Skip to main content
. 2018 Nov 7;148:208–218. doi: 10.1016/j.applthermaleng.2018.11.023

Table 8.

The pollutant’s exposure level of ventilation Case #3 with FFU.

Mean SF6 concentration (ppm)
Percentage difference (%)
(Cv3-1-Cv3)/ Cv3
Ventilation
Case #3
Ventilation
Case #3 w/FFU
HCW-1 (1.4 m) 24.4 4.8 -80.3
HCW-2 (1.4 m) 21.2 8.9 -58.0
HCW-3 (1.4 m) 21.3 2.0 -90.6
Average of 1.4 m level 34.5 5.1 -85.2
Average of Room 34.8 7.1 -79.6