Volumetric flow (cubic meters per hour) and air exchange rates (air changes per hour) measured during the demonstration

Parameter BED1 BTH1 BED2 BTH2 BED3 BTH3 BED4 ISR* ISA ISB UTL ANT IWH
Surface area (m2) 25.5 6.9 29.8 5.3 25.5 6.9 25.5 18.1 5.7 6.3 15.6 11.9
Volume (m3) 69.9 16.9 81.8 13.0 69.9 16.9 69.9 49.6 15.6 15.3 47.5 32.6
Pretest ∑Supply 505 0 395 0 327 121 154 4745
∑Return 319 443 356 270 529 337 N/A
∑Exhaust 189 230 172 398
AER 7.2 11.1 5.4 17.7 5.6 10.1 3.9 10.7 21.6 26.0 3.2
Negative-pressure demonstration ∑Supply 432 0 396 0 346 135 164 3781
∑Return 343 482 386 325 563 347 N/A
∑Exhaust 161 200 159 385 2209
AER 6.2 9.5 5.9 15.4 5.7 9.4 4.6 11.4 22.2 25.2 3.5 67.7
Posttest ∑Supply 391 0 433 0 N/A 136 N/A N/A
∑Return 340 425 391 297 N/A 306 N/A
∑Exhaust 170 195 170 382
AER 5.6 10.0 5.2 15.0 6.2 10.0 4.3 N/A 19.6 25.0 N/A

AER, air exchange rate; ANT, temporary anteroom; BED1, bedroom 1; BED2, bedroom 2; BED3, bedroom 3; BED4, bedroom 4; BTH1, bathroom 1; BTH2, bathroom 2; BTH3, bathroom 3; ISA, isolation anteroom; ISB, isolation bathroom; ISR, isolation room; IWH, isolation ward hallway; N/A, not applicable; UTL, utility closet.

*

Only 2 of 3 return registers were measured; therefore, the total return and AERs listed here are underestimates of the actual rates. Estimating the AER for the ISR using the design flow rate for the unmeasured register resulted in pretest and demonstration phase AERs of 15.5 and 16.1 air changes per hour, respectively.

UTL return register could not be accessed for measurements.