. 2013 Jun 27;13:291. doi: 10.1186/1471-2334-13-291

Table 3.

Legionella culturing and monoclonal antibody testing of potable water samples collected from an apartment complex for seniors (n = 103 samples)

Sample site
No. tested
No. (%) positive
    Any Legionella* L. pneumophila 1 (1,2,3)**
Affected buildings (A-1 and A-2)
  Water intake valves
11
6 (55%)
0
   A-1 apartments
21
21 (100%)
18 (86%)
   A-2 apartments
21
20 (95%)
13 (62%)
   Common areas
22
12 (55%)
0
Unaffected buildings (U-1 and U-2)
  Water intake valves
8
1 (13%)
0
   U-1 apartments
7
4 (57%)
0
   U-2 apartments
7
6 (86%)
0
Fire hydrants 6 2 (33%) 0

* Any Legionella includes L. pneumophila and other undetermined species of blue-white Legionella that typically are not pathogenic.

**L. pneumophila 1 (1,2,3) denotes serogroup 1, monoclonal antibody type Knoxville (1,2,3).

 Cases occurred among residents and visitors of affected buildings A-1 and A-2 only.