Skip to main content
. 2013 Dec 25;2013:604852. doi: 10.1155/2013/604852

Table 2.

Results for optimal trigeneration system (base case) and conventional system.

System composition Conventional system Trigeneration system
Number Total power Number Total power
Gas engines 3 1739 kW
Hot water boilers 6 3420 kW 3 1710 kW
Heat exchangers 4 1600 kW
Absorption chillers 1 490 kW
Mechanical chillers 4 1960 kW 3 1470 kW
Cooling towers 3 3000 kW 3 3000 kW

Natural gas (total) MWh/yr 8703 37,324
Purchased electricity MWh/yr 3572 29
Sold electricity MWh/yr 11,389
Natural gas (cogeneration) MWh/yr 36,638
Cogenerated electricity MWh/yr 14,954
Cogenerated useful heat MWh/yr 8,602

Primary energy savings % 10.01
Equivalent electrical efficiency % 55.22

Annual fixed cost €/yr 219,650 510,830
Cost of natural gas €/yr 217,582 933,092
Cost of electricity €/yr 366,951 3207
Profit with the sale of electricity €/yr −876,960
Annual energy cost €/yr 584,534 59,339

Annual total cost €/yr 804,184 570,169