. 2019 Nov 27;85(24):e01942-19. doi: 10.1128/AEM.01942-19

TABLE 5.

Changes in pathogen occurrence resulting from differences between water taken from cold- and hot-water taps for each disinfectant typea

Total chlorine residual (mg/liter) Cold-water line
Hot-water line
Cold- vs hot-water line
No. (%) of samples
P/N ratio No. (%) of samples
P/N ratio Fisher exact testb P value
P N P N
Chlorine
    <0.01 19 (70) 8 (20) 2:1 36 (56) 28 (44) 1:1 NS 0.246
    0.1–0.5 9 (36) 16 (64) 1:2 5 (16) 26 (84) 1:5 NS 0.123
    0.5–1.0 9 (36) 16 (64) 1:2 2 (33) 4 (67) 1:2 NS 1
    1.0–1.5 4 (25) 12 (75) 1:3 0 (0) 1 (100) 0:1 NS 1
    >1.5 5 (42) 7 (56) 1:1 1 (33) 2 (67) 1:2 NS 1
Chloramine
    <0.01 2 (25) 6 (75) 1:3 7 (41) 10 (59) 1:2 NS 0.661
    0.1–0.5 3 (50) 3 (50) 1:1 5 (62) 3 (38) 2:1 NS 1
    0.5–1.0 8 (57) 6 (43) 1:1 9 (56) 7 (44) 1:1 NS 1
    1.0–1.5 8 (80) 2 (20) 4:1 4 (36) 7 (64) 1:2 NS 0.080
    >1.5 16 (44) 20 (56) 1:1 13 (59) 9 (41) 1:1 NS 0.417
a

P, a sample with molecular detection of one or more of the microbes measured; N, a sample with no detection of the five pathogens.

b

NS, not significant.