Table 1.

Comparison of results for the presence or absence of Legionella or Legionella pneumophila as determined by quantitative PCR (qPCR) and culture

Results by culture

Legionella spp. Leg. pneumophila


Results by qPCR Detected Not detected Detected Not detected
Cooling towers
 Detected 73 (31)* 148 (64) 62 (27) 52 (22)
 Not detected 0 (0) 11 (5) 3 (1) 115 (50)
Hot and cold water
 Detected 278 (55) 217 (43) 249 (49) 168 (33)
 Not detected 3 (1) 7 (1) 10 (2) 78 (15)
*

Number (%) of samples.