. 2007 Jan 19;73(5):1489–1492. doi: 10.1128/AEM.02191-06

TABLE 2.

Association of hot water distribution systems and hotel characteristics with Legionella contamination by univariate analysis

Characteristic No. (%) of samples:
RR (95% CI)
With Legionella spp. Without Legionella spp.
No. of rooms, ≥80 31 (27.0) 49 (18.2) 1.5 (1.0-2.2)a
Hotel age, ≥30 yr 34 (17.2) 42 (28.0) 0.6 (0.4-0.9)a
Boiler age, ≥20 yr 5 (20.8) 58 (22) 0.9 (0.4-2.1)
Apartments 73 (21.2) 6 (23.1) 0.9 (0.4-1.9)
Bungalows 11 (44) 68 (19.8) 2.2 (1.3-3.6)b
Seasonal operation 16 (42.1) 58 (18.4) 2.3 (1.5-3.5)b
Water source, municipal supply 70 (20.5) 10 (23.3) 0.8 (0.5-1.6)
Water source, well 3 (25.0) 77 (20.6) 1.2 (0.4-3.3)
Water tank 30 (27.5) 44 (17.1) 1.6 (1.0-2.4)a
Operation temp, ≥55°C 15 (27.3) 58 (19.0) 1.4 (0.9-2.3)
Thermal insulation of system 50 (20.4) 19 (19.4) 1.0 (0.6-1.7)
Steel plumbing 5 (26.3) 75 (20.5) 1.2 (0.6-2.8)
Cu-PVC plumbing 3 (23.1) 77 (20.7) 1.1 (0.4-3.0)
Cu plumbing 32 (21.1) 48 (20.6) 1.0 (0.7-1.5)
PVC plumbing 9 (24.3) 71 (20.4) 1.2 (0.6-2.2)
Independent disinfection system 9 (10.8) 245 (29.3) 0.4 (0.2-0.7)c
Independent water filtration 10 (23.8) 49 (21.6) 1.1 (0.6-2.0)
Water storage tank protected 22 (30.1) 3 (18.8) 1.6 (0.4-4.7)
Oil heat 55 (25.1) 25 (15.1) 1.7 (1.0-2.5)a
Electric heat 8 (14.8) 72 (21.8) 0.6 (0.3-1.3)
Solar heat 8 (17.4) 72 (21.2) 0.8 (0.4-1.6)
a

P = 0.01 to 0.03.

b

P = 0.001 to 0.007.

c

P = 0.00001.