. 2018 Nov 1;18(11):3724. doi: 10.3390/s18113724

Figure 11.

Figure 11

Experimental diagram of inductive directional non-intrusive coupled cable fault diagnosis. (a) open circuit of 4.75 m; detected location is 5 m and error is 0.25 m; 167% larger than 2nd largest peaks. (b) short circuit of 4.75 m; detected location is 5 m and error is 0.25 m; 66.6% larger than 2nd largest peaks. (c) open circuit of 8.10 m; detected location is 7.91 m and error is 0.19 m; 212% larger than 2nd largest peaks. (d) short circuit of 8.10 m; detected location is 8.33 m and error is 0.23 m. 156% larger than 2nd largest peaks. (e) open circuit of 11.0 m; detected location is 11.25 m and error is 0.25 m; 357% larger than 2nd largest peaks. (f) short circuit of 11.0 m; detected location is 11.25 m and error is 0.25 m. 500% larger than 2nd largest peaks.