Table 2.

Test operating conditions for R134a tests with 1800 rev·min−1 compressor speed

Rating test Capacity Condenser Evaporator



kW Tsat,ave
°C
THTF,in
°C
THTF,out
°C
Tsat,ave
°C
THTF,in
°C
THTF,out
°C



Cooling A* 1.69 43.6 33.9 39.0 8.1 20.2 15.4
Cooling B 1.95 35.8 24.9 30.9 5.5 19.8 14.2
Heating H1 1.88 39.6 32.0 36.3 0.3 10.2 6.5
*

‘reference run’ for CYCLE_D-HX model