Table 1.
Summary of air-exchange and outdoor air proportion measurements
Location | Volume, m3 | N∗ | Total ACH, mean ± SD | MSE† | Outdoor air proportion | Precision, %‡ | Mean outdoor ACH§ | Outdoor air, m3/h |
---|---|---|---|---|---|---|---|---|
Lung Function Laboratory | 168.5 | 3 | 8.5 ± 0.8 | 0.03 | 0.57 | 25.3 | 4.9 | 817.4 |
ED isolation room | 23.5 | 3 | 23.8 ± 1.5 | 0.16 | 1.0 | – | 23.8 | 559.7 |
Consulting room A (closed) | 31.5 | 3 | 7.0 ± 0.1 | 0.01 | 0.28 | 14.2 | 2.0 | 62 |
Consulting room A (open) | – | 3 | 13.2 ± 1.1 | 0.06 | – | – | 3.7 | 117.3 |
Consulting room B (closed) | 36.0 | 3 | 6.1 ± 0.1 | 0.01 | 0.28 | 14.2 | 1.7 | 62.1 |
Consulting room B (open) | – | 3 | 9.1 ± 1.1 | 0.02 | – | – | 2.6 | 92.6 |
Number of ventilation measurements.
Mean standard error of line fit to CO2 decays.
Precision of outdoor air proportion measurement.17
The number of outdoor ACH was equal to the measured ACH rate multiplied by the proportion of outdoor air supplied.