed] [Google Scholar]
  47. Gupta P.; Doraiswamy P.; Levy R.; Pikelnaya O.; Maibach J.; Feenstra B.; Polidori A.; Kiros F.; Mills K. Impact of California fires on local and regional air quality: The role of a low-cost sensor network and satellite observations. GeoHealth 2018, 2, 172–181. 10.1029/2018GH000136. [DOI] [PMC free article] [PubMed] [Google Scholar]
  48. Liang Y.; Sengupta D.; Campmier M. J.; Lunderberg D. M.; Apte J. S.; Goldstein A. H. Wildfire smoke impacts on indoor air quality assessed using crowdsourced data in California. PNAS 2021, 118, e2106478118 10.1073/pnas.2106478118. [DOI] [PMC free article] [PubMed] [Google Scholar]
  49. Nova Fitness Co., Ltd. Laser PM2.5 (SDS011) Sensor specification. https://www-sd-nf.oss-cn-beijing.aliyuncs.com/%E5%AE%98%E7%BD%91%E4%B8%8B%E8%BD%BD/SDS011%20laser%20PM2.5%20sensor%20specification-V1.4.pdf. Accessed July 19, 2022.
  50. NodeMCU ESP8266 Specifications, Overview and Setting Up. September 2021. https://www.make-it.ca/nodemcu-details-specifications/. Accessed September 27, 2022.
  51. IoT Analytics - ThingSpeak Internet of Things. https://thingspeak.com/. Accessed September 28, 2024.
  52. Rahmani A. M.; Gia T. N.; Negash B.; Anzanpour A.; Azimi I.; Jiang M.; Liljeberg P. Exploiting smart e-Health gateways at the edge of healthcare Internet-of-Things: A fog computing approach. Future Generation Computer Systems 2018, 78, 641–658. 10.1016/j.future.2017.02.014. [DOI] [Google Scholar]
  53. Zimmerman N. Tutorial: Guidelines for implementing low-cost sensor networks for aerosol monitoring. J. Aerosol Sci. 2022, 159, 105872. 10.1016/j.jaerosci.2021.105872. [DOI] [Google Scholar]
  54. Jayaratne R.; Liu X.; Thai P.; Dunbabin M.; Morawska L. The influence of humidity on the performance of a low-cost air particle mass sensor and the effect of atmospheric fog. Atmospheric Measurement Techniques 2018, 11, 4883–4890. 10.5194/amt-11-4883-2018. [DOI] [Google Scholar]
  55. Tagle M.; Rojas F.; Reyes F.; Vásquez Y.; Hallgren F.; Lindén J.; Kolev D.; Watne Å. K.; Oyola P. Field performance of a low-cost sensor in the monitoring of particulate matter in Santiago, Chile. Environmental monitoring and assessment 2020, 192, 171. 10.1007/s10661-020-8118-4. [DOI] [PMC free article] [PubMed] [Google Scholar]
  56. Crilley L. R.; Shaw M.; Pound R.; Kramer L. J.; Price R.; Young S.; Lewis A. C.; Pope F. D. Evaluation of a low-cost optical particle counter (Alphasense OPC-N2) for ambient air monitoring. Atmospheric Measurement Techniques 2018, 11, 709–720. 10.5194/amt-11-709-2018. [DOI] [Google Scholar]
  57. Duvall R.; Clements A.; Hagler G.; Kamal A.; Kilaru V.; Goodman L.; Frederick S.; Barkjohn K.; VonWald I.; Greene D.; et al. Performance Testing Protocols, Metrics, and Target Values for Fine Particulate Matter Air Sensors: Use in Ambient, Outdoor, Fixed Sites, Non-Regulatory Supplemental and Informational Monitoring Applications. US EPA Office of Research and Development, 2021.
  58. Alberta wildfire’s seasonal statistics. https://open.alberta.ca/publications/alberta-wildfire-season-statistics. Accessed January 27, 2025.
  59. Air indicators – Fine particulate matter | Alberta.ca. August 16, 2024. https://www.alberta.ca/air-indicators-fine-particulate-matter. Accessed August 23, 2024.
  60. He J.; Huang C.-H.; Yuan N.; Austin E.; Seto E.; Novosselov I. Network of low-cost air quality sensors for monitoring indoor, outdoor, and personal PM2. 5 exposure in Seattle during the 2020 wildfire season. Atmos. Environ. 2022, 285, 119244. 10.1016/j.atmosenv.2022.119244. [DOI] [Google Scholar]
  61. Li Z.; Wen Q.; Zhang R. Sources, health effects and control strategies of indoor fine particulate matter (PM2. 5): A review. Sci. Total Environ. 2017, 586, 610–622. 10.1016/j.scitotenv.2017.02.029. [DOI] [PubMed] [Google Scholar]
  62. Hu Y.; Zhao B. Indoor sources strongly contribute to exposure of Chinese urban residents to PM2. 5 and NO2. Journal of Hazardous Materials 2022, 426, 127829. 10.1016/j.jhazmat.2021.127829. [DOI] [PubMed] [Google Scholar]
  63. Wei S.; Semple S. Exposure to fine particulate matter (PM2. 5) from non-tobacco sources in homes within high-income countries: a systematic review. Air Quality, Atmosphere & Health 2023, 16, 553–566. 10.1007/s11869-022-01288-8. [DOI] [PMC free article] [PubMed] [Google Scholar]
  64. Wallace L.; Williams R. Use of personal-indoor-outdoor sulfur concentrations to estimate the infiltration factor and outdoor exposure factor for individual homes and persons. Environ. Sci. Technol. 2005, 39, 1707–1714. 10.1021/es049547u. [DOI] [PubMed] [Google Scholar]
  65. Bhangar S.; Mullen N. A.; Hering S. V.; Kreisberg N. M.; Nazaroff W. Ultrafine particle concentrations and exposures in seven residences in northern California. Indoor Air 2011, 21, 132–144. 10.1111/j.1600-0668.2010.00689.x. [DOI] [PubMed] [Google Scholar]
  66. Schneider S. R.; Lee K.; Santos G.; Abbatt J. P. Air quality data approach for defining wildfire influence: Impacts on PM2. 5, NO2, CO, and O3 in Western Canadian cities. Environ. Sci. Technol. 2021, 55, 13709–13717. 10.1021/acs.est.1c04042. [DOI] [PubMed] [Google Scholar]
  67. Vadrevu K.; Lasko K. Intercomparison of MODIS AQUA and VIIRS I-Band fires and emissions in an agricultural landscape—Implications for air pollution research. Remote Sensing 2018, 10, 978. 10.3390/rs10070978. [DOI] [PMC free article] [PubMed] [Google Scholar]
  68. Ye W.; Zhang X.; Gao J.; Cao G.; Zhou X.; Su X. Indoor air pollutants, ventilation rate determinants and potential control strategies in Chinese dwellings: a literature review. Sci. Total Environ. 2017, 586, 696–729. 10.1016/j.scitotenv.2017.02.047. [DOI] [PubMed] [Google Scholar]
  69. Belias E.; Licina D. Outdoor PM2. 5 air filtration: optimizing indoor air quality and energy. Building & Cities 2022, 3, 186–203. 10.5334/bc.153. [DOI] [Google Scholar]
  70. Jung C.-C.; Wu P.-C.; Tseng C.-H.; Su H.-J. Indoor air quality varies with ventilation types and working areas in hospitals. Building and Environment 2015, 85, 190–195. 10.1016/j.buildenv.2014.11.026. [DOI] [Google Scholar]
  71. Chen C.; Zhao B. Review of relationship between indoor and outdoor particles: I/O ratio, infiltration factor and penetration factor. Atmospheric environment 2011, 45, 275–288. 10.1016/j.atmosenv.2010.09.048. [DOI] [Google Scholar]
  72. Jelili M. O.; Gbadegesin A. S.; Alabi A. T. Comparative analysis of indoor and outdoor particulate matter concentrations and air quality in Ogbomoso, Nigeria. Journal of Health and Pollution 2020, 10, 201205. 10.5696/2156-9614-10.28.201205. [DOI] [PMC free article] [PubMed] [Google Scholar]
  73. Alonso-Blanco E.; Gómez-Moreno F. J.; Díaz-Ramiro E.; Fernández J.; Coz E.; Yagüe C.; Román-Cascón C.; Narros A.; Borge R.; Artíñano B. Real-Time Measurements of Indoor–Outdoor Exchange of Gaseous and Particulate Atmospheric Pollutants in an Urban Area. International journal of environmental research and public health 2023, 20, 6823. 10.3390/ijerph20196823. [DOI] [PMC free article] [PubMed] [Google Scholar]
  74. Deng G.; Li Z.; Wang Z.; Gao J.; Xu Z.; Li J.; Wang Z. Indoor/outdoor relationship of PM2. 5 concentration in typical buildings with and without air cleaning in Beijing. Indoor and Built Environment 2017, 26, 60–68. 10.1177/1420326X15604349. [DOI] [Google Scholar]
  75. Guidance Document on Achievement Determination: Canadian Ambient Air Quality Standards for Fine Particulate Matter and Ozone; Canadian Council of Ministers of the Environment, 2012. https://publications.gc.ca/collections/collection_2013/ccme/En108-4-55-2012-eng.pdf. Accessed August 20, 2024. [Google Scholar]
  76. Li T.; Siegel J. A. In situ efficiency of filters in residential central HVAC systems. Indoor Air 2020, 30, 315–325. 10.1111/ina.12633. [DOI] [PubMed] [Google Scholar]
  77. Kulmala I.; Zwęgliński T.; Smolarkiewicz M.; Salmela H.; Kalliohaka T.; Taipale A.; Kataja J.; Mäkipää V. Effect of enhanced supply air filtration in buildings on protecting citizens from environmental radioactive particles. Building Simulation 2020, 13, 865–872. 10.1007/s12273-020-0621-6. [DOI] [Google Scholar]
  78. Fazli T.; Zeng Y.; Stephens B. Fine and ultrafine particle removal efficiency of new residential HVAC filters. Indoor Air 2019, 29, 656–669. 10.1111/ina.12566. [DOI] [PubMed] [Google Scholar]
  79. Why Wildfire Smoke is a Health Concern. https://www.epa.gov/wildfire-smoke-course/why-wildfire-smoke-health-concern. Accessed January 27, 2025.
  80. Filtration and Disinfection. https://www.ashrae.org/technical-resources/filtration-disinfection. Accessed June 18, 2024.
  81. Macneill M.; Dobbin N.; St-Jean M.; Wallace L.; Marro L.; Shin T.; You H.; Kulka R.; Allen R. W.; Wheeler A. J. Can changing the timing of outdoor air intake reduce indoor concentrations of traffic-related pollutants in schools?. Indoor Air 2016, 26, 687–701. 10.1111/ina.12252. [DOI] [PubMed] [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Supplementary Materials

ea4c00342_si_001.pdf (3.8MB, pdf)

Articles from ACS Es&t Air are provided here courtesy of American Chemical Society

RESOURCES