Table 3.
Legionella culturing and monoclonal antibody testing of potable water samples collected from an apartment complex for seniors (n = 103 samples)
|
Sample site |
No. tested |
No. (%) positive |
|
|---|---|---|---|
| Any Legionella* | L. pneumophila 1 (1,2,3)** | ||
|
Affected buildings (A-1 and A-2)† | |||
| Water intake valves |
11 |
6 (55%) |
0 |
| A-1 apartments |
21 |
21 (100%) |
18 (86%) |
| A-2 apartments |
21 |
20 (95%) |
13 (62%) |
| Common areas |
22 |
12 (55%) |
0 |
|
Unaffected buildings (U-1 and U-2)† | |||
| Water intake valves |
8 |
1 (13%) |
0 |
| U-1 apartments |
7 |
4 (57%) |
0 |
| U-2 apartments |
7 |
6 (86%) |
0 |
| Fire hydrants | 6 | 2 (33%) | 0 |
* Any Legionella includes L. pneumophila and other undetermined species of blue-white Legionella that typically are not pathogenic.
**L. pneumophila 1 (1,2,3) denotes serogroup 1, monoclonal antibody type Knoxville (1,2,3).
† Cases occurred among residents and visitors of affected buildings A-1 and A-2 only.