Table 4.

Calibration parameters of individual sensors. The calibration model is CO2 corrected = β0 + β1 × CO2 sensor + ε. Standard errors of coefficients are indicated in parenthesis. The determination coefficient (R2) and the standard error of estimation (SEE) are also indicated.

CO2 level β0 β1 R2 SEE (ppm)
Sensor #1 −537.4 (3.6) 0.498 (0.0006) 0.998 58.2
Sensor #2 −60.46 (3.9) 0.808 (0.001) 0.997 74.8
Sensor #3 −6.6 (4.7) 0.829 (0.001) 0.996 91.5
Sensor #4 −438.3 (4.6) 0.543 (0.001) 0.997 80.3
Sensor #5 −88.7 (5.7) 0.774 (0.002) 0.994 109.0
Sensor #6 7.2 (4.6) 0.849 (0.001) 0.996 91.0
Sensor #7 −57.2 (4.5) 0.803 (0.001) 0.996 87.5
Sensor #8 −24.5 (4.3) 0.802 (0.001) 0.997 83.3
Sensor #9 −144.9 (5.5) 0.793 (0.001) 0.995 102.3
Sensor #10 −283.9 (6.1) 0.749 (0.002) 0.994 110.5
Sensor #11 −309.0 (6.6) 0.708 (0.002) 0.993 117.1
Sensor #12 −37.0 (4.5) 0.818 (0.001) 0.996 86.6