Skip to main content
. 2015 Aug 4;10(8):e0134726. doi: 10.1371/journal.pone.0134726

Table 3. Calculated time for a 4-log reduction of five Legionella strains at five different temperatures.

Inactivation kinetics adjusted to first-order models (straight line). R2 values showed the robustness of the models.

Legionella strains Calculated time (min) to reduce 4 logs
50°C R2 55°C R2 60°C R2 65°C R2 70°C R2
L. pneumophila sg. 1 ATCC 33152 117 0.8 10 0.92 2 0.90 0.8 0.88 0.9 0.79
L. pneumophila sg. 1 env. 46 0.84 8 0.98 3 0.83 1.4 0.90 0.6 0.82
L. pneumophila sg. 7 ATCC 33823 40 0.97 25 0.96 3 0.76 0.6 0.87 1.2 0.77
L. pneumophila sg. 8 env. 68 0.97 16 0.89 4 0.94 0.8 0.90 0.7 0.99
L. longbeachae ATCC 33462 15 0.94 2 0.88 —- —- —- —- —- —-