Skip to main content
. 2018 Nov 1;144:553–560. doi: 10.1016/j.watres.2018.07.070

Table 2.

COD removal rates in different components of the liquid treatment system. Data are mean ± S.D. (range).

COD removal rate
mg h−1 kg m−3GAC d−1
settling tanksa 195 ± 104 (65–489)
pre-process tank GAC 428 ± 197 (101–749) 0.64 ± 0.30 (0.15–1.12)
EC process 58 ± 217 (-340–460)b
post-process holding tank GAC 64 ± 47 (10–200) 0.10 ± 0.07 (0.01–0.30)
a

Data from steady state only (d > 14), see figure.

b

Negative values denote that measured COD increased over treatment time.