Table 1.

Beam Temperatures Measured by Thermocouples (TC) and Fiber Optic Sensors (DFOS-T) at Five Heat Release Rates

Temperature (°C)

Sensor location Method 25 kW 65 kW 120 kW 195 kW 350 kW
Beam #1 1 TC1 210 (1)a 405 (1) 634 (8) 927 (23) 1,016 (12)
DFOS-T 205 (4) 394 (8) 641 (17) 877 (35) 1,032 (29)
Difference (%) −2.4b −2.8 1.1 −5.7 1.6
2 TC2 197 (1) 374 (1) 611 (4) 928 (20) 998 (22)
DFOS-T 198 (4) 385 (10) 603 (14) 876 (27) 1,025 (13)
Difference (%) 0.5 2.9 −1.3 −5.9 2.6
3 TC3 180 (1) 347 (2) 557 (8) 747 (5) 1,018 (11)
DFOS-T 185 (4) 358 (6) 594 (15) 812 (17) 1,038 (23)
Difference (%) 2.7 3.1 6.2 8.0 1.9
4 TC4 190 (1) 370 (1) 631 (2) 959 (7) 1,015 (28)
DFOS-T 193 (3) 351 (7) 650 (13) 872 (18) 1,004 (25)
Difference (%) 1.6 −5.4 2.9 −10.0 −1.1
Beam #2 1 TC1 203 (2) 396 (1) 617 (2) 844 (7) 1,022 (15)
DFOS-T 197 (4) 412 (3) 631 (4) 847 (5) 1,033 (11)
Difference (%) −3.0 3.9 2.2 0.4 1.1
2 TC2 183 (1) 363 (3) 575 (6) 790 (7) 1,018 (21)
DFOS-T 174 (3) 366 (6) 593 (16) 816 (19) 1,028 (19)
Difference (%) −5.2 0.8 3.0 3.2 1.0
3 TC3 c
DFOS-T 175 (3) 360 (3) 603 (2) 828 (6) 1,027 (16)
Difference
4 TC4 175 (2) 356 (2) 597 (6) 832 (9) 1,008 (10)
DFOS-T 165 (3) 354 (3) 614 (7) 839 (7) 1,015 (14)
Difference (%) −6.1 −0.6 2.8 0.8 0.7
Beam #3 1 TC1 205 (3) 403 (3) 623 (8) 830 (8) 1,021 (24)
DFOS-T 197 (5) 399 (4) 610 (10) 822 (10) 1,030 (17)
Difference (%) −4.1 −1.0 −2.1 −1.0 0.9
2 TC2 177 (3) 351 (2) 559 (5) 779 (4) 1,013 (36)
DFOS-T 173 (4) 368 (4) 607 (6) 808 (7) 1,023 (19)
Difference (%) −2.3 4.6 7.9 3.6 1.0
3 TC3 182 (4) 358 (3) 563 (8) 759 (7) 991 (36)
DFOS-T 175 (5) 351 (6) 580 (9) 777 (12) 1,026 (26)
Difference (%) −4.0 −2.0 2.9 2.3 3.4
4 TC4 172 (3) 349 (2) 572 (5) 801 (4) 1,000 (31)
DFOS-T 162 (4) 338 (3) 586 (6) 810 (10) 1,020 (29)
Difference (%) −6.2 −3.3 2.4 1.1 2.0
a

The value in parentheses is the standard deviation.

b

Relative difference of the mean temperature of the DFOS and the TC.

c

”—” denotes a failed thermocouple.