Published in final edited form as: Appl Therm Eng. 2016 Apr 5;98:61–72. doi: 10.1016/j.applthermaleng.2015.11.108

Table 3.

Coefficients of determination (R2) for Q, COP, and SHR

System I System II System III System IV System V
Fault-free (Eq. 2) Q 0.996 0.990 0.999 0.993 0.994
COP 0.997 0.995 0.999 0.998 0.998
SHR 0.999 0.993 0.999 0.990 0.997
UC Fault
(Eq. 4)
Q 0.991 0.998 0.897 0.990 0.994
COP 0.988 0.995 0.998 0.987 0.993
SHR 0.886 0.846 0.830 0.859 0.889
OC Fault (Eq. 4) Q 0.994 0.963 - 0.956 0.931
COP 0.909 0.949 - 0.962 0.901
SHR 0.843 0.958 - 0.893 0.917
EA Fault (Eq. 4) Q 0.930 0.904 0.987 0.963 -
COP 0.918 0.872 0.983 0.923 -
SHR 0.901 0.809 0.998 0.956 -
CA Fault (Eq. 4) Q 0.976 0.991 0.959 0.969 0.990
COP 0.983 0.996 0.975 0.992 0.999
SHR 0.973 0.991 0.991 0.932 0.871