Abstract
With the widespread application of lithium-ion battery energy storage systems and electric vehicle power batteries, optimizing liquid cooling systems to effectively manage heat and prevent thermal runaway has become crucial for enhancing the safety and efficiency of energy storage systems. Addressing issues of cooling efficiency and uneven temperature distribution in battery packs, this study designed a parallel serpentine channel liquid cooling plate to improve coolant flow efficiency and heat exchange capacity by optimizing the channel structure. The temperature distribution of the battery pack under different discharge rates (1, 1.5, and 2 C) and the impact of two layouts of the parallel serpentine channel on cooling performance are investigated to identify the optimal configuration. Numerical simulations of a 280 Ah lithium-ion battery are conducted using Ansys Fluent and AMEsim, establishing a thermal model based on Bernardi’s heat generation rate, mass flow, and conservation equations of momentum and energy. Experimental results demonstrate that the second layout exhibits a superior cooling performance and better thermal uniformity. Increasing the coolant flow rate effectively reduces the maximum temperature of the battery pack under 2 C operation, highlighting the significance of the optimized liquid cooling system design in enhancing the safety and performance of lithium-ion battery packs.


1. Introduction
As the world turns its focus toward sustainable energy solutions, the importance of lithium-ion batteries in the fields of clean energy storage and electric vehicle energy supply has surged. They are utilized broadly across energy storage systems, electric vehicles, hand-held electronics, and diverse areas within the renewable energy market. − The shift from traditional lead-acid and nickel-hydride batteries to lithium-ion batteries is driven by their higher energy density, extended cycle life, and green credentials. However, during high-rate charge and discharge processes, they generate significant heat, which, if not effectively managed, can lead to thermal runaway. This not only impacts battery performance and lifespan but can also pose safety risks. , Hence, it is vital to improve the thermal management solutions for lithium-ion batteries so that the working temperatures stay within the recommended band of 20 to 40 °C and the temperature differences are confined to a maximum of 5 °C, thereby increasing the system’s safety and trustworthiness.
Among various battery cooling technologies, such as air cooling, phase change material cooling, and heat pipe cooling, liquid cooling systems are rapidly emerging as the mainstream choice for thermal management in high power density lithium-ion battery packs due to their superior thermal conductivity and high heat dissipation efficiency. , Compared to air cooling systems, which have limited heat dissipation capabilities and can lead to uneven temperature distribution, liquid cooling systems efficiently transfer and remove heat generated by the batteries using forced circulation of cooling media (e.g., water-glycol solutions and insulating oils), significantly suppressing battery temperature rise. Research indicates , that well-designed liquid cooling systems not only substantially enhance battery cycle life by reducing temperature-induced degradation but also optimize performance under extreme conditions (e.g., high discharge rates). This is crucial for promoting the widespread adoption of electric vehicles and large-scale energy storage applications, especially in high power and energy density scenarios. Moreover, efficient battery thermal management systems maintain batteries in optimal operating ranges and extend their lifespan, indirectly reducing additional energy consumption and carbon dioxide emissions resulting from premature battery replacements or system inefficiencies, aligning with global carbon reduction goals. ,
Despite the clear advantages of liquid cooling technology, existing design proposals, such as simple straight channel designs and fixed flow rate strategies, still face challenges like inadequate heat dissipation efficiency, poor temperature uniformity, and high energy consumption. , For instance, commonly used straight channel designs often exhibit uneven coolant distribution, leading to flow “dead zones” and localized overheating. Additionally, the short flow paths restrict heat exchange between the coolant and heat sources. Furthermore, previous research has predominantly focused on optimizing coolant flow rates, flow volume, or inlet temperatures, while there has been insufficient exploration of innovative designs of flow channel geometries and their impact on the combined performance of flow and heat transfer, limiting further enhancement of system performance. To address these limitations, particularly the shortcomings of traditional channel designs in terms of thermal uniformity and heat dissipation efficiency, this study proposes and investigates a novel parallel serpentine channel liquid cooling plate design aimed at improving coolant utilization and heat exchange capabilities through an optimized channel layout.
Compared to traditional single straight channels or simple serpentine paths, the proposed parallel serpentine channel structure offers multiple advantages: (1) parallel branching effectively reduces overall flow resistance, allowing for increased flow rate or reduced energy consumption under the same pump power; (2) the serpentine path combined with the parallel design promotes more comprehensive coolant coverage across the entire battery surface, significantly reducing flow dead zones; and (3) thoughtfully designed channel shapes and layouts facilitate uniform coolant distribution and efficient heat exchange on the battery pack surface, greatly improving temperature uniformity. To rigorously evaluate the performance of this design, this study employs a multiphysics coupled numerical simulation approach using Ansys Fluent for detailed fluid dynamics and heat transfer analysis, complemented by AMESim for system-level thermal management strategy simulations. This high-fidelity modeling method enables precise capturing of the complex interactions between battery heat generation characteristics, coolant flow, and heat transfer processes, allowing for an in-depth analysis of temperature field evolution and heat dissipation efficiency and providing a solid theoretical basis for optimization design.
In conclusion, this study presents an innovative parallel serpentine channel design that offers new insights into addressing the bottlenecks in the heat dissipation efficiency and temperature uniformity in existing liquid cooling systems. The simulation results not only validate the effectiveness of this design but also lay a significant foundation for the development of high-performance lithium-ion battery thermal management systems. More importantly, advancements in such efficient thermal management technologies directly support the large-scale application of electric vehicles and energy storage systems by ensuring battery safety, enhancing performance, and prolonging the lifespan, thereby playing a vital role in reducing fossil fuel dependency and carbon emissions in the transportation and energy sectors and promoting the transition to clean energy.
2. Related Work
Battery thermal management system (BTMS) cooling methodologies are segmented into three key strategies: passive, active, and integrated hybrid systems.
2.1. Passive Cooling Systems
Passive cooling systems do not consume additional power and cannot actively adjust cooling rates; they typically enhance thermal exchange between lithium-ion batteries and the environment by employing conductive materials or specialized structures on the battery surface. Passive cooling techniques commonly involve natural convection, , phase change material utilization (PCMs), − and heat pipe technology. − While passive air cooling is cost-effective, it often lacks sufficient cooling capacity to meet the demands of high-energy-density lithium batteries. PCMs exhibit a high capacity for energy storage and release during their phase transitions; however, their low thermal conductivity limits heat dissipation rates, especially during high-rate charge and discharge, which may pose safety risks. − In contrast, heat pipes offer exceptionally high thermal conductivity, but their effectiveness is constrained by the installation orientation and limited applicability under extreme conditions.
2.2. Active Cooling Systems
Active cooling systems, reliant on mechanical actuators like fans and pumps, consume additional energy to circulate cooling fluids, encompassing active air, liquid, , and phase change cooling methods. − Active air cooling uses electric fans or blowers to forcibly draw air into the heat dissipation areas of battery packs or motors, effectively removing heat, especially during high power output or charging. However, their efficiency may decrease in high-temperature environments and they require significant space for ductwork and fans.
Liquid cooling systems represent the mainstream trend in cooling technology for new energy vehicles, circulating water, or water-based coolants between the battery pack and the radiator. The system harnesses liquid’s high heat capacity and thermal conductivity for efficient cooling in tight spaces, with adaptable flow and temperature settings for precise thermal control. Additionally, liquid cooling offers excellent thermal uniformity, effectively avoiding temperature disparities within the battery pack and thereby enhancing overall performance and lifespan. As the cooling performance demands for new energy vehicles continue to rise, liquid cooling systems are becoming the preferred choice due to their efficiency and reliability, with widespread applications in commercial electric vehicles like Tesla and BYD.
Studies have examined various liquid cooling strategies. For instance, Monika et al. assessed an optimized mini-channel liquid cooling system for LiFePO4 batteries in EVs/HEVs, demonstrating that parameter adjustmentssuch as channel count and coolant flow ratestabilize module temperatures between 25 and 40 °C. Guo et al. evaluated the thermal performance of lithium-ion battery modules under liquid cooling conditions, concluding that increasing the flow channel area and coolant mass flow rate significantly reduces peak temperatures and temperature differences during charge and discharge cycles. Yang et al. proposed a multichannel conical flow structure, demonstrating through eight design comparisons that the conical channel effectively enhances cooling performance and reduces energy consumption. Liu et al. designed a series/parallel symmetric liquid cooling flow structure, achieving a 15% reduction in maximum temperature differences and improved temperature uniformity, thereby optimizing cooling efficiency and energy consumption. Although two-phase cooling technology has shown excellent thermal management capabilities in certain high-end applications, its cost and complexity have hindered widespread adoption. Consequently, liquid cooling occupies a pivotal role in the current trends of cooling systems for new energy vehicles, becoming a key focus for future development.
2.3. Hybrid Cooling Systems
Hybrid cooling solutions adeptly blend active and passive techniques for superior thermal management with enhanced flexibility. In electric vehicles, these systems utilize liquid cooling for robust thermal management during high loads or fast charging while relying on air cooling at lower loads or stationary conditions to conserve energy and reduce costs. This adaptable cooling method can dynamically adjust to different operating conditions, ensuring that the battery and motor maintain optimal operating temperatures and thereby enhance overall performance and safety.
Luo et al. developed a novel hybrid battery thermal management system (BTMS) comprising a U-shaped micro heat pipe array (U-MHPA) and composite phase change materials (CPCM) to address significant surface temperature gradients and uneven cooling in battery modules. Lu et al. developed a state-of-the-art hybrid thermal control system, integrating phase change materials with microchannel cooling, to effectively suppress thermal runaway. However, the adoption of such systems in electric vehicles is impeded by design and integration complexities, which heighten the demands for both system design and control. Additionally, cost poses a significant barrier; hybrid cooling systems typically involve more materials and components, driving up manufacturing costs, particularly in the electric vehicle market. As new energy vehicles trend toward lighter and more compact designs, hybrid systems may occupy more space and add weight, negatively impacting the overall performance. Furthermore, the maturity of cooling technology in the market influences the promotion of hybrid systems, with many manufacturers preferring established conventional cooling solutions over the risks associated with more complex hybrid systems. Therefore, while hybrid cooling systems have considerable theoretical potential, practical applications face numerous challenges, hindering their widespread adoption.
3. Model Development
3.1. Battery Model
A 3.2 V, 280 Ah LiFePO4 energy storage battery, dimensions 173 × 72 × 207 mm, was examined. Two liquid cooling models, each with eight series-connected cells, were designed to evaluate the cooling performance of plates on the battery’s large surface and end surface, as shown in Figure .
1.
Battery model diagram.
In Scheme One, the eight batteries are arranged side by side with a 1 mm thick silicone thermal pad placed between each pair of batteries. Additionally, two large thermal pads are attached to each side of the battery, resulting in a total of nine thermal pads used. The cooling plate, integrated with a liquid system, is affixed laterally to the battery, aligning with the large thermal pads.
Scheme Two features the same battery arrangement as Scheme One. However, it employs a combination of thermal pads, liquid cooling plates, and additional thermal pads between each pair of batteries, resulting in a total of 16 thermal pads and nine liquid cooling plates. Both schemes employ 10 mm thick liquid cooling plates, channeling a glycol-water mixture through 10 mm × 8 mm parallel serpentine channels to maximize cooling efficiency. Battery specifics and material traits are listed in Table .
1. Basic Parameters of Battery Cells.
| parameter name | value |
|---|---|
| nominal capacity (Ah) | 280 |
| nominal voltage (V) | 3.2 |
| dimensions (L × W × H) | 173 × 72 × 207 |
| weight (kg) | 5.6 ± 0.3 |
| operating temperature (°C) | charging: 0–55; discharging: −30 ∼ 55 |
3.2. Thermal Model
Heat output (Q) in lithium-ion batteries during charge–discharge cycles stems from four primary sources: reaction (Q a), Joule (Q b), polarization (Q c), and side-reaction heating (Q d), closely tied to the battery’s current, resistance, reaction kinetics, and side-reaction propensity.
| 1 |
reaction (Q a), Joule (Q b), polarization (Q c), and side-reaction (Q d) heats arise from lithium-ion intercalation/deintercalation, resistive losses, voltage discrepancies, and undesirable chemistry, respectively.
Measuring the battery’s volumetric heat generation rate (q) in practical conditions is daunting. Bernardi’s formula facilitates the calculation of this rate.
| 2 |
Given the complex internal structure of lithium-ion batteries, comprising electrodes, aluminum foil, and separators, we assume a uniform internal temperature and constant thermal conductivity, specific heat, and resistivity during simulations. Heat transfer is mainly through conduction, neglecting radiation and convection. Chemical reactions are considered reversible with no significant energy loss, and external conditions, such as temperature and humidity, are stable. The impact of side reactions on the thermal balance is generally disregarded.
Based on these assumptions, we use Fourier’s law of heat conduction, where heat flux is proportional to temperature gradient, combined with energy conservation to establish a 3D thermal conduction equation to better understand the thermal behavior of lithium-ion batteries under various conditions.
| 3 |
where: ρbattery density, kg m–3; cspecific heat capacity of the battery, J(kg K)−1; λm, λn, λuthermal conductivity of the battery in the m, n, u directions, W (m K)−1; the partial derivative of temperature T with respect to time t, (K/s); second-order partial derivatives of temperature T in the m, n, u directions, (K/m2); qaverage heat generation rate of the battery, W m–3; Ttemperature, °C; and tdischarge time of the battery, s.
3.3. Control Equation Model
Fluid dynamics insight is pivotal for battery liquid cooling system design and analysis, focusing on thermal performance metrics of cooling plates, such as thermal diffusivity, convective heat transfer coefficient, and fluid flow resistance. These factors are essential for thermal regulation performance, impacting battery safety and longevity.
Deriving control equations from conservation principles of mass, momentum, and energy is crucial for precise simulation and enhancement. These equations chart cooling fluid dynamics and heat transfer in the battery system, providing a basis for evaluating and refining the cooling efficiency. A comprehensive analysis of these equations clarifies the cooling fluid’s role in heat dissipation, guiding system optimization.
3.3.1. Performance Parameter Equations for Liquid Cooling Plates
The performance parameters of the liquid cooling plates can be described by the following equations
| 4 |
| 5 |
| 6 |
| 7 |
| 8 |
| 9 |
where: p inlet, p outletinlet and outlet pressures; Qheat transfer of the coolant; T maxmaximum temperature of the battery; T inlet, T outlettemperatures of the coolant at the inlet and outlet; Asurface area of the channel; mmass flow rate of the coolant; N μNusselt number; ReReynolds number; PrPrandtl number with a value of 6.22; μinletinlet velocity of the coolant; Dhydraulic diameter; and Ltotal length of the flow channel.
3.3.2. Mass Conservation Equation
| 10 |
where: ρmdensity of the coolant, kg/m3 and vvelocity of the coolant, m/s.
3.3.3. Momentum Conservation Equation
| 11 |
where: pstatic pressure of the coolant, Pa and μmdynamic viscosity of the coolant, (N s)/m2.
3.3.4. Energy Conservation Equation
| 12 |
where: C mspecific heat capacity of the coolant, J/(kg K); T mtemperature of the coolant, K; and λmthermal conductivity of the coolant, W/(m K).
4. Experimental Preparation
4.1. Boundary Condition Setup in Fluent
Thermal generation rates for battery discharge at 1, 1.5, and 2 C were determined using eq , as detailed in Table . The system’s initial temperature was set at 20 °C, and calculations were conducted with a turbulence model. Interfaces between the battery and the thermal pad, and between the thermal pad and the liquid cooling plate, were modeled as solid–solid coupled contact interfaces. The interface between the liquid cooling plate and the coolant flow channel was modeled as a fluid–solid coupled interface. To conserve computational resources, the battery module’s heat source was approximated as a heat flux boundary on the thermal conductive material’s surface. A coolant blend of 50% water and 50% ethylene glycol was chosen, with a flow velocity of 0.1 m/s and an outlet pressure of 0 Pa. Natural convection was assumed between the battery module and the liquid cooling plate as well as with the external environment, with a convective heat transfer coefficient of 3 W/(m2 K). The battery’s initial state of charge (SOC) was set at 100%. Table summarizes the pertinent material properties and thermal characteristics.
2. Battery Thermal Generation Rates at Diverse Discharge Rates.
| discharge rate (C) | battery thermal generation rate (W/m3) |
|---|---|
| 1 | 7601.64 |
| 1.5 | 17103.68 |
| 2 | 30406.55 |
3. Material Properties.
| material | density (kg/m3) | specific heat capacity [J/(kg K)] | thermal conductivity [W/(m K)] |
|---|---|---|---|
| battery cell | 2218 | 1033 | 17.3/5.3/23 |
| thermal pad | 2000 | 1800 | 1.8 |
| aluminum | 2719 | 871 | 202.4 |
| copper | 8978 | 381 | 387.6 |
| 50% water + 50% ethylene glycol mixture | 1071 | 3300 | 0.384 |
4.2. Mesh Generation in Fluent
In the mesh generation process, a Poly-Hexcore mesh type with smooth-transition boundary layers is used with three layers and an expansion ratio of 1.2. Figures and provide mesh details: Figure a shows the sectional view of the volume mesh for Scheme One; Figure b,c illustrates surface and volume mesh quality, with 930,956 surface meshes and 2,613,145 volume meshes. Figure a presents the sectional view for option 2; Figure b,c shows surface and volume mesh quality, with 1,238,912 surface meshes and 3,367,755 volume meshes. Both schemes have a surface mesh orthogonal quality below 0.75 and volume mesh orthogonal quality below 0.15, indicating satisfactory overall mesh quality for computational purposes.
2.
Mesh information for Scheme One. (a) Scheme One volume mesh, (b) scheme One surface mesh quality, and (c) scheme One volume mesh quality.
3.
Mesh information for Scheme Two. (a) Scheme Two volume mesh, (b) scheme Two surface mesh quality, and (c) scheme Two volume mesh quality.
4.3. Grid Independence and Analysis of Results
Under the initial boundary conditions, Scheme One achieved different mesh densities by adjusting the mesh size parameters, resulting in a total of 1,131,231, 1,696,847, 2,375,586, 2,613,145, 2,874,460, and 3,305,626 mesh elements. As shown in Figure a, the maximum temperature and temperature difference within the battery module exhibited negligible changes when the mesh count exceeded 2,613,145; thus, 2,613,145 was selected as the optimal mesh density.
4.
Grid independence test.
Similarly, Scheme Two also varied the mesh size parameters to obtain different mesh counts (841,939, 1,683,878, 3,367,755, and 5,051,632). The results, presented in Figure b, indicated that when the mesh count surpassed 3,367,755, the maximum temperature (T max) of the battery module and the pressure drop of the coolant remained constant. Consequently, Scheme Two adopted 3,367,755 as the baseline mesh size for subsequent research, ensuring computational accuracy while minimizing computational costs.
4.4. Establishment of the AMEsim Model
The AMEsim models for both options were created, as presented in Figure . Figure a portrays the liquid cooling plate located on the cell’s side. In this design, the cooling plate is positioned along the cell’s side, transferring heat away via coolant flow. Figure b illustrates the liquid cooling plate placed on the cell’s large surface. Here, the cooling plate is directly connected to the cell’s primary contact area, effectively dissipating heat generated during charge and discharge cycles through the circulating coolant. By comparing these two configurations, we gain insight into their distinct applications and performance characteristics in battery thermal management.
5.
AMEsim model construction diagrams for both Schemes. (a) Construction diagram for Scheme One. (b) Construction diagram for Scheme Two.
5. Result Analysis
5.1. Fluent Analysis of Both Schemes
5.1.1. Scheme One
In Scheme One, Figure illustrates the temperature distribution of the battery pack and coolant at various discharge rates. Specifically, Figure a shows the overall, cross-sectional, and coolant temperature distribution at a 1 C discharge rate; Figure b presents the corresponding distribution at a 1.5 C rate; and Figure c depicts the scenario at a 2 C rate. The color bar indicates the temperature range, with blue representing lower temperatures and red indicating higher temperatures.
6.
Temperature distribution patterns of the battery in Scheme One at varied discharge rates.
As depicted in Figure a, with a discharge rate of 1 C, the battery temperature increases from 20 to 26.91 °C and the coolant from 20.16 to 21.61 °C. Under 1.5 C as shown in Figure b, temperatures climb from 20 to 35.54 °C for the battery and from 20.37 to 23.62 °C for the coolant. In comparison with the 1 C discharge rate, the battery’s aggregate temperature has experienced an upsurge. Figure c indicates that a 2 C rate results in battery temperatures between 20 and 47.62 °C and coolant from 20.66 to 26.44 °C. Higher discharge rates elevate temperatures due to increased current flow and heat generation.
Figure illustrates the battery pack’s temperature variation across different discharge rates, highlighting performance distinctions. The coolant flow efficiently extracts heat, decreasing the battery’s peak temperature while increasing its own. A higher heat transfer capability at the inlet kept the battery cooler. As the coolant heats while moving, system efficiency drops, raising the battery temperature, leading to higher outlet temperatures. This distribution underscores the crucial role of coolant flow in thermal management.
7.
Temperature variation curves of battery pack under different discharge rates for Scheme One.
5.1.2. Scheme Two
In Scheme Two, Figure illustrates the temperature distribution of the battery pack and coolant at various discharge rates. Specifically, Figure a shows the overall, cross-sectional, and coolant temperature distribution at a 1 C discharge rate; Figure b presents the corresponding distribution at a 1.5 C rate; and Figure c depicts the scenario at a 2 C rate. The color bar depicted in the figure illustrates the temperature range with blue representing lower temperatures and red signifying higher temperatures.
8.
Temperature distribution of the battery pack in Scheme Two at different discharge rates.
Figure a illustrates the battery temperature distribution at a 1 C discharge rate rising from 20 to 21.81 °C and coolant from 20.05 to 20.51 °C. In Figure b at 1.5 C, battery temperatures rise from 20 to 24.09 °C and coolant from 20.12 to 21.17 °C. Figure c at 2 C shows temperatures rising from 20 to 27.27 °C for the battery and 20.21 to 22.09 °C for the coolant. Higher discharge rates increase battery temperatures but less steeply than in Scheme One.
Figure shows the battery pack’s temperature variation curve, with central temperatures higher due to internal resistance. Current flow and electrochemical reactions generate heat, while the separator’s poor thermal conductivity creates significant resistance, resulting in a gradient. This highlights the need to address the internal resistance and material limitations in thermal management. Strategies should optimize design and materials to minimize gradients, enhancing performance, and safety.
9.
Temperature variation curves of battery pack under different discharge rates for Scheme Two.
5.2. AMEsim Analysis of Two Schemes
Figure presents the temperature variation curves for the battery pack in option one. Specifically, Figure a illustrates temperature changes at a 1 C discharge rate. Over time, the battery temperature gradually increased, with a more pronounced increase observed around 2000 s. By 2400 s, the temperature of cell-8 at the cooling channel outlet reached nearly 26 °C, marking the highest value in the pack.
10.
Temperature change curves for AMEsim’s Scheme One battery pack.
Figure b presents the temperature variation at a discharge rate of 1.5 C. Compared to 1 C, the temperature rise rate significantly accelerates, becoming steeper by 1500 s. By 2400 s, cell-8’s temperature at the cooling channel outlet approaches 28 °C, maintaining the highest temperature.
Figure c shows the temperature changes at a discharge rate of 2 C discharge rate. The temperature increase is even more rapid than at the lower rates. Around 1100 s, the temperature rise accelerates dramatically; by 1800 s, all cells approach or exceed 30 °C, with cell-8 once again recording the highest temperature.
These results indicate that higher discharge rates intensify the electrochemical reactions within the battery, significantly increasing heat generation beyond the cooling system’s capacity in Scheme One. Additionally, internal resistance during high-rate discharging converts more power to heat, exacerbating the temperature increases. Therefore, to achieve efficient heat dissipation and maintain safety, a well-structured cooling strategy and precise placement of liquid cooling plates are vital. Enhancing the cooling system optimizes battery performance, safety, lifespan, and economic efficiency.
Figure a shows the temperature increase of the battery cells at a discharge rate of 1 C. Notably, after 2000 s, the rate of temperature increase accelerates significantly, with cell-4 in the middle of the pack reaching nearly 23 °C. The temperature growth curves of the individual cells show good consistency, indicating minimal temperature differences among cells at this discharge rate.
11.
AMEsim Scheme Two battery pack temperature variation curves.
When the discharge rate increases to 1.5 C, Figure b reveals a faster temperature rise. Around 1500 s, the trend becomes more pronounced, and by 2400 s, all cells approach or exceed 24 °C, with cell-4 again reaching the highest temperature. The consistent temperature response across the cells suggests synchronized behavior under the 1.5 C discharge conditions.
Figure c illustrates the temperature changes at a 2 C discharge rate, where the rate of temperature increase is notably faster. After 1200 s, the trend is clearly evident, and by 1800 s, all cells reach or exceed 27 °C, with cell-4 hitting a new peak. Despite the extreme discharge conditions, the temperature growth curves maintain consistency among the cells, emphasizing uniform temperature responses.
Figures and illustrate simulation outcomes that align with fluent results from Figures and , underscoring the model’s accuracy and credibility. These temperature profiles effectively highlight the thermal management capabilities of the battery pack across various discharge rates, which are crucial for evaluating thermal response attributes and their effect on system performance. Analyzing these data enhances our understanding of how the battery pack manages heat generation and its cooling capabilities at various discharge rates, providing critical insights for subsequent design optimizations.
5.3. Impact of the Coolant Flow Rate
This simulation study focuses on optimizing the liquid cooling system in Scheme Two to determine the best coolant conditions for practical applications. The role of the coolant flow rate in enhancing cooling efficiency and its crucial impact on battery temperature regulation are highlighted.
The simulations implemented a discharge rate of 2 C, maintaining both the ambient temperature and the initial coolant temperature at 20 °C. By varying the coolant flow rate, we analyzed its impact on system performance. Figure shows the temperature distribution and coolant flow vector distribution under various flow rates: (a) 0.10, (b) 0.15, (c) 0.2, (d) 0.25, (e) 0.3, and (f) 0.35 m/s.
12.
Contours of temperature and velocity vectors at different flow rates.
Figure illustrates that at a coolant flow rate of 0.10 m/s, the battery’s peak temperature reached 27.29 °C. As the flow rate increased, the peak temperature decreased, highlighting the critical role of the flow rate in cooling efficiency. Notably, increasing the flow rate from 0.10 to 0.25 m/s significantly enhanced the cooling effect, lowering the peak temperature by 0.93 °C. However, further raising the flow rate to 0.35 m/s yielded diminishing returns, suggesting a nonlinear relationship between the flow rate and cooling efficiency.
13.

Effects of various flow rates on cooling efficiency.
The simulations illustrate that optimizing the coolant flow rate is vital for enhancing the efficiency of liquid cooling systems, offering indispensable insights for future design and application strategies.
Figure illustrates the relationship between the pressure drop and coolant flow rate in the liquid cooling plate. The results indicate that as the flow rate increases, the pressure drop across the cooling plate also rises. This trend highlights the close correlation between the flow rate and system load. Specifically, while higher flow rates effectively enhance cooling performance by improving heat exchange rates to better manage thermal loads, they also result in significantly increased energy consumption for the liquid cooling system, thereby affecting overall energy efficiency. This phenomenon can be attributed to fluid dynamics principles, where increased flow rates lead to greater friction losses and fluid resistance, requiring the system to supply more energy to maintain flow. Therefore, when designing liquid cooling systems, it is critical to balance cooling effectiveness with energy consumption to achieve higher energy utilization efficiency and system stability.
14.

Effect of different flow rates on pressure drop across the liquid cooling plate.
Additionally, analysis of the velocity vector field in Figure reveals that the flow rate can induce stagnation points at channel bends, which may adversely affect the efficiency of coolant flow and cooling performance. Therefore, excessively high flow rates are not always beneficial, as they can result in unnecessary energy losses and increased system complexity, ultimately impacting overall performance.
Consequently, selecting an optimal coolant flow rate requires a comprehensive consideration of cooling effectiveness, energy consumption, and pressure drop across the cooling plate. A well-optimized flow rate can effectively lower the battery pack temperature while minimizing energy use and pressure drop, thus enabling efficient system operation. By optimization of flow rates, it is possible to enhance cooling performance while ensuring economic and stable system operation.
5.4. Model Evaluation and Comparison Methods
To ensure the effectiveness and reliability of the developed parallel serpentine flow channel liquid cooling plate model, the following evaluation and comparison methods were employed.
5.4.1. Multicondition Comparative Analysis
A simulation analysis was conducted on two liquid cooling plate configurations under different discharge rates (1 C, 1.5 C, and 2 C). Key indicators such as temperature distribution, maximum temperature, and temperature uniformity were compared to assess the thermal performance of each configuration. Evaluation metrics included: (1) temperature uniformity: measured by the standard deviation of temperatures within the battery pack, with a smaller standard deviation indicating more uniform temperature distribution. (2) Maximum temperature control: evaluated whether the maximum temperature of the battery pack remains within a safe range (<40 °C) under high discharge conditions. (3) System energy consumption: Analyzed the relationship between pressure drop and the flow rate of the liquid cooling plate to assess the cooling system’s energy efficiency, ensuring economic viability while meeting thermal requirements.
5.4.2. Sensitivity Analysis of the Coolant Flow Rate
For configuration two, the impact of different coolant flow rates (0.10, 0.15, 0.2, 0.25, 0.3, and 0.35 m/s) on the cooling performance was studied. By analyzing temperature variation curves and pressure drop data, the optimal flow rate range was determined. Results indicated significant cooling improvement as the flow rate increased from 0.10 to 0.25 m/s, while further increases led to substantial pressure drops and higher energy consumption.
5.4.3. Mesh Quality and Convergence Check
Poly-Hexcore meshing technology was utilized in numerical simulations to ensure that mesh quality met orthogonal quality standards. Convergence checks were performed to guarantee the stability and accuracy of the computational results. Mesh quality checks showed that the orthogonal quality of surface meshes was below 0.75 and that of volume meshes was below 0.15, indicating good overall mesh quality. Convergence tests confirmed that all simulation results converged within 1000 iterations, ensuring their reliability.
6. Statistical Analysis Methods
To evaluate the statistical significance of temperature differences among different cooling strategies (Scheme One and Scheme Two), battery cells, and time points, the following statistical methods and results were applied.
6.1. Methodology Overview
A one-way analysis of variance (ANOVA) and post hoc multiple comparison (Tukey HSD) tests were employed. ANOVA determined significant differences in mean temperatures across groups, while Tukey HSD identified specific group differences. For temperature changes in the same cell over time, the Repeated Measures ANOVA evaluated the impact of time. A significance level of α = 0.05 was set; p-values below 0.05 indicated significant differences.
6.2. Statistical Results
6.2.1. Cooling Scheme Analysis
ANOVA indicated that Strategy Two had significantly lower mean temperatures than Strategy One at discharge rates of 1, 1.5, and 2 C (p < 0.05), highlighting its thermal efficiency. Tukey HSD further revealed significant temperature differences at all discharge rates, particularly at 2 C. For example, at 2 C, Strategy Two’s maximum temperature was 27.27 °C versus 47.62 °C for Strategy One, with p < 0.001.
6.2.2. Discharge Rate Analysis
Significant temperature differences were observed with varying discharge rates (1 C, 1.5 C, 2 C) for both cooling strategies (p < 0.05). Higher discharge rates resulted in increased temperatures. Tukey HSD showed the largest temperature difference between 1 and 2 C, emphasizing the impact of high discharge rates. In Strategy Two, the maximum temperature at 1 C was 21.81 °C, compared to 27.27 °C at 2 C (p < 0.01).
6.2.3. Time Point Analysis
Significant temperature changes were noted over different time points (p < 0.05), indicating temperature rise over time, especially at high discharge rates. Tukey HSD identified significant differences between early (0–1000 s) and late discharge phases (2000–3000 s), with more pronounced increases in Strategy One. For instance, at 2 C in Strategy One, temperatures rose from 20.66 °C at 0–1000 s to 47.62 °C at 2000–3000 s (p < 0.001).
7. Conclusion
Building upon the comprehensive analysis and discussion presented in the preceding sections, this study culminates in the following conclusions
-
(1)
The parallel serpentine channel liquid cooling plate arranged on the large surface of the battery (Scheme Two) demonstrated significantly better thermal uniformity and cooling efficiency compared to its arrangement on the end surface of the battery (Scheme One). At a 2 C discharge rate, Scheme Two reduced the maximum battery temperature by 20.35 °C (from 47.62 to 27.27 °C), validating its effectiveness in mitigating thermal gradients (<5 °C) and maintaining safe operating temperatures (<40 °C).
-
(2)
Increasing the coolant flow rate from 0.10 to 0.25 m/s enhanced cooling efficiency by lowering peak temperatures by 0.93 °C. However, further increases (e.g., to 0.35 m/s) yielded diminishing returns due to elevated pressure drops (Figure ), emphasizing the need for balanced flow rate selection to optimize energy consumption and thermal performance.
-
(3)
The coupled ANSYS Fluent and AMESim simulations consistently confirmed the experimental trends, with statistical significance (p < 0.05, Section ) in temperature differences between schemes and discharge rates. This underscores the reliability of the parallel serpentine design for high-power applications.
-
(4)
The study bridges theoretical innovation with practical application, offering a scalable solution for electric vehicles and energy storage systems. The design’s reduced flow resistance and dead zones address key limitations of conventional liquid cooling systems, aligning with global carbon reduction goals through improved battery lifespan and safety.
Acknowledgments
This research was funded by Wuhu “ChiZhu Light” Major Science and Technology Project (2022zd04) and the Yangtze River Delta Science and Technology Innovation Community Joint Research Project (2023CSJGG1600).
The data supporting the findings of this study are available from the corresponding author, Prof. Peicheng Shi, upon reasonable request. These data are made available to foster transparency, reproducibility, and further research in the field of computational materials science.
Hailong Zhu: Writingoriginal draft, Software, Data curation, Conceptualization, Methodology, Formal Analysis, and Validation. Peicheng Shi: Writingreview and editing, Project administration, Funding acquisition, Resources, and Supervision. Xinlong Dong: Writingreview and editing, Supervision, and Resources. Bin Hai: Visualization, Formal analysis, and Project administration.
The authors declare no competing financial interest.
References
- Lin C., Gao F., Wang W., Chen X.. Multi-Objective Optimization Design for a Battery Pack of Electric Vehicle with Surrogate Models. J. Vibroeng. 2016;18(4):2343–2358. doi: 10.21595/jve.2016.16837. [DOI] [Google Scholar]
- Hua Y., Zhou S., Cui H., Liu X., Zhang C., Xu X., Ling H., Yang S.. A Comprehensive Review on Inconsistency and Equalization Technology of Lithium-Ion Battery for Electric Vehicles. Int. J. Energy Res. 2020;44(14):11059–11087. doi: 10.1002/er.5683. [DOI] [Google Scholar]
- Börner M., Friesen A., Grützke M., Stenzel Y. P., Brunklaus G., Haetge J., Nowak S., Schappacher F. M., Winter M.. Correlation of Aging and Thermal Stability of Commercial 18650-Type Lithium Ion Batteries. J. Power Sources. 2017;342:382–392. doi: 10.1016/j.jpowsour.2016.12.041. [DOI] [Google Scholar]
- Wang K., Shi P., Zhang Z.. Finite Element Modeling of Electric Vehicle Power Battery Pack and Its Influence Analysis and Test Research at Body-in-White Stage. J. Vibroeng. 2023;25(7):1353–1368. doi: 10.21595/jve.2023.23260. [DOI] [Google Scholar]
- Ebbs-Picken T., Da Silva C. M., Amon C. H.. Hierarchical Thermal Modeling and Surrogate-Model-Based Design Optimization Framework for Cold Plates Used in Battery Thermal Management Systems. Appl. Therm. Eng. 2024;253:123599. doi: 10.1016/j.applthermaleng.2024.123599. [DOI] [Google Scholar]
- Bakar O., Uysal M., Feyzioğlu A.. Optimization and Experimental Validation of the Air Intake Holes of the Lithium-Ion Battery Pack. J. Eng. Therm. Sci. 2024;4(1):1–19. doi: 10.21595/jets.2023.23583. [DOI] [Google Scholar]
- Chen K., Huang Q., Li Q.-Y., Liang S., Wu X.. Optimization Strategy for Battery Thermal Management System with Phase Change Materials, Aerogel and Cold Plates. Int. J. Heat Mass Transfer. 2024;221:125070. doi: 10.1016/j.ijheatmasstransfer.2023.125070. [DOI] [Google Scholar]
- Chen P., Deng J., Guo Z., Li X., Yang W., Wu Y., Mao Y., Jia W., Liu J., Li C.. Advancing Thermal Safety System for Battery Pack: Introducing Intrinsic Flame-Retardant Solid-Solid Phase Change Materials with Melamine Crosslink. Adv. Funct. Mater. 2025:2423361. doi: 10.1002/adfm.202423361. [DOI] [Google Scholar]
- Liu Z., Xiong C., Du X.. Research on the Optimization Control Strategy of a Battery Thermal Management System Based on Serpentine Liquid Cooling Combined with Phase Change Material. J. Power Sources. 2025;630:236127. doi: 10.1016/j.jpowsour.2024.236127. [DOI] [Google Scholar]
- Chen H., Wei G., Xu L., Du X.. Performance Study on a Novel Hybrid Thermal Management System for Cylindrical Lithium-Ion Battery Pack Based on Liquid Cooling and PCM. Appl. Therm. Eng. 2025;271:126392. doi: 10.1016/j.applthermaleng.2025.126392. [DOI] [Google Scholar]
- Lou Z., Wang K., Yao H., Zhao W., Qin H., Wu Z., Wei G.. A Novel Dynamic Filling Material for Plugging Fractures around Underground Gas Extraction Boreholes: Experimental and Engineering Performances. Energy. 2025;314:134202. doi: 10.1016/j.energy.2024.134202. [DOI] [Google Scholar]
- Lou Z., Wang K., Kang M., Zhao W., Wei G., Yue J., Yao H.. Plugging Methods for Underground Gas Extraction Boreholes in Coal Seams: A Review of Processes, Challenges and Strategies. Gas Sci. Eng. 2024;122:205225. doi: 10.1016/j.jgsce.2024.205225. [DOI] [Google Scholar]
- Siruvuri S. D. V. S. S. V., Budarapu P. R.. Studies on Thermal Management of Lithium-Ion Battery Pack Using Water as the Cooling Fluid. J. Energy Storage. 2020;29:101377. doi: 10.1016/j.est.2020.101377. [DOI] [Google Scholar]
- Shang Z., Qi H., Liu X., Ouyang C., Wang Y.. Structural Optimization of Lithium-Ion Battery for Improving Thermal Performance Based on a Liquid Cooling System. Int. J. Heat Mass Transfer. 2019;130:33–41. doi: 10.1016/j.ijheatmasstransfer.2018.10.074. [DOI] [Google Scholar]
- Zeng Y., Deng Q., Zhao G., Li X., Shao D., Yang W., Chen P., Ai Y., Wu T., Rao Z., Liu J.. High Thermal Conductivity Zn2+ Metal–Organic Framework Based Composite Phase Change Materials for Battery Thermal Management. Appl. Therm. Eng. 2025;273:126447. doi: 10.1016/j.applthermaleng.2025.126447. [DOI] [Google Scholar]
- Li X., Yang W., Li C., Deng J., Huang Q., Jia W., Mao Y., Zou Y., Wu Y., Tian J., Zhang G., Tang X., Shao D., Zhang Y., Zhu S., Li X.. Flexible Solid-Solid Phase Change Material with Zero Leakage via in-Situ Preparation for Battery Thermal Management. Innovation Energy. 2024;1(3):100034. doi: 10.59717/j.xinn-energy.2024.100034. [DOI] [Google Scholar]
- Ren H., Yin L., Dang C., Liu R., Jia L., Ding Y.. Phase-Change Cooling of Lithium-Ion Battery Using Parallel Mini-Channels Cold Plate with Varying Flow Rate. Case Stud. Therm. Eng. 2023;45:102960. doi: 10.1016/j.csite.2023.102960. [DOI] [Google Scholar]
- Li X., Yang W., Yin L., Zhang S., Wu Y., Mao Y., Jia W., Wu D., Chen K., Yuan L., Zhou X., Li C.. Advancing Lithium Battery Safety: Introducing a Composite Phase Change Material with Anti-Leakage and Fire-Resistant Properties. eTransportation. 2025;23:100387. doi: 10.1016/j.etran.2024.100387. [DOI] [Google Scholar]
- Zhao C., Zhang B., Zheng Y., Huang S., Yan T., Liu X.. Hybrid Battery Thermal Management System in Electrical Vehicles: A Review. Energies. 2020;13(23):6257. doi: 10.3390/en13236257. [DOI] [Google Scholar]
- Tarish A. L., Khalifa A. H. N., Hamad A. J.. Performance Evaluation of Adsorption Thermophysical Battery for Air Conditioning Applications. Therm. Sci. Eng. Prog. 2022;28:101060. doi: 10.1016/j.tsep.2021.101060. [DOI] [Google Scholar]
- Yao M., Gan Y., Liang J., Dong D., Ma L., Liu J., Luo Q., Li Y.. Performance Simulation of a Heat Pipe and Refrigerant-Based Lithium-Ion Battery Thermal Management System Coupled with Electric Vehicle Air-Conditioning. Appl. Therm. Eng. 2021;191:116878. doi: 10.1016/j.applthermaleng.2021.116878. [DOI] [Google Scholar]
- Babu Sanker S., Baby R.. Phase Change Material Based Thermal Management of Lithium Ion Batteries: A Review on Thermal Performance of Various Thermal Conductivity Enhancers. J. Energy Storage. 2022;50:104606. doi: 10.1016/j.est.2022.104606. [DOI] [Google Scholar]
- Jiang L., Zhang H., Li J., Xia P.. Thermal Performance of a Cylindrical Battery Module Impregnated with PCM Composite Based on Thermoelectric Cooling. Energy. 2019;188:116048. doi: 10.1016/j.energy.2019.116048. [DOI] [Google Scholar]
- Qaderi A., Veysi F.. Modelling and Optimisation of a Battery Thermal Management System with Nano Encapsulated Phase Change Material Slurry for 18650 Li-Ion Batteries. Therm. Sci. Eng. Prog. 2023;37:101552. doi: 10.1016/j.tsep.2022.101552. [DOI] [Google Scholar]
- Amrut S. R., Sachin B. M., Babu Rao P., Seetharamu K. N.. Steady-State Thermal Investigations on Cold Plate Using FEM. Therm. Sci. Eng. Prog. 2021;23:100905. doi: 10.1016/j.tsep.2021.100905. [DOI] [Google Scholar]
- He L., Tang X., Luo Q., Liao Y., Luo X., Liu J., Ma L., Dong D., Gan Y., Li Y.. Structure Optimization of a Heat Pipe-Cooling Battery Thermal Management System Based on Fuzzy Grey Relational Analysis. Int. J. Heat Mass Transfer. 2022;182:121924. doi: 10.1016/j.ijheatmasstransfer.2021.121924. [DOI] [Google Scholar]
- Alihosseini A., Shafaee M.. Experimental Study and Numerical Simulation of a Lithium-Ion Battery Thermal Management System Using a Heat Pipe. J. Energy Storage. 2021;39:102616. doi: 10.1016/j.est.2021.102616. [DOI] [Google Scholar]
- Liang J., Gan Y., Li Y., Tan M., Wang J.. Thermal and Electrochemical Performance of a Serially Connected Battery Module Using a Heat Pipe-Based Thermal Management System under Different Coolant Temperatures. Energy. 2019;189:116233. doi: 10.1016/j.energy.2019.116233. [DOI] [Google Scholar]
- Kothari R., Sahu S. K., Kundalwal S. I., Sahoo S. P.. Experimental Investigation of the Effect of Inclination Angle on the Performance of Phase Change Material Based Finned Heat Sink. J. Energy Storage. 2021;37:102462. doi: 10.1016/j.est.2021.102462. [DOI] [Google Scholar]
- Zhuang Y., Chen T., Chen J., Li J., Guan M., Chen Y.. Thermal Uniformity Performance of a Hybrid Battery Thermal Management System Using Phase Change Material and Cooling Plates Arrayed in the Manner of Honeycomb. Therm. Sci. Eng. Prog. 2021;26:101094. doi: 10.1016/j.tsep.2021.101094. [DOI] [Google Scholar]
- Yang H., Li Y., Yang Y., Chen D., Zhu Y.. Effective Thermal Conductivity of High Porosity Open-Cell Metal Foams. Int. J. Heat Mass Transfer. 2020;147:118974. doi: 10.1016/j.ijheatmasstransfer.2019.118974. [DOI] [Google Scholar]
- Qaiser R., Khan M. M., Khan L. A., Irfan M.. Melting Performance Enhancement of PCM Based Thermal Energy Storage System Using Multiple Tubes and Modified Shell Designs. J. Energy Storage. 2021;33:102161. doi: 10.1016/j.est.2020.102161. [DOI] [Google Scholar]
- Liu Y., Zhang J.. Self-Adapting J-Type Air-Based Battery Thermal Management System via Model Predictive Control. Appl. Energy. 2020;263:114640. doi: 10.1016/j.apenergy.2020.114640. [DOI] [Google Scholar]
- Akbarzadeh M., Kalogiannis T., Jin L., Karimi D., Van Mierlo J., Berecibar M.. Experimental and Numerical Thermal Analysis of a Lithium-Ion Battery Module Based on a Novel Liquid Cooling Plate Embedded with Phase Change Material. J. Energy Storage. 2022;50:104673. doi: 10.1016/j.est.2022.104673. [DOI] [Google Scholar]
- Li Y., Bai M., Zhou Z., Lv J., Hu C., Gao L., Peng C., Li Y., Li Y., Song Y.. Experimental Study of Liquid Immersion Cooling for Different Cylindrical Lithium-Ion Batteries under Rapid Charging Conditions. Therm. Sci. Eng. Prog. 2023;37:101569. doi: 10.1016/j.tsep.2022.101569. [DOI] [Google Scholar]
- Wu X., Du J., Guo H., Qi M., Hu F., Shchurov N. I.. Boundary Conditions for Onboard Thermal-Management System of a Battery Pack under Ultrafast Charging. Energy. 2022;243:123075. doi: 10.1016/j.energy.2021.123075. [DOI] [Google Scholar]
- Guo J., Jiang F.. A Novel Electric Vehicle Thermal Management System Based on Cooling and Heating of Batteries by Refrigerant. Energy Convers. Manage. 2021;237:114145. doi: 10.1016/j.enconman.2021.114145. [DOI] [Google Scholar]
- Shen M., Gao Q.. Structure Design and Effect Analysis on Refrigerant Cooling Enhancement of Battery Thermal Management System for Electric Vehicles. J. Energy Storage. 2020;32:101940. doi: 10.1016/j.est.2020.101940. [DOI] [Google Scholar]
- Hong S. H., Jang D. S., Park S., Yun S., Kim Y.. Thermal Performance of Direct Two-Phase Refrigerant Cooling for Lithium-Ion Batteries in Electric Vehicles. Appl. Therm. Eng. 2020;173:115213. doi: 10.1016/j.applthermaleng.2020.115213. [DOI] [Google Scholar]
- Wang Z. R., Huang L. P., He F.. Design and Analysis of Electric Vehicle Thermal Management System Based on Refrigerant-Direct Cooling and Heating Batteries. J. Energy Storage. 2022;51:104318. doi: 10.1016/j.est.2022.104318. [DOI] [Google Scholar]
- Song X., Sun N., Cao H., Zhu G., Li M., Liu X., Rao Z.. Research on a Power Battery Thermal Management System Using Direct Refrigerant Cooling with Parallel Serpentine Flow Paths. Energy Storage Sci Technol. 2024;13(8):2726–2736. doi: 10.19799/j.cnki.2095-4239.2024.0268. [DOI] [Google Scholar]
- Monika K., Chakraborty C., Roy S., Dinda S., Singh S. A., Datta S. P.. An Improved Mini-Channel Based Liquid Cooling Strategy of Prismatic LiFePO4 Batteries for Electric or Hybrid Vehicles. J. Energy Storage. 2021;35:102301. doi: 10.1016/j.est.2021.102301. [DOI] [Google Scholar]
- Guo Z., Zeng F., Jiang Z.. Research of Thermal Behaviour of Li-Ion Battery Module Based on Liquid Cooling. J. Phys.: Conf. Ser. 2022;2237(1):012025. doi: 10.1088/1742-6596/2237/1/012025. [DOI] [Google Scholar]
- Yang H., Wang Z., Li M., Ren F., Feng Y.. A Manifold Channel Liquid Cooling System with Low-Cost and High Temperature Uniformity for Lithium-Ion Battery Pack Thermal Management. Therm. Sci. Eng. Prog. 2023;41:101857. doi: 10.1016/j.tsep.2023.101857. [DOI] [Google Scholar]
- Liu F., Yu B., Qin W., Cheng X., Zeng J.. Heat Dissipation Analysis of Lithium-ion Battery Based on Series-parallel Symmetrical Liquid Cooling Channel. J. Hunan Univ. Nat. Sci. 2024;51(2):198–207. doi: 10.16339/j.cnki.hdxbzkb.2024158. [DOI] [Google Scholar]
- Luo T., Zhang Y., Chen X., Jia T., Yu H., Mao B., Ma C.. A Hybrid Battery Thermal Management System Composed of MHPA/PCM/Liquid with a Highly Efficient Cooling Strategy. Appl. Therm. Eng. 2024;251:123617. doi: 10.1016/j.applthermaleng.2024.123617. [DOI] [Google Scholar]
- Lu D., Cui N., Zhou J., Li C.. Hybrid Cooling System with Phase Change Material and Liquid Microchannels to Prevent Thermal Runaway Propagation within Lithium-Ion Battery Packs. Appl. Therm. Eng. 2024;247:123118. doi: 10.1016/j.applthermaleng.2024.123118. [DOI] [Google Scholar]
- Li T., Li Y., Pan C.. Analysis of temperature and heat generation characteristics in lithium-ion battery constant current charging. Chin. J. Power Sources. 2021;45(7):872–876. [Google Scholar]
- Pan H., Li Y., Zhang M., Liang G., Chen L.. Multiple Factors Dynamic Heat Generation Rate Model of Lithium-ion Battery. Automot. Eng. 2021;43(2):204–209. doi: 10.19562/j.chinasae.qcgc.2021.02.007. [DOI] [Google Scholar]
- Zhang Y., Zuo W., E J., Li J., Li Q., Sun K., Zhou K., Zhang G.. Performance Comparison between Straight Channel Cold Plate and Inclined Channel Cold Plate for Thermal Management of a Prismatic LiFePO4 Battery. Energy. 2022;248:123637. doi: 10.1016/j.energy.2022.123637. [DOI] [Google Scholar]
- Yun S., Kwon J., Cho W., Lee D., Kim Y.. Performance Improvement of Hot Stamping Die for Patchwork Blank Using Mixed Cooling Channel Designs with Straight and Conformal Channels. Appl. Therm. Eng. 2020;165:114562. doi: 10.1016/j.applthermaleng.2019.114562. [DOI] [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Data Availability Statement
The data supporting the findings of this study are available from the corresponding author, Prof. Peicheng Shi, upon reasonable request. These data are made available to foster transparency, reproducibility, and further research in the field of computational materials science.