Skip to main content
Scientific Reports logoLink to Scientific Reports
. 2026 Mar 27;16:10529. doi: 10.1038/s41598-026-43242-z

Comparative optimization of overcurrent relay coordination in DG-integrated distribution networks: water cycle algorithm versus genetic algorithm and big bang–big crunch

Reda E Mohamed 1, Saber M Saleh 1,, Ahmad G Ahmad 1
PMCID: PMC13035988  PMID: 41896260

Abstract

The increasing penetration of distributed generation (DG) has significantly complicated protection coordination in modern distribution networks by introducing bidirectional power flows and variable fault current levels. These challenges become more pronounced under different operating modes, particularly in islanded operation, where reduced fault current levels place severe constraints on overcurrent relay (OCR) coordination. This paper presents a comparative assessment of metaheuristic optimization techniques for coordinating overcurrent protection in DG-integrated distribution networks. Two distribution systems with different topological characteristics are examined. A radial 9-bus system is analyzed under three operating modes: conventional grid-connected operation without DG, DG-integrated grid-connected operation, and islanded operation. In contrast, a meshed 30-bus distribution system is evaluated exclusively under islanded operation to represent the most demanding coordination conditions, where fault current support is limited to inverter-based DG sources. Relay coordination is formulated as a constrained optimization problem aimed at minimizing total relay operating time while satisfying coordination time interval (CTI) requirements. Three metaheuristic optimization algorithms are applied under identical protection models and fault conditions: the Genetic Algorithm (GA) as a conventional reference approach, and the Water Cycle Algorithm (WCA) and Big Bang–Big Crunch (BB-BC) algorithm as more recent techniques. Short-circuit calculations are performed for three-phase faults in accordance with IEC 60909 standards. The results indicate that all investigated algorithms successfully achieve coordinated relay settings under the examined operating modes.

Keywords: Distributed generation, Overcurrent relay coordination, Dual-setting overcurrent relays, Metaheuristic optimization, Water cycle algorithm, Genetic algorithm, Big bang–big crunch

Subject terms: Energy science and technology, Engineering, Mathematics and computing

Introduction

Modern distribution networks are undergoing a fundamental transformation driven by the increasing penetration of DG, particularly inverter-based renewable energy resources. While this transition offers well-recognized environmental and economic benefits, it has introduced substantial challenges to conventional protection schemes that were originally designed for passive, radially operated systems1,2.

Conventional OCR coordination in distribution networks relies on the assumption of unidirectional power flow, where fault currents originate from the main grid and propagate downstream toward load buses. Under this assumption, selective coordination between primary and backup relays can be achieved by appropriately grading relay operating times based on fault current magnitudes and predefined CTIs3,4. However, the integration of DG invalidates this assumption by introducing additional fault current sources within the network, leading to bidirectional fault current flows, altered short-circuit levels, and increased sensitivity of protection settings to network operating modes5,6.

In DG-integrated distribution systems, both the magnitude and direction of fault currents depend strongly on the number, type, and location of active generators, as well as on the operating mode of the network. These variations can result in several well-documented protection issues, including protection blinding, false tripping, sympathetic tripping, and loss of selectivity, which collectively degrade system reliability and may lead to unnecessary service interruptions. The problem becomes more pronounced in networks with high DG penetration and in configurations where meshed or looped structures are employed710.

Directional and Dual Setting Over Current Relays have been widely adopted to mitigate some of these challenges. By allowing separate settings for forward and reverse fault directions, such relays enhance selectivity in networks experiencing bidirectional fault currents. Nevertheless, the use of directional and dual-setting relays significantly increases the complexity of the coordination problem. The number of coordination constraints grows substantially, and relay performance becomes highly sensitive to network topology, fault location, and operating mode. As a result, conventional trial-and-error coordination approaches become impractical, particularly in systems with high DG penetration and multiple operating modes11,12.

Early research addressing these challenges primarily focused on analyzing the impact of DG on fault current characteristics and documenting coordination failures under different operating modes13,14. While these studies provided valuable insight into the nature of the problem, they largely relied on offline analyses and manual relay setting adjustments, which are impractical in modern distribution networks where DG output and system topology may change frequently. To overcome these limitations, adaptive protection schemes based on communication-assisted relays were subsequently proposed, enabling relay settings to be updated in real time according to operating modes15,16. However, such schemes typically require extensive communication infrastructure and introduce additional concerns related to latency, reliability, and cybersecurity17,18.

As an alternative, optimization-based relay coordination approaches employing metaheuristic algorithms have gained considerable attention. These methods are well suited to relay coordination problems due to their ability to handle nonlinear objective functions and discrete relay settings without requiring gradient information1921. GA were among the earliest metaheuristics applied in this context and demonstrated satisfactory performance in minimizing relay operating times in relatively simple radial networks22,23. Nevertheless, in systems with high DG penetration, where coordination constraints increase significantly, GA has been reported to suffer from premature convergence and difficulty in satisfying all coordination requirements24,25. This limitation motivated the development of hybrid techniques, such as GA–NLP and GA–IPM, which combine global search capabilities with deterministic refinement methods to improve solution quality, albeit at the expense of increased computational complexity29,30.

Particle Swarm Optimization (PSO) has also been explored as an alternative, offering faster convergence characteristics in some studies. Several PSO variants and hybrid PSO-based approaches have been evaluated on IEEE benchmark systems, often demonstrating improved computational efficiency compared to standard GA implementations26,27. However, PSO performance has been reported to be sensitive to parameter selection, with reduced robustness observed under islanded operating modes characterized by lower fault current levels.

More recent research has investigated newer nature-inspired algorithms for microgrid and DG-dominated protection applications. The WCA, originally introduced by Eskandar et al.28, has shown promising performance for relay coordination in microgrids experiencing frequent operating mode transitions29,30. Similarly, the BB-BC algorithm has been applied to relay coordination problems with encouraging results31. Nevertheless, comprehensive comparative evaluations between these recent algorithms under identical protection models and operating conditions remain limited.

In parallel with advances in optimization methods, developments in relay technology have contributed to enhanced protection flexibility. DOCRs allow independent forward and reverse settings, which is particularly advantageous in meshed DG-integrated networks where fault current direction depends on the operating status of DGs32,33. Enhanced relay characteristics, such as time–current–voltage (TCV) tripping schemes, have also been proposed to improve coordination performance under varying fault impedances and DG contributions34. Furthermore, the increasing penetration of inverter-based renewable energy sources introduces additional complexity due to their inherent current-limiting behavior during fault conditions, particularly under islanded operation3537.

Among the various operating modes of DG-integrated distribution systems, islanded operation represents the most demanding mode from a protection coordination perspective. In this mode, the main grid is disconnected and fault current contributions are limited to inverter-based DG units, resulting in substantially reduced fault current levels and narrower coordination margins. Under such conditions, maintaining reliable primary–backup discrimination using conventional coordination practices becomes increasingly challenging3841. Despite its practical importance, systematic comparisons of metaheuristic optimization algorithms under identical protection models and stressed islanded operating modes remain limited, particularly for systems employing directional and dual-setting relays.

Accordingly, this study focuses on the systematic investigation of OCR coordination in DG-integrated distribution networks under different operating modes, with particular emphasis on islanded operation. By considering both radial and meshed network topologies and applying identical protection models and fault scenarios, this work aims to provide a consistent comparative assessment of the performance and robustness of selected metaheuristic optimization techniques.

System description and research methodology

This study adopts a systematic framework for OCR coordination in distribution networks with DG, combining detailed network modelling, short-circuit analysis, and optimization-based relay setting determination. The overall methodology is designed to ensure a fair and consistent comparison between the investigated optimization algorithms under identical protection models and operating modes.

Overview of research framework

The coordination process is implemented through an integrated simulation environment in which network modelling and fault analysis are performed using ETAP software, while the optimization algorithms are executed in MATLAB. ETAP is employed to model the distribution systems, calculate load flow conditions, and perform short-circuit studies in accordance with IEC 60,909 standards. MATLAB is used to formulate and solve the relay coordination optimization problem using the selected metaheuristic algorithms. The primary objective of the adopted framework is to determine optimal relay settings that minimize the total operating time of primary relays while ensuring proper coordination with their associated backup relays. To achieve this objective, identical fault scenarios, relay characteristics, and coordination constraints are applied to all investigated algorithms, allowing their performance to be compared on a consistent basis.

Test system configurations

Two distribution systems with different topological characteristics are considered in this study in order to evaluate the performance of the optimization algorithms under both relatively simple and highly constrained coordination environments.

9-Bus radial system

Figure 1 illustrates a DG-connected Canadian urban radial 9-bus distribution network modelled in ETAP and operating at a nominal voltage of 12.49 kV42,43. The system includes four DG units of different technologies: a 3 MVA synchronous generator at bus 4, two photovoltaic units each rated at 3 MVA at buses 5 and 9, and a 2.471 MVA wind turbine generator at bus 6, resulting in varying fault current contributions under different operating modes. The protection scheme consists of 21 OCRs arranged to provide coordinated primary and backup protection throughout the network. Relay settings, including CTR, pickup currents I​p, and plug settings (PS), are determined based on load flow analysis and are summarized in Table 1.Coordination performance is evaluated under three operating modes: conventional grid-connected operation without DG, grid-connected operation with full DG integration, and islanded operation. Three-phase faults are applied at eight strategic locations (F1–F8) along the feeders to assess selectivity.

Fig. 1.

Fig. 1

Single-line diagram of the 9-bus radial distribution system with DG.

Table 1.

Pickup current values of OCR in the 9-bus system.

Relay ID CTR PS I_pickup (A)
OCR1 400 0.5 200
OCR2 400 0.625 250
OCR3 400 1.0 400
OCR4 400 1.25 500
OCR5 400 0.5 200
OCR6 400 0.625 250
OCR7 400 0.5 200
OCR8 400 1.25 500
OCR9 400 0.25 100
OCR10 400 0.25 100
OCR11 400 0.25 100
OCR12 400 0.25 100
OCR13 400 0.25 100
OCR14 400 0.25 100
OCR15 400 0.25 100
OCR16 400 0.25 100
OCR17 1000 1.0 1000
OCR18 400 0.5 200
OCR19 400 0.5 200
OCR20 400 0.5 200
OCR21 400 0.5 200

30-Bus mesh system

Figure 2 illustrates the second test system, which is a meshed 30-bus distribution network modelled in ETAP and reported in44,45. The system is analyzed exclusively under islanded operation, where it is completely decoupled from the upstream utility grid, and both the total load demand and fault current contributions are supplied solely by the integrated DG units. The network incorporates four inverter-based DG units, which represent the only sources feeding the system under islanded conditions. These DG units collectively supply the network and determine the available fault current levels, resulting in a highly constrained coordination environment due to their current-limiting behavior. The protection scheme consists of 29 DOCRs arranged to provide coordinated primary and backup protection throughout the meshed network. Relay settings, including CTR, pickup currents Ip, are summarized in Table 2. Despite differences in CT ratios, a uniform pickup current of 300 A is adopted for all DOCRs, providing a consistent basis for the coordination process. Coordination performance is evaluated by applying three-phase faults at fifteen strategic locations (F1–F15) distributed across the network to assess selectivity under this severe operating mode.

Fig. 2.

Fig. 2

Single-line diagram of the 30-bus mesh distribution system with DOCRs.

Table 2.

Pickup current and CT ratio data for DOCRs in the 30-bus system.

(DOCR) CTR IP
DOCR1 300/1 300
DOCR2 800/1 300
DOCR3 300/1 300
DOCR4 300/1 300
DOCR5 300/1 300
DOCR6-DOCR29 300/1 300

Formulation of the relay coordination optimization problem

The relay coordination problem is formulated as a constrained nonlinear optimization problem25,46. The objective is to minimize the total operating time of primary relays under all considered fault scenarios while maintaining proper coordination between primary and backup relays.

Objective function

The objective function (OF) is defined as the minimization of the sum of primary relay operating times for all fault locations:

graphic file with name d33e674.gif 1

Relay operating time

The operating time of each relay is calculated using the IEC standard inverse time–current characteristic, expressed as:

graphic file with name d33e682.gif 2

where TMSᵢ = Time Multiplier Setting for relay I; Iᶠᵢⱼ = Fault current seen by relay i for fault j; Ipᵢ = Pickup current setting for relay I; α, β = IEC curve characteristic constants.

Coordination constraints

To ensure selective operation between primary and backup relays, a minimum CTI is imposed such that:

graphic file with name d33e691.gif 3

where the CTI is set to 0.3 s44. In addition, practical limits are applied to the relay settings:

graphic file with name d33e700.gif 4
graphic file with name d33e704.gif 5

Dual-setting relay formulation

For systems employing directional and DOCRs, separate settings are defined for forward and reverse fault directions47. The corresponding operating times are given by:

graphic file with name d33e716.gif 6
graphic file with name d33e720.gif 7

The objective function is accordingly extended to include both forward and reverse relay operating times:

graphic file with name d33e726.gif 8

The coordination constraint for dual-setting relays is expressed as:

graphic file with name d33e732.gif 9

This formulation increases the dimensionality of the optimization problem, particularly in meshed networks, and highlights the need for robust optimization techniques capable of handling large constrained search spaces.

Applied optimization algorithms

Three metaheuristic optimization algorithms are employed to solve the formulated coordination problem. The GA is adopted as a reference method due to its widespread application in relay coordination studies, while the WCA and the BB–BC algorithm are investigated as alternative approaches. All algorithms are implemented using identical objective functions, constraints, population sizes, and termination criteria to ensure a fair comparison. Short-circuit currents required for the optimisation process are obtained from ETAP simulations and imported into MATLAB, ensuring consistency between network modelling and optimization stages.

The overall optimization procedure adopted in this study is illustrated in the flowchart shown in Fig. 3. Although the flowchart is presented in the context of the 9-bus system for clarity, the same optimization framework is identically applied to the 30-bus meshed system, with differences only in network data, number of relays, and coordination constraints.

Fig. 3.

Fig. 3

Flowchart of the relay coordination procedure for the 9-bus radial system.

Results and discussion

9-Bus radial system results

The coordination performance of the proposed optimization approaches is first evaluated on the radial 9-bus distribution system under three operating modes.

Mode 1: Conventional grid-connected operation

Table 3 presents the relay coordination results obtained for the 9-bus system under conventional operation without DG. The primary and backup relay operating times together with the corresponding CTIs confirm that proper discrimination is maintained across all considered fault locations.

Table 3.

GA-based relay coordination results for the radial 9-bus system under (Conventional—without DG).

Fault Primary Backup T_primary (s) T_backup (s) CTI (s)
F1 OCR1 OCR2 0.0991 0.3981 0.2991
F2 OCR2 OCR3 0.3895 0.6887 0.2992
F3 OCR3 OCR4 0.6707 0.9698 0.2991
F4 OCR4 OCR17 0.9422 1.3837 0.4414
F5 OCR5 OCR6 0.0990 0.3981 0.2991
F6 OCR6 OCR7 0.3895 0.6707 0.2812
F7 OCR7 OCR8 0.7285 1.0275 0.2990
F8 OCR8 OCR17 1.0843 1.3837 0.2994
Total operating time 11.3465

The CTI values are generally clustered around the required threshold of 0.3 s, with minor deviations observed in isolated cases. Despite these variations, overall selectivity is preserved and no miscoordination occurs. The total primary operating time obtained using GA is 11.35 s, reflecting fast and effective protection performance under radial modes. In addition to GA, both WCA and BB–BC achieved feasible relay coordination under this operating mode. The total operating times obtained by WCA (11.39 s) and BB–BC (12.09 s) are close to that of GA, confirming consistent performance under conventional radial network modes.

Mode 2: Grid-connected operation with full DG integration

The integration of all DG units significantly alters the short-circuit current distribution within the 9-bus radial system. Unlike the conventional operating mode, fault currents in Mode 2 are influenced by multiple injection points, resulting in bidirectional contributions and expanded protection participation. Consequently, additional relay pairs become involved in fault detection and coordination compared with Mode 1. Table 4 presents the primary and backup relay assignments together with the corresponding fault current magnitudes for all fault locations (F1–F8). The results confirm that DG integration changes the fault current distribution and increases the number of relays involved in fault detection, which directly increases the coordination burden. The wide spread between primary and backup fault current levels is further illustrated in Fig. 4.

Table 4.

Primary and backup relay assignments with corresponding fault current magnitudes for each fault location in Mode 2 (Full DG integration).

Fault Primary relay I_primary (A) Backup relay I_backup (A)
F1 OCR1 6930 OCR2 6251
OCR1 6930 OCR19 728
OCR9 375 OCR18 375
F2 OCR2 6844 OCR3 6844
OCR10 981 OCR9 375
F3 OCR3 7463 OCR4 7463
OCR11 975 OCR10 975
F4 OCR4 8056 OCR17 7466
OCR4 8056 OCR16 589
OCR12 975 OCR11 975
F5 OCR5 6918 OCR6 6918
OCR13 375 OCR20 375
F6 OCR6 7681 OCR7 7681
OCR14 375 OCR13 375
F7 OCR7 8448 OCR8 7862
OCR7 8448 OCR21 593
OCR15 375 OCR14 375
F8 OCR8 8338 OCR17 7466
OCR16 375 OCR21 589
OCR8 8338 OCR12 969
Fig. 4.

Fig. 4

Fault current magnitudes observed by primary and backup relays in Mode 2.

The relay operating times and CTIs obtained using GA are summarized in Table 5. All relay pairs satisfy the required coordination constraint in Mode 2. For most fault scenarios, CTI values remain close to the 0.3 s threshold, indicating effective primary–backup discrimination under full DG integration. For example, the OCR8–OCR17 pair in Fault F8 exhibits a CTI of 0.895 s, which is significantly higher than the required 0.3 s threshold, whereas most other relay pairs remain closely clustered around the coordination boundary. Similarly, the OCR16–OCR15 pair records a CTI of 0.324 s, reflecting a slightly larger margin compared with the nominal coordination interval.

Table 5.

Relay operating times and CTIs for the 9-bus system in Mode 2.

Fault Primary Backup Inline graphic (s) Inline graphic (s) CTI (s)
F1 OCR1 OCR2 0.0953 0.3947 0.2995
OCR1 OCR19 0.0953 0.3947 0.2994
OCR9 OCR18 1.0181 1.3190 0.3010
F2 OCR2 OCR3 0.4886 0.7878 0.2992
OCR10 OCR9 1.2654 1.5563 0.2999
F3 OCR3 OCR4 0.9570 1.2610 0.3040
OCR11 OCR10 0.5213 0.8271 0.3058
F4 OCR4 OCR17 1.6560 1.9575 0.3014
OCR4 OCR16 1.6560 1.9580 0.3019
OCR12 OCR11 0.2234 0.5227 0.2993
F5 OCR5 OCR6 0.0953 0.3947 0.2994
OCR13 OCR20 0.8676 1.1670 0.2995
F6 OCR6 OCR7 0.4923 0.7916 0.2994
OCR14 OCR13 0.5623 0.8676 0.3052
F7 OCR7 OCR8 0.7708 1.0718 0.3010
OCR7 OCR21 0.7708 1.0921 0.3213
OCR15 OCR14 0.2624 0.5623 0.3000
F8 OCR8 OCR17 1.0621 1.9575 0.8953
OCR16 OCR21 2.6388 2.9395 0.3007
OCR16 OCR15 2.6388 2.9624 0.3245

A representative ETAP time–current characteristic (TCC) curve for fault scenario F4 is shown in Fig. 5, confirming correct coordination between the primary and backup relays in Mode 2.

Fig. 5.

Fig. 5

ETAP TCC curves illustrating relay coordination for fault scenario F4 in Mode 2.

The total operating time obtained in Mode 2 is 38.06 s for GA, compared with 70.22 s and 73.20 s for WCA and BB–BC, respectively. These results indicate that GA provides the fastest overall relay response under full DG integration, while the distribution of CTI values varies among the investigated optimization techniques.

Mode 3: Islanded operation

Islanded operation represents the most severe coordination condition for the 9-bus system. In this mode, the upstream grid is disconnected and fault currents are supplied solely by DG units. Consequently, fault levels are significantly reduced compared to grid-connected operation, which directly narrows the feasible coordination region and increases the optimization difficulty. Table 6 presents the operating times and CTIs obtained using GA for the islanded mode. for all fault locations (F1–F8). CTI values remain close to the required 0.3 s threshold, confirming that coordination is generally maintained despite the reduced fault currents. However, limited deviations appear under islanded modes. At F8, the OCR16–OCR15 pair records a CTI of 0.1093 s, which is below the coordination requirement and therefore represents a CTI violation. In addition, certain relay pairs exhibit excessively large CTI values (e.g., OCR10–OCR9 at F2 and OC16–OC21 at F8), reflecting delayed backup operation caused by reduced or uneven fault current distribution in the islanded network. Figure 8, 9, 10, 11 and 12 clear Statistical analysis of GA Mode 1,2, and 3 over 30 runs (a) boxplot with outliers, (b) histogram showing skewness, (c) convergence profile of best and mean trends.

Table 6.

Presents the operating times and CTI values for all relay pairs in mode3.

Fault Primary Backup Inline graphic (s) Inline graphic (s) CTI (s)
F1 OCR1 OCR2 0.1830 0.4825 0.2995
OCR1 OCR19 0.1830 0.4824 0.2994
F2 OCR9 OCR18 6.3405 6.6395 0.2990
OCR2 OCR3 0.4795 0.7787 0.2992
F3 OCR10 OCR9 3.1928 6.3405 3.1477
OCR3 OCR4 2.1969 2.4962 0.2993
F4 OCR11 OCR10 1.9150 2.2142 0.2992
OCR4 OCR16 3.0644 3.3025 0.3090
OCR12 OCR11 1.6212 1.9203 0.2992
F5 OCR5 OCR6 0.1731 0.4722 0.2991
OCR13 OCR20 0.8602 1.1597 0.2995
F6 OCR6 OCR7 0.7066 1.0058 0.2991
OCR14 OCR13 0.5608 0.8602 0.2995
F7 OCR7 OCR8 0.9998 1.2997 0.2999
OCR7 OCR21 0.9998 1.2996 0.2998
F8 OCR15 OCR14 0.2613 0.5608 0.2995
OCR16 OCR21 0.1520 1.3079 1.1559
OCR16 OCR15 0.1520 0.2613 0.1093

Figure 6. illustrates the distribution of primary and backup operating times together with the CTI values. Most relay pairs cluster around the 0.3 s reference line, while only a few outliers are observed. These results highlight the increased coordination sensitivity in islanded operation due to the limited DG fault current contribution.

Fig. 6.

Fig. 6

Fault current magnitudes observed by primary and backup relays in Mode 3.

The total operating times in islanded mode are 74.79 s for GA, 89.35 s for WCA, and 144.00 s for BB–BC. GA achieves the lowest operating time; however, a CTI violation is observed under the reduced fault current conditions. WCA maintains coordination without violations, while BB–BC results in significantly higher operating time. A comprehensive comparison across all operating modes is provided in the next section.

Comparative analysis across all operating modes

The overall coordination performance of the 9-bus system was evaluated under three operating conditions: conventional operation without DG, full DG integration, and islanded mode. The optimized TMS values for all relays and the corresponding total operating times are summarized in Table 7, while the comparative total operating times are illustrated in Fig. 7. The statistical validation of the three optimization algorithms is presented through detailed analysis in Figs. 8, 9, 10, which show the performance of GA over 30 independent runs for Modes 1, 2, and 3, respectively. Each figure includes boxplots illustrating dispersion and outliers, histograms showi For Mode 1 (Fig. 8), WCA achieves the best objective function value (11.3789) with a coefficient of variation (CV%) of 0.681%, while GA demonstrates the highest stability (CV% = 0.424%). Similar trends are observed in Modes 2 and 3 (Figs. 9 and 10), where increased coordination complexity results in greater variability.ng distribution characteristics, and convergence profiles of best and mean trends. The overall statistical comparison among GA, BB–BC, and WCA is presented in Fig. 11. Figure 11a illustrates the objective function values across the three operating modes, Fig. 11b presents mean values with error bars (± 1 standard deviation) to quantify stochastic variability, and Fig. 11d shows the coefficient of variation for stability assessment. These results indicate that WCA provides a balanced performance in terms of solution quality, robustness, and computational efficiency across all investigated operating modes.

Table 7.

Optimized TMS values and total operating times for GA, WCA, and BB–BC in the three operating modes of the 9-bus system.

Relay Mode 1 Mode 2 Mode 3
GA WCA BB-BC GA WCA BB-BC GA WCA BB-BC
OCR1 0.050 0.051 0.058 0.050 0.050 0.057 0.050 0.050 0.050
OCR2 0.189 0.190 0.208 0.219 0.188 0.195 0.059 0.059 0.063
OCR3 0.286 0.286 0.299 0.456 0.413 0.436 0.120 0.120 0.115
OCR4 0.380 0.381 0.411 0.729 0.677 0.735 0.388 0.388 0.401
OCR5 0.054 0.054 0.080 0.050 0.050 0.052 0.050 0.050 0.050
OCR6 0.189 0.190 0.203 0.250 0.250 0.455 0.185 0.186 0.186
OCR7 0.285 0.286 0.303 0.430 0.429 2.010 0.297 0.460 0.341
OCR8 0.437 0.438 0.454 0.435 0.435 1.705 0.123 0.174 0.130
OCR9 0.210 0.194 0.282 1.218 1.616 1.560
OCR10 0.292 0.273 0.324 0.739 0.993 0.966
OCR11 0.192 0.174 0.189 0.639 0.830 0.772
OCR12 0.050 0.050 0.059 0.364 0.492 0.396
OCR13 0.167 0.165 0.229 0.167 0.165 1.265
OCR14 0.109 0.107 0.104 0.107 0.107 1.175
OCR15 0.050 0.050 0.058 0.050 0.050 0.679
OCR16 0.538 0.505 0.542 0.512 0.600 2.649
OCR17 0.414 0.415 1.342 1.260 1.963 0.000 0.000 0.000
OCR18 0.127 0.119 0.526 0.603 0.795 1.209
OCR19 0.074 0.074 1.093 0.091 0.092 0.821
OCR20 0.226 0.226 1.461 0.230 0.263 1.701
OCR21 0.485 0.458 0.501 0.204 0.290 0.462
Total Time 11.36 11.39 12.09 38.06 70.22 73.20 74.79 89.35 144.00

Fig. 7.

Fig. 7

Comparison of total relay operating times obtained by GA, WCA, and BB–BC in conventional, full DG, and islanded operating modes.

Fig. 8.

Fig. 8

Statistical analysis of GA Mode 1 over 30 runs (a) boxplot with outliers, (b) histogram showing skewness, (c) convergence profile of best and mean trends.

Fig. 9.

Fig. 9

Statistical analysis of GA Mode 2 over 30 runs (a) boxplot with outliers, (b) histogram showing skewness, (c) convergence profile of best and mean trends.

Fig. 10.

Fig. 10

Statistical analysis of GA Mode 3 over 30 runs (a) boxplot with outliers, (b) histogram showing skewness, (c) convergence profile of best and mean trends.

Fig. 11.

Fig. 11

Statistical performance analysis.

In conventional operation all algorithms achieved nearly identical and low operating times, confirming that relay coordination in a passive radial network can be efficiently handled by different optimization techniques. GA produced the lowest total operating time (11.36 s), with only minor differences compared to WCA and BB–BC. With full DG integration, coordination complexity increased due to bidirectional fault currents and multiple fault current contributions. Although GA produced the lowest total operating time (38.06 s), the solution did not fully satisfy coordination requirements for all relay pairs. In contrast, WCA and BB–BC maintained full coordination, with total operating times of 70.22 s and 73.20 s, respectively. Under this condition, WCA provided the most consistent coordination performance.

Islanded operation represents the most restrictive coordination scenario due to reduced short-circuit levels and limited fault current contribution from DG units. Under these conditions, all algorithms exhibited increased operating times. GA achieved a total operating time of 74.79 s but showed coordination sensitivity under strict constraints. WCA preserved coordination feasibility with a total operating time of 89.35 s, whereas BB–BC resulted in 144.00 s, reflecting difficulty in navigating the severely constrained solution space. Table 8 presents the comprehensive statistical comparison of GA, BB–BC, and WCA across the three operating modes based on 30 independent runs with 200 iterations each. Mode 1 involves 9 decision variables (basic configuration), while Modes 2 and 3 involve 21 decision variables due to DG integration. The reported metrics include best and worst objective values, mean performance, standard deviation (Std. Dev.), coefficient of variation (CV%), and mean computational time. Bold values indicate superior performance in each category.The overall statistical analysis shown in Fig. 11 further highlights the comparative behavior of the algorithms. As illustrated in Fig. 11a, WCA consistently achieves competitive objective function values across all operating modes (11.3789, 85.1263, and 74.8924 for Modes 1, 2, and 3, respectively). Figure 11b presents the mean values with error bars (± 1 standard deviation), confirming the robustness of the algorithms. The coefficient of variation analysis in Fig. 11d indicates that GA exhibits the highest stability in Modes 1 and 2 (CV% = 0.424% and 2.478%, respectively), while WCA demonstrates strong stability in Mode 3 (CV% = 2.440%). Overall, GA demonstrates strong objective minimization capability under moderately constrained conditions, whereas WCA provides a balanced trade-off between solution quality, stability, and coordination feasibility across all investigated scenarios. BB–BC remains stable but becomes less efficient as coordination complexity increases.

Table 8.

Comprehensive statistical analysis of optimization algorithms for 9-bus relay coordination problem.

Mode Algorithm Num Vars Best Worst Mean Val Std Dev CV percent
Mode 1 GA 9 11.3857 11.5623 11.4422 0.0485 0.423869536
Mode 1 BB-BC 9 11.3928 11.7456 11.5187 0.0895 0.776997404
Mode 1 WCA 9 11.3789 11.6895 11.4966 0.0782 0.680201103
Mode 2 GA 21 85.4726 92.8406 88.1564 2.1846 2.478095748
Mode 2 BB-BC 21 86.1246 95.7823 89.5478 3.1285 3.493664836
Mode 2 WCA 21 85.1263 93.4587 87.8925 2.4879 2.830616947
Mode 3 GA 21 75.3125 82.5679 78.2454 2.0159 2.576381487
Mode 3 BB-BC 21 76.0489 84.9236 79.8322 2.7563 3.452616864
Mode 3 WCA 21 74.8924 81.3456 77.5648 1.8923 2.439637568

Results for the 30-bus distribution system

The 30-bus mesh system implements DOCRs to handle bidirectional fault currents inherent in meshed topologies with distributed generation. This configuration represents modern active distribution networks with multiple power flow paths and complex protection requirements. Fault scenarios F1-F15 are strategically distributed throughout the network to evaluate comprehensive coordination performance under diverse conditions. Each fault location tests different relay pairs in both forward and reverse directions. Table 9. summarizes the optimized relay operating times obtained using GA, BB-BC, and WCA for all fault locations. The total operating times are 40.63 s for GA, 39.10 s for BB-BC, and 38.13 s for WCA. The results indicate that all three algorithms succeed in achieving feasible coordination across the investigated scenarios. However, WCA provides the lowest cumulative operating time, followed closely by BB-BC, while GA yields a slightly higher total delay.

Table 9.

Optimization results for 30-bus mesh system.

Fault Fault current (A) CMS Relay TMS (GA) TMS (WCA) TMS (BB-BC)
F1 12,954 25.91 DOCR1-F 0.05 0.04 0.04
2527 3.16 DOCR2-R 1.52 0.25 0.25
2527 8.42 DOCR3-F 0.46 0.45 0.45
F2 10,428 20.86 DOCR2-F 0.57 0.48 0.47
3655 4.57 DOCR9-R 0.70 0.53 0.53
2088 6.96 DOCR5-F 0.69 0.66 0.66
F3 2925 9.75 DOCR4-F 0.42 0.41 0.41
7375 24.58 DOCR5-F 0.41 0.30 0.30
6177 7.72 DOCR6-R 0.62 0.41 0.51
F4 3202 10.67 DOCR6-F 0.07 0.07 0.07
9416 31.39 DOCR7-F 0.71 0.48 0.48
2085 6.95 DOCR8-R 1.12 0.68 0.68
F5 3645 12.15 DOCR10-F 0.07 0.06 0.06
1226 4.09 DOCR11-R 0.27 0.26 0.26
F9 4360 14.53 DOCR16-F 0.24 0.38 0.38
2980 9.93 DOCR17-F 0.07 0.11 0.11
850 2.83 DOCR23-R 0.61 0.31 0.31
F11 6661 22.20 DOCR20-F 0.05 0.04 0.04
4700 15.67 DOCR21-F 0.06 0.06 0.06
1645 5.48 DOCR22-R 0.27 0.27 0.27
F15 5314 17.71 DOCR27-F 0.06 0.05 0.05
2270 7.57 DOCR24-R 0.26 0.25 0.25
Total operating time 40.63 s 38.13 s 39.10 s

For each fault scenario, the relay operating in the forward direction (F) acts as the main clearing device for that fault path, while the corresponding reverse (R) setting of adjacent relays provides the required time-graded backup in the opposite direction. The optimized results confirm proper separation between forward and reverse operating times, ensuring secure discrimination without directional mis operation. Although the performance differences among the algorithms are moderate, WCA achieves the lowest cumulative operating time while maintaining stable coordination across all directional relay pairs. The close proximity of the obtained totals indicates that the dual-setting formulation increases the dimensionality of the search space but remains tractable for the investigated metaheuristic techniques.

Practical deployment considerations and limitations

Although the proposed optimization framework demonstrates effective coordination performance under the investigated operating modes, several practical considerations must be acknowledged before real-world deployment. First, the relay TMS are treated in this study as continuous decision variables, whereas practical digital relays implement discrete setting steps with limited resolution. Consequently, the optimal values obtained from the metaheuristic algorithms may require rounding to the nearest available setting, which can slightly alter CTIs. In practical applications, a post-optimization verification stage is therefore necessary to ensure that discretized settings preserve coordination feasibility. Second, the short-circuit currents used in this study are calculated according to IEC 60909 under defined operating modes. In actual distribution networks, fault current levels vary with system topology, DG penetration level, and generation dispatch. Inverter-based distributed generators, in particular, typically provide limited and controlled fault current contributions, especially during islanded operation. These variations may narrow coordination margins and increased sensitivity to parameter uncertainty. For this reason, practical implementation may require conservative CTI margins greater than the nominal 0.3 s adopted in this work. Furthermore, non-ideal hardware characteristics are not explicitly modeled in the optimization framework. Current transformer saturation, measurement errors, breaker mechanical operating time variability, and relay processing delays can influence effective clearing times in practice. These factors may reduce the effective discrimination margin between primary and backup relays, particularly under low fault current conditions. Finally, while the proposed methodology is validated on 9-bus and 30-bus benchmark systems, large-scale practical distribution networks may involve significantly higher numbers of relays and coordination constraints. In such cases, computational burden and convergence reliability become important considerations, and parallel or hybrid optimization strategies may be required. Despite these limitations, the presented framework provides a structured and extensible foundation for relay coordination in DG-integrated distribution systems and can be further enhanced to incorporate discrete settings, uncertainty modeling, and large-scale implementation requirements.

Conclusion

This study investigated overcurrent relay coordination in DG-integrated distribution networks under different operating modes. The results show that coordination performance becomes increasingly sensitive to fault current distribution as DG penetration increases, particularly under islanded operation where fault levels are significantly reduced. The analysis confirms that achieving reliable coordination in DG-dominated networks requires optimization techniques with strong robustness and effective constraint-handling capability. As coordination margins become narrower, maintaining feasibility across different operating modes becomes more critical than aggressive minimization of relay operating times. Overall, the findings emphasize the need for reliable and robust coordination strategies for modern active distribution networks and provide useful insight into the suitability of metaheuristic optimization approaches for practical protection applications.

In the radial 9-bus system, the GA achieves the lowest total operating time under conventional grid-connected operation (11.36 s), followed closely by WCA (11.39 s) and BB–BC (12.09 s). However, under DG-integrated conditions (Mode 2), GA records 38.06 s, while WCA and BB–BC result in 70.22 s and 73.20 s, respectively. Under islanded operation (Mode 3), GA achieves 74.79 s, WCA results in 89.35 s, and BB–BC reaches 144.00 s, reflecting the increased coordination difficulty under reduced fault current levels.

In the islanded 30-bus system, WCA attains the minimum total operating time, followed by BB–BC, while GA yields slightly higher operating times but maintains stable coordination behavior. Statistical analysis over 30 independent runs confirms consistent performance, with GA showing the lowest variability in Mode 1 (CV% = 0.424%) and WCA demonstrating strong robustness in Mode 3 (CV% = 2.440%).

Author contributions

A.B. and C. wrote the main manuscript text and prepared figures. All authors reviewed the manuscript.

Funding

Open access funding provided by The Science, Technology & Innovation Funding Authority (STDF) in cooperation with The Egyptian Knowledge Bank (EKB).

Data availability

The datasets analyzed during the current study are available from the corresponding author on reasonable request.

Competing interests

The authors declare no competing interests.

Footnotes

Publisher’s note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

References

  • 1.Burrett, R. et al. Renewable energy policy network for the 21st century. REN21 Renewables Global Status Report (2009).
  • 2.Couture, T., Busch, H., Hansen, T. & Leidreiter, A. REN21-Renewables in cities 2019 global status report-preliminary findings (2019).
  • 3.Coster, E. J., Myrzik, J. M., Kruimer, B. & Kling, W. L. Integration issues of distributed generation in distribution grids. Proc. IEEE99(1), 28–39 (2010). [Google Scholar]
  • 4.Brahma, S. M. & Girgis, A. A. Development of adaptive protection scheme for distribution systems with high penetration of distributed generation. IEEE Trans. Power Deliv.19(1), 56–63 (2004). [Google Scholar]
  • 5.Gonen, T. Electric Power Distribution Engineering (CRC Press, 2014). [Google Scholar]
  • 6.Sookrod, P. & Wirasanti, P. Overcurrent relay coordination tool for radial distribution systems with distributed generation. In 2018 5th International Conference on Electrical and Electronic Engineering (ICEEE) 13–17. (IEEE, 2018).
  • 7.Agarwal, H. & Rai, J. Protection coordination of distributed system with distributed generation. In 2022 International Conference on Intelligent Controller and Computing for Smart Power (ICICCSP) 1–6. (IEEE, 2022).
  • 8.Norshahrani, M., Mokhlis, H., Abu Bakar, A. H., Jamian, J. J. & Sukumar, S. Progress on protection strategies to mitigate the impact of renewable distributed generation on distribution systems. Energies10(11), 1864 (2017). [Google Scholar]
  • 9.Coffele, F., Booth, C., Dysko, A. & Burt, G. Quantitative analysis of network protection blinding for systems incorporating distributed generation. IET Gener. Transm. Distrib.6(12), 1218–1224 (2012). [Google Scholar]
  • 10.Jennett, K. I., Booth, C. D., Coffele, F. & Roscoe, A. J. Investigation of the sympathetic tripping problem in power systems with large penetrations of distributed generation. IET Gener. Transm. Distrib.9(4), 379–385 (2015). [Google Scholar]
  • 11.Ataee-Kachoee, A., Hashemi-Dezaki, H. & Ketabi, A. Optimized adaptive protection coordination of microgrids by dual-setting directional overcurrent relays considering different topologies based on limited independent relays’ setting groups. Electr. Power Syst. Res.214, 108879 (2023). [Google Scholar]
  • 12.Eladl, A. A., Sheta, A. N., Elgamal, M., Vasquez, J. C. & Sedhom, B. E. Optimal directional overcurrent relay settings for stable microgrids with synchronous and inverter-based resources. Int. J. Electr. Power Energy Syst.167, 110639 (2025). [Google Scholar]
  • 13.Bhise, D. R., Kankale, R. S. & Jadhao, S. Impact of distributed generation on protection of power system. In 2017 International conference on innovative mechanisms for industry applications (ICIMIA) 399–405. (IEEE, 2017).
  • 14.Yousaf, M. & Mahmood, T. Protection coordination for a distribution system in the presence of distributed generation. Turk. J. Electr. Eng. Comput. Sci.25(1), 408–421 (2017). [Google Scholar]
  • 15.Singh, M. & Teja, A. R. Adaptive over-current protection algorithm for a microgrid. In 2018 IEEE 13th International Conference on Industrial and Information Systems (ICIIS) 448–452. (IEEE, 2018).
  • 16.Nascimento, J. P., Brito, N. S. & Souza, B. A. An adaptive overcurrent protection system applied to distribution systems. Comput. Electr. Eng.81, 106545 (2020). [Google Scholar]
  • 17.Kaur, G., Prakash, A. & Rao, K. U. A critical review of microgrid adaptive protection techniques with distributed generation. Renew. Energy Focus39, 99–109 (2021). [Google Scholar]
  • 18.Shabani, A. & Mazlumi, K. Evaluation of a communication-assisted overcurrent protection scheme for photovoltaic-based DC microgrid. IEEE Trans. Smart Grid11(1), 429–439 (2019). [Google Scholar]
  • 19.Jamal, N. Z., Sulaiman, M. H., Aliman, O. & Mustaffa, Z. Optimal overcurrent relays coordination using an improved grey wolf optimizer. Int. J. Adv. Comput. Sci. Appl.9(11), 7 (2018). [Google Scholar]
  • 20.S. Abeid and Y. Hu, "Overcurrent relays coordination optimisation methods in distribution systems for microgrids: A review," in 15th International Conference on Developments in Power System Protection (DPSP 2020), 2020: IET.
  • 21.V. A. Papaspiliotopoulos, G. N. Korres, and N. D. Hatziargyriou, "Protection coordination in modern distribution grids integrating optimization techniques with adaptive relay setting," in 2015 IEEE Eindhoven PowerTech, 2015: IEEE, pp. 1–6.
  • 22.C. So, K. Li, K. Lai, and K. Fung, "Application of genetic algorithm for overcurrent relay coordination," in 6th international conference on developments in power systems protection, 1997: IET, pp. 66–69.
  • 23.Razavi, F., Abyaneh, H. A., Al-Dabbagh, M., Mohammadi, R. & Torkaman, H. A new comprehensive genetic algorithm method for optimal overcurrent relays coordination. Electr. Power Syst. Res.78(4), 713–720 (2008). [Google Scholar]
  • 24.Alam, M. N., Khurshaid, T. & Rhee, S.-B. Hybrid GA-IPM algorithm for optimal protection coordination of directional overcurrent relays with mixed time current characteristic curves. Electr. Eng.106(4), 5027–5041 (2024). [Google Scholar]
  • 25.Bedekar, P. P. & Bhide, S. R. Optimum coordination of directional overcurrent relays using the hybrid GA-NLP approach. IEEE Trans. Power Deliv.26(1), 109–119 (2010). [Google Scholar]
  • 26.Tantichaiwanich, W. & Chayakulkheeree, K. Optimal coordination of adaptive overcurrent relay for microgrid system using hybrid PSO-LP. In 2025 13th International Electrical Engineering Congress (iEECON) 1–6. (IEEE, 2025).
  • 27.Habib, K. et al. An improved technique of hybridization of PSO for the optimal coordination of directional overcurrent protection relays of IEEE bus system. Energies15(9), 3076 (2022). [Google Scholar]
  • 28.Eskandar, H., Sadollah, A., Bahreininejad, A. & Hamdi, M. Water cycle algorithm–A novel metaheuristic optimization method for solving constrained engineering optimization problems. Comput. Struct.110, 151–166 (2012). [Google Scholar]
  • 29.El Naily, N., Saad, S. M., El Misslati, M. M. & Mohamed, F. A. Optimal protection coordination for IEC microgrid benchmark using water cycle algorithm. In 2019 10th International Renewable Energy Congress (IREC) 1–6. (IEEE, 2019).
  • 30.Alanazi, M. Optimal integration of distributed generators and soft open points in radial distribution networks: A hybrid WCA-PSO approach. Processes13(6), 1775 (2025). [Google Scholar]
  • 31.Zhu, L. Energy management in microgrid integrated with ultracapacitor-equipped electric vehicles and renewable resources using hybrid algorithm perspective. Mainten. Reliab. Eksploatacja i Niezawodność27, 3 (2025). [Google Scholar]
  • 32.Abeid, S., Hu, Y., Alasali, F. & El-Naily, N. Innovative optimal nonstandard tripping protection scheme for radial and meshed microgrid systems. Energies15(14), 4980 (2022). [Google Scholar]
  • 33.Rezaei, M. F., Gandomkar, M. & Nikoukar, J. Multi-objective function optimization for locating and sizing of renewable energy sources and energy storages in radial distribution networks with digital directional overcurrent relays and digital dual-setting directional overcurrent relays. J. Electr. Eng. Technol.17(4), 2095–2105 (2022). [Google Scholar]
  • 34.Saleh, K. A., Zeineldin, H., Al-Hinai, A. & El-Saadany, E. F. Optimal coordination of directional overcurrent relays using a new time–current–voltage characteristic. IEEE Trans. Power Deliv.30(2), 537–544 (2014). [Google Scholar]
  • 35.Li, J., Feng, J., Huang, M., Liu, S. & Wang, G. Optimal protection coordination for directional overcurrent relays in radial distribution networks with inverter-based distributed energy resources. Int. J. Electr. Power Energy Syst.167, 110622 (2025). [Google Scholar]
  • 36.Asl, S. A. F., Gandomkar, M. & Nikoukar, J. Optimal protection coordination in the micro-grid including inverter-based distributed generations and energy storage system with considering grid-connected and islanded modes. Electr. Power Syst. Res.184, 106317 (2020). [Google Scholar]
  • 37.Sati, T. E., Azzouz, M. A. & Shaaban, M. F. Harmonic dual-setting directional overcurrent protection for inverter-based islanded microgrids. IEEE Access11, 34630–34642 (2023). [Google Scholar]
  • 38.Nsaif, Y. M., Lipu, M. H., Ayob, A., Yusof, Y. & Hussain, A. Fault detection and protection schemes for GE integrated to distribution network: Challenges and suggestions. IEEE Access9, 142693–142717 (2021). [Google Scholar]
  • 39.Najy, W. K., Zeineldin, H. H. & Woon, W. L. Optimal protection coordination for microgrids with grid-connected and islanded capability. IEEE Trans. Industr. Electron.60(4), 1668–1677 (2012). [Google Scholar]
  • 40.Patel, K., Arif, M. T., Saha, S. & Aktarujjaman, M. Investigation of renewable energy based DG impacts on protection relay operation. In 2019 29th Australasian Universities Power Engineering Conference (AUPEC) 1–6. (IEEE, 2019).
  • 41.Zhou, X., Qiu, Z., Liu, Q., Jiang, R. & Liu, J. Influence of distribution network under distributed power access on relay protection. In 2019 IEEE Sustainable Power and Energy Conference (iSPEC) 1066–1071. (IEEE, 2019).
  • 42.Dehghanpour, E., Karegar, H. K., Kheirollahi, R. & Soleymani, T. Optimal coordination of directional overcurrent relays in microgrids by using cuckoo-linear optimization algorithm and fault current limiter. IEEE Trans. Smart Grid9(2), 1365–1375 (2016). [Google Scholar]
  • 43.Vala, T. M., Rajput, V. N. & Al-Sumaiti, A. S. Investigating the performance of non-standard characteristics-based overcurrent relays and their optimum coordination in distributed generators connected networks. IET Gener. Transm. Distrib.17(13), 2978–2995 (2023). [Google Scholar]
  • 44.Rajput, V. N., Adelnia, F. & Pandya, K. S. Optimal coordination of directional overcurrent relays using improved mathematical formulation. IET Gener. Transm. Distrib.12(9), 2086–2094 (2018). [Google Scholar]
  • 45.Dabbagchi, I. IEEE 30-Bus System (American Electric Power System, 1993). [Google Scholar]
  • 46.Noghabi, A. S., Sadeh, J. & Mashhadi, H. R. Considering different network topologies in optimal overcurrent relay coordination using a hybrid GA. IEEE Trans. Power Deliv.24(4), 1857–1863 (2009). [Google Scholar]
  • 47.Sharaf, H. M., Zeineldin, H. H. & El-Saadany, E. Protection coordination for microgrids with grid-connected and islanded capabilities using communication assisted dual setting directional overcurrent relays. IEEE Trans. Smart Grid9(1), 143–151 (2016). [Google Scholar]
  • 48.El-Hamrawy, A. H., Ebrahiem, A. A. M. & Megahed, A. I. Improved adaptive protection scheme based combined centralized/decentralized communications for power systems equipped with distributed generation. IEEE Access10, 97061–97074 (2022). [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

The datasets analyzed during the current study are available from the corresponding author on reasonable request.


Articles from Scientific Reports are provided here courtesy of Nature Publishing Group

RESOURCES