Table II.

Parameters and Values for Energy and Cost Equations

Term Definition Value Term Definition Value
ρa Air density, kg m−3 1.225 Qtw Total flow of wall fans, m3 s−1 0
ca Specific heat of air, J kg−1 K−1 1005.4 Qtp Total flow of pit fans, m3 s−1 0.823 (0.412,1.65)
Tr, Room temperature, K Computed in Eq. 1; initial value = 293 Qapc Flow through contaminant control equipment (APC), m3 s−1 0, 0.236, 0.472, 0.944, 1.888
Tp Pit temperature, K Computed in Eq. 1; initial value = 293 rapc Fraction of air in APC that is recirculated 0, 0.25, 0.5, 0.75, 1.0
Tf Floor temperature, K 273.9 Qae Airflow exchange ratio between pit and room air, m3 s−1 0.1×Qtp
Tg Ground temperature, K 273.9 qgen Heat generation rate, W qheater + qlamps + qswine
To Outside temperature, K Eq. 3 qheater Heat generation rate from 2 heaters, W 35166, when on
Tbias Temperature bias to set median winter Temperature to test site in equation 3, K 278 qlamp Heat generation rate from heating lamps (20 125-W lamps), W 2500
Arw, Surface area of room-walls (including ceiling), m2 238.4 qswine Heat generation rate from swine, W (Eq. 4) 11,254 (sow = 181.4 kg, piglet = 5.85 kg)
Arf Surface area of floor, m2 54.6 Pelect Electricity cost, $ / kWh 0.0536
Apw Surface area of pit-walls, m2 146.464 Pgas Natural gas cost, $ / m3 0.19
Urw Heat transfer coefficient, room to wall, W m−2 K−1 0.286 Qheater Natural gas consumption of 1 heater, m3 s−1 0.000472
Urf Heat transfer coefficient, room to floor, W m−2 K−1 0.568 qfan Pit fan power consumption, W 345
Upw Heat transfer coefficient, pit to wall, W m−2 K−1 0.568 qapc APC power consumption, W Varies by APC; See Table 4
Sheater Switch function of heater, as determined by room temperature, per second 0 = off; 1 = on