Table 2.
Parameter | Recommended level |
---|---|
Temperature (dry bulb) | 19-23°C |
Relative humidity (RH) | 40-70% |
More than 55% RH is needed in carpeted buildings with under floor heating to avoid electrostatic shocks | |
Ventilation | |
Delivery of fresh air | 8 l/s/person (minimum) |
16 l/s/person where some smoking | |
25 l/s/person where heavy smoking | |
Total air supply | 4–6 air changes/h |
Air speed | 0.1–0.3 m/s. Less than 0.1 m/s causes stuffiness. More than 0.3 m/s causes draughts. For air speeds higher than 0.1 m/s, CIBSE recommends an increase in air temperature to take account of air movement |
Sound | 46 dBA is the upper limit for general office work |
Lighting | 500 lux for general office work, 750 lux for deep-plan offices and work at drawing boards, proofreading, etc. |