Table 2.
Dataset of ten fault types located at distances of 3 km and 4 km from the substation.
v a | v b | v c | i a | i b | i c | cc-va | cc-vb | cc-vc | cc-ia | cc-ib | cc-ic | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AG | 1.9197 | −0.3071 | 0.1245 | 4.9815 | −0.7968 | 0.3232 | 0.5941 | −0.0950 | 0.0385 | 0.0502 | −0.0080 | 0.0033 |
0.6990 | −0.1118 | 0.0453 | 1.5998 | −0.2559 | 0.1038 | 3.5687 | −0.5708 | 0.2315 | 3.0765 | −0.4921 | 0.1996 | |
BG | 1.4521 | 0.7277 | 0.5122 | 3.7681 | 1.8884 | 1.3290 | 0.4494 | 0.2252 | 0.1585 | 0.0380 | 0.0190 | 0.0134 |
0.5287 | 0.2650 | 0.1865 | 1.2101 | 0.6064 | 0.4268 | 2.6995 | 1.3528 | 0.9521 | 2.3271 | 1.1662 | 0.8208 | |
CG | 0.4648 | 4.5783 | 3.1718 | 0.0857 | 0.8445 | 0.5851 | 0.0275 | 0.2711 | 0.1878 | 0.0237 | 0.2331 | 0.1615 |
0.0880 | 0.8668 | 0.6005 | 0.2284 | 2.2492 | 1.5582 | 0.0272 | 0.2683 | 0.1858 | 0.0023 | 0.0227 | 0.0157 | |
BCG | −8.2016 | 9.6684 | 16.2648 | −2.5267 | 2.9785 | 5.0107 | −0.1137 | 0.1340 | 0.2254 | −0.1137 | 0.1340 | 0.2254 |
−4.1309 | 4.8697 | 8.1921 | −0.7620 | 0.8983 | 1.5112 | −0.2446 | 0.2884 | 0.4852 | −0.2104 | 0.2480 | 0.4172 | |
ACG | −1.2835 | 2.5576 | 4.8025 | −0.9796 | 1.9519 | 3.6650 | −1.6907 | 3.3688 | 6.3257 | −1.4240 | 2.8375 | 5.3279 |
−1.4241 | 1.7834 | 3.8278 | −1.0868 | 1.3610 | 2.9212 | −1.8757 | 2.3491 | 5.0419 | −1.5799 | 1.9786 | 4.2466 | |
ABG | −1.1327 | 0.0679 | 2.6912 | −2.9393 | 0.1763 | 6.9832 | −0.3506 | 0.0210 | 0.8329 | −0.0296 | 0.0018 | 0.0704 |
−2.0970 | 0.1258 | 4.9821 | −1.6003 | 0.0960 | 3.8021 | −2.7621 | 0.1657 | 6.5623 | −2.3265 | 0.1395 | 5.5272 | |
AB | −7.4589 | −4.8688 | 17.7206 | −1.3759 | −0.8981 | 3.2688 | −0.4417 | −0.2883 | 1.0495 | −0.3798 | −0.2479 | 0.9024 |
−1.4121 | −0.9218 | 3.3549 | −3.6643 | −2.3918 | 8.7055 | −0.4370 | −0.2853 | 1.0383 | −0.0369 | −0.0241 | 0.0877 | |
AC | −1.0143 | −1.2113 | 7.8915 | −0.7741 | −0.9244 | 6.0225 | −1.3360 | −1.5955 | 10.3945 | −1.1253 | −1.3439 | 8.7550 |
−1.5121 | −7.9329 | 40.5259 | −0.4658 | −2.4439 | 12.4847 | −0.0210 | −0.1099 | 0.5616 | −0.0210 | −0.1099 | 0.5616 | |
BC | 2.0444 | −4.2356 | 23.5915 | 0.3771 | −0.7813 | 4.3518 | 0.1211 | −0.2508 | 1.3972 | 0.1041 | −0.2157 | 1.2013 |
0.1409 | −0.2920 | 1.6262 | 0.3225 | −0.6682 | 3.7220 | 0.7195 | −1.4907 | 8.3028 | 0.6203 | −1.2851 | 7.1576 | |
ABC | 0.3508 | −0.3674 | 1.9940 | 0.8029 | −0.8408 | 4.5638 | 1.7911 | −1.8757 | 10.1807 | 1.5440 | −1.6170 | 8.7765 |
1.7837 | −1.8679 | 10.1386 | 1.3612 | −1.4255 | 7.7374 | 2.3494 | −2.4604 | 13.3543 | 1.9788 | −2.0723 | 11.2480 |
AG, BG, and CG are single phase-to-ground faults; BCG, ACG, and ABG are double line-to-ground faults; AB, AC, and BC are line-to-line faults; ABC is three-phase faults; va, vb, vc, ia, ib, and ic are magnitudes of reflected voltages and currents, respectively; cc-va, cc-vb, cc-vc, cc-ia, cc-ib, and cc-ic are CCR between reflected signal and incident signal.