Control of endemic nosocomial legionnaires' disease by using sterile potable water for high risk patients.

T J Marrie 1, D Haldane 1, S MacDonald 1, K Clarke 1, C Fanning 1, S Le Fort-Jost 1, G Bezanson 1, J Joly 1
PMCID: PMC2272081  PMID: 1752308

Abstract

In a setting where potable water is contaminated with Legionella pneumophila serogroup 1, we performed two case control studies. The first case control study consisted of 17 cases of nosocomial Legionnaires' disease (LD) and 33 control (the patients who were admitted to the ward where the case was admitted immediately before and after the case) subjects. Cases had a higher mortality rate 65% vs 12% (P less than 0.004); were more likely to have received assisted ventilation (P less than 0.00001); to have nasogastric tubes (P less than 0.0004) and to be receiving corticosteroids or other immunosuppressive therapy (P less than 0.0001). Based on the results of this study, sterile water was used to flush nasogastric tubes and to dilute nasogastric feeds. Only 3 cases of nosocomial LD occurred during the next year compared with 12 the previous year (P less than 0.0001). Nine cases subsequently occurred and formed the basis for the second case-control study. Eighteen control subjects were those patients admitted to the same unit where the case developed LD, immediately before and after the case. The mortality rate for the cases was 89% vs 6% for controls (P less than 0.00003). The only other significant difference was that cases were more likely to be receiving corticosteroids or other immunosuppressive therapy 89% vs 39% (less than 0.01). We hypothesized that microaspiration of contaminated potable water by immunocompromised patients was a risk factor for nosocomial Legionnaires' disease. From 17 March 1989 onwards such patients were given only sterile potable water. Only two cases of nosocomial LD occurred from June 1989 to September 1990 and both occurred on units where the sterile water policy was not in effect. We conclude that aspiration of contaminated potable water is a possible route for acquisition of nosocomial LD in our hospital and that provision of sterile potable water to high risk patients (those who are receiving corticosteroids or other immunosuppressive drugs; organ transplant recipients or hospitalized in an intensive care unit) should be mandatory.

Full text

PDF
591

Selected References

These references are in PubMed. This may not be the complete list of references from this article.

  1. Arnow P. M., Chou T., Weil D., Shapiro E. N., Kretzschmar C. Nosocomial Legionnaires' disease caused by aerosolized tap water from respiratory devices. J Infect Dis. 1982 Oct;146(4):460–467. doi: 10.1093/infdis/146.4.460. [DOI] [PubMed] [Google Scholar]
  2. Atherton S. T., White D. J. Stomach as source of bacteria colonising respiratory tract during artificial ventilation. Lancet. 1978 Nov 4;2(8097):968–969. doi: 10.1016/s0140-6736(78)92530-8. [DOI] [PubMed] [Google Scholar]
  3. Bollin G. E., Plouffe J. F., Para M. F., Prior R. B. Difference in virulence of environmental isolates of Legionella pneumophila. J Clin Microbiol. 1985 May;21(5):674–677. doi: 10.1128/jcm.21.5.674-677.1985. [DOI] [PMC free article] [PubMed] [Google Scholar]
  4. Craven D. E., Driks M. R. Nosocomial pneumonia in the intubated patient. Semin Respir Infect. 1987 Mar;2(1):20–33. [PubMed] [Google Scholar]
  5. Craven D. E., Kunches L. M., Kilinsky V., Lichtenberg D. A., Make B. J., McCabe W. R. Risk factors for pneumonia and fatality in patients receiving continuous mechanical ventilation. Am Rev Respir Dis. 1986 May;133(5):792–796. [PubMed] [Google Scholar]
  6. Edelstein P. H., Beer K. B., DeBoynton E. D. Influence of growth temperature on virulence of Legionella pneumophila. Infect Immun. 1987 Nov;55(11):2701–2705. doi: 10.1128/iai.55.11.2701-2705.1987. [DOI] [PMC free article] [PubMed] [Google Scholar]
  7. Edelstein P. H. Improved semiselective medium for isolation of Legionella pneumophila from contaminated clinical and environmental specimens. J Clin Microbiol. 1981 Sep;14(3):298–303. doi: 10.1128/jcm.14.3.298-303.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
  8. Fraser D. W. Potable water as a source for legionellosis. Environ Health Perspect. 1985 Oct;62:337–341. doi: 10.1289/ehp.8562337. [DOI] [PMC free article] [PubMed] [Google Scholar]
  9. Fraser D. W., Tsai T. R., Orenstein W., Parkin W. E., Beecham H. J., Sharrar R. G., Harris J., Mallison G. F., Martin S. M., McDade J. E. Legionnaires' disease: description of an epidemic of pneumonia. N Engl J Med. 1977 Dec 1;297(22):1189–1197. doi: 10.1056/NEJM197712012972201. [DOI] [PubMed] [Google Scholar]
  10. Haley R. W., Quade D., Freeman H. E., Bennett J. V. The SENIC Project. Study on the efficacy of nosocomial infection control (SENIC Project). Summary of study design. Am J Epidemiol. 1980 May;111(5):472–485. doi: 10.1093/oxfordjournals.aje.a112928. [DOI] [PubMed] [Google Scholar]
  11. Helms C. M., Massanari R. M., Wenzel R. P., Pfaller M. A., Moyer N. P., Hall N. Legionnaires' disease associated with a hospital water system. A five-year progress report on continuous hyperchlorination. JAMA. 1988 Apr 22;259(16):2423–2427. [PubMed] [Google Scholar]
  12. Joly J. R., Chen Y. Y., Ramsay D. Serogrouping and subtyping of Legionella pneumophila with monoclonal antibodies. J Clin Microbiol. 1983 Nov;18(5):1040–1046. doi: 10.1128/jcm.18.5.1040-1046.1983. [DOI] [PMC free article] [PubMed] [Google Scholar]
  13. Kaan J. A., Simoons-Smit A. M., MacLaren D. M. Another source of aerosol causing nosocomial Legionnaires' disease. J Infect. 1985 Sep;11(2):145–148. doi: 10.1016/s0163-4453(85)92051-1. [DOI] [PubMed] [Google Scholar]
  14. Katz S. M., Hammel J. M. The effect of drying, heat, and pH on the survival of Legionella pneumophila. Ann Clin Lab Sci. 1987 May-Jun;17(3):150–156. [PubMed] [Google Scholar]
  15. Knaus W. A., Draper E. A., Wagner D. P., Zimmerman J. E. APACHE II: a severity of disease classification system. Crit Care Med. 1985 Oct;13(10):818–829. [PubMed] [Google Scholar]
  16. Korvick J. A., Yu V. L., Fang G. D. Legionella species as hospital-acquired respiratory pathogens. Semin Respir Infect. 1987 Mar;2(1):34–47. [PubMed] [Google Scholar]
  17. Le Saux N. M., Sekla L., McLeod J., Parker S., Rush D., Jeffery J. R., Brunham R. C. Epidemic of nosocomial Legionnaires' disease in renal transplant recipients: a case-control and environmental study. CMAJ. 1989 May 1;140(9):1047–1053. [PMC free article] [PubMed] [Google Scholar]
  18. Marrie T. J., MacDonald S., Clarke K., Haldane D. Nosocomial legionnaires' disease: lessons from a four-year prospective study. Am J Infect Control. 1991 Apr;19(2):79–85. doi: 10.1016/0196-6553(91)90043-c. [DOI] [PubMed] [Google Scholar]
  19. Mastro T. D., Fields B. S., Breiman R. F., Campbell J., Plikaytis B. D., Spika J. S. Nosocomial Legionnaires' disease and use of medication nebulizers. J Infect Dis. 1991 Mar;163(3):667–671. doi: 10.1093/infdis/163.3.667. [DOI] [PubMed] [Google Scholar]
  20. McDade J. E., Shepard C. C., Fraser D. W., Tsai T. R., Redus M. A., Dowdle W. R. Legionnaires' disease: isolation of a bacterium and demonstration of its role in other respiratory disease. N Engl J Med. 1977 Dec 1;297(22):1197–1203. doi: 10.1056/NEJM197712012972202. [DOI] [PubMed] [Google Scholar]
  21. Muder R. R., Yu V. L., McClure J. K., Kroboth F. J., Kominos S. D., Lumish R. M. Nosocomial Legionnaires' disease uncovered in a prospective pneumonia study. JAMA. 1983 Jun 17;249(23):3184–3188. [PubMed] [Google Scholar]
  22. Pierce A. K., Sanford J. P. Aerobic gram-negative bacillary pneumonias. Am Rev Respir Dis. 1974 Nov;110(5):647–658. doi: 10.1164/arrd.1974.110.5.647. [DOI] [PubMed] [Google Scholar]
  23. Roussel A. F., Chabbert Y. A. Taxonomy and epidemiology of gram-negative bacterial plasmids studied by DNA-DNA filter hybridization in formamide. J Gen Microbiol. 1978 Feb;104(2):269–276. doi: 10.1099/00221287-104-2-269. [DOI] [PubMed] [Google Scholar]
  24. Stout J. E., Yu V. L., Muraca P. Isolation of Legionella pneumophila from the cold water of hospital ice machines: implications for origin and transmission of the organism. Infect Control. 1985 Apr;6(4):141–146. doi: 10.1017/s0195941700062937. [DOI] [PubMed] [Google Scholar]
  25. Stout J., Yu V. L., Vickers R. M., Zuravleff J., Best M., Brown A., Yee R. B., Wadowsky R. Ubiquitousness of Legionella pneumophila in the water supply of a hospital with endemic Legionnaires' disease. N Engl J Med. 1982 Feb 25;306(8):466–468. doi: 10.1056/NEJM198202253060807. [DOI] [PubMed] [Google Scholar]
  26. Thacker S. B., Bennett J. V., Tsai T. F., Fraser D. W., McDade J. E., Shepard C. C., Williams K. H., Jr, Stuart W. H., Dull H. B., Eickhoff T. C. An outbreak in 1965 of severe respiratory illness caused by the Legionnaires' disease bacterium. J Infect Dis. 1978 Oct;138(4):512–519. doi: 10.1093/infdis/138.4.512. [DOI] [PubMed] [Google Scholar]
  27. Vickers R. M., Stout J. E., Yu V. L., Rihs J. D. Manual of culture methodology for Legionella. Semin Respir Infect. 1987 Dec;2(4):274–279. [PubMed] [Google Scholar]
  28. du Moulin G. C., Paterson D. G., Hedley-Whyte J., Lisbon A. Aspiration of gastric bacteria in antacid-treated patients: a frequent cause of postoperative colonisation of the airway. Lancet. 1982 Jan 30;1(8266):242–245. doi: 10.1016/s0140-6736(82)90974-6. [DOI] [PubMed] [Google Scholar]

Articles from Epidemiology and Infection are provided here courtesy of Cambridge University Press

RESOURCES