. 2011 Apr;110(4):1032–1044. doi: 10.1111/j.1365-2672.2011.04957.x

Table 4.

Cooling towers – comparison of action and alert levels using quantitative PCR (qPCR) and culture for Legionella pneumophila and Legionella spp

Culture No. (%)

Target Action (>104 CFU l−1) Alert (>103 CFU l−1) Satisfactory (<103 CFU l−1)
Leg. pneumophila
 qPCR No. (%) Action (>5 × 104 GU l−1) 7 (3)* 2 (1) 11 (5)
Alert (>5 × 103 GU l−1) 9 (4) 10 (4) 9 (4)
Satisfactory (<5 × 103 GU l−1) 0 (0) 25 (11) 159 (69)
Legionella spp.
 qPCR No. (%) Action (>106 GU l−1) 5 (2) 9 (4) 41 (18)
Alert (>105 GU l−1) 11 (5) 22 (9) 44 (19)
Satisfactory (<105 GU l−1) 3 (1) 8 (3) 89 (38)

Figures in bold typeface represent those samples for which the results of both methods indicated the same action.

*

The number and (%) of tests displaying the indicated result.