Table 5.

Diagnosis efficiency of the preliminary FDD and the FDD with Tc acquittal.

Type Bias The preliminary FDD The FDD with Tc acquittal
FDR (%) MDR (%) Time (s) FDR (%) MDR (%) Time (s)
Fixed bias of Tsup sensor 0.5 25.28 0.12 0.0154 1.80 1.67 0.0156
1.0 2.77 0.00 0.0153 0.00 0.00 0.0155
1.5 1.30 0.00 0.0152 0.00 0.00 0.0154

Fixed bias of Twr sensor 0.5 25.39 2.59 0.0142 0.17 2.98 0.0144
1.0 25.26 2.47 0.0146 0.22 2.47 0.0149
1.5 25.26 2.51 0.0150 0.30 2.51 0.0153

Fixed bias of Tws sensor 0.5 31.83 4.71 0.0133 7.96 4.80 0.0136
1.0 31.27 5.36 0.0133 8.74 5.36 0.0136
1.5 30.45 4.41 0.0145 7.35 4.41 0.0147

Fixed bias of Mw sensor 5% 22.19 6.96 0.0143 12.24 6.96 0.0146

Note: cases that MDR increased are marked in bold.