. 2015 Oct 27;12(10):13602–13623. doi: 10.3390/ijerph121013602

Table 3.

Quality of water from samples collected from taps and storage containers when water treatment systems were fully operational and during treatment interruptions.

WTS Fully Operational Treatment Interruption *
TAPS n (%) Containers n (%) Taps n (%) Containers n (%)
Number of samples 369 77 83 13
E. coli (MPN **/100 mL)
<1 363 (98.4) 69 (89.6) 81 (97.6) 12 (92.3)
1–10 6 (1.6) 5 (6.5) 1 (1.2) 0 (0)
>10 0 (0.0) 3 (3.9) 1 (1.2) 1 (7.69)
Total Coliforms (MPN **/100 mL)
<1 344 (93.5) 53 (68.8) 70 (84.3) 9 (69.2)
1–10 16 (4.4) 10 (13.0) 6 (7.23) 1 (7.69)
>10 8 (2.1) 14 (18.2) 7 (8.43) 3 (23.8)
Number of samples 364 76 83 13
Free chlorine residual (mg/L) ††
Mean 0.13 0.11 0.02 <0.02
Median 0.02 0.02 <0.02 <0.02
Range <0.02–2.20 <0.02–2.20 <0.02–0.17 <0.02–0.04
Total chlorine residual (mg/L) ††
Mean 0.19 0.15 0.06 0.02
Median 0.07 0.04 0.04 0.02
Range <0.02–2.20 <0.02–2.20 <0.02–0.26 <0.02–0.09
Turbidity (NTU)
Mean 1.09 1.30 1.17 1.49
Median 0.71 0.62 0.74 0.74
Range 0.02–20.07 0.12–26.6 0.05–6.92 0.12–5.76

* Treatment interruption indicates periods when the mechanisms for ensuring safe water at the point of use, such the chlorine dosing mechanism, were compromised. ** Most Probable Number. During treatment interruptions, samples collected from taps were 2.66 times more likely to have one or more total coliforms MPN per 100 mL (OR: 2.7, 95% CI: 1.3–5.5) compared to tap samples collected when the MF systems were fully operational. †† Limits of detection for free and total chlorine residual were 0.02 to 2.20 mg/L.