Skip to main content
. 2010 Dec 2;10:343. doi: 10.1186/1471-2334-10-343

Table 1.

Environmental findings from the workplace of Case A, plant A

Date
(before or after infection)
Water systems sampled
(sample type)
Temperature (°C) Legionella concentration
(cfu/l)
Type of Legionella
28th Feb 2006
(before)
Active sludge basin
at the waste water treatment plant (water)
33.0 2.0 × 107 L. pneumophila serogroup 13

28th Feb 2006
(before)
Circulating waste water at the waste water treatment plant (water) 35.0 1.0 × 104 L. pneumophila serogroup 3

29th Aug 2006
(after)
Active sludge basin
at the waste water treatment plant (water)
36.0 1.0 × 106 L. pneumophila serogroup 1

29th Aug 2006
(after)
Post-clarification basin at the waste water treatment plant (water) 35.0 2.3 × 104 L. pneumophila serogroup 1, subgroup Bellingham

29th Aug 2006
(after)
Post-clarification basin at the waste water treatment plant (sludge) 36.0 2.0 × 106 and
1.0 × 106
L. pneumophila serogroup 1, subgroup Bellingham and L. pneumophila serogroup 13