. 2006 Jan;72(1):378–383. doi: 10.1128/AEM.72.1.378-383.2006

TABLE 4.

Change in sampling site-specific parameters between the chlorine phase and the monochloramine phase

Parameter Value for hot water heaters
Value for distal sites
CL phase MC phase P valuea CL phase MC phase P value
Total chlorine detectable, no. (%) 72 (75.8) 77 (81.0) 1.0 70 (76.1) 77 (81.9) 0.21
Free chlorine detectable, no. (%) 59 (61.5) 0 (0) <0.0001 60 (63.8) 0 (0) <0.0001
MC detectable, no. (%) 0 (0) 85 (88.5) <0.0001 0 (0) 87 (92.6) <0.0001
Temp categoryb
    <26°C 4 (4.2) 2 (2.1) 0.61c 2 (2.2) 1 (1.1) 0.54c
    26-42°C 35 (36.5) 39 (40.6) 28 (30.8) 35 (37.2)
    >42°C 57 (59.4) 55 (57.3) 61 (67.0) 58 (61.7)
Mean temp (°C) 43.6 44.1 0.72d 44.1 43.5 0.57d
Mean pH 7.6 7.7 0.05d 7.7 7.7 0.19d
Mean conductivity (μS/cm) 533.7 503.8 0.12d 518.7 498.7 0.07d
No. of sample locations with Legionella 9 (9.4) 4 (4.2) 0.062 13 (13.8) 4 (4.3) 0.004
No. of sample locations with amoebae 2 (2.0) 2 (2.1) 1.0 11 (11.7) 14 (14.9) 0.25
a

P value comparing the value for CL phase to the value for MC phase by McNemar's test unless otherwise indicated.

b

Categories indicate temperatures favorable (26 to 42°C) and unfavorable (<26°C and >42°C) for Legionella growth.

c

By Fisher's exact test.

d

By t test.