Table 2.
Infiltration (air leakage) data [2].
| Building component | Air leakage data | |
|---|---|---|
| Exterior wall | Lobby | Average: EqLA75 2.1 cm2/m2 |
| Typical floors | EqLA10 1.51 cm2/m2 | |
| Door | Ward entrance door | EqLA10 70 cm2/item |
| Elevator door | EqLA10 325 cm2/item | |
| Stairwell door | EqLA10 120 cm2/item | |
| Swing door located on lobby floor | 430 CMH at 50 Pa | |
| Revolving door located on lobby floor | 73 CMH at 50 Pa | |
| Etc | Top of elevator shaft | Equivalent orifice area of 1.0 m2 |
EqLA75: Equivalent leakage area at 75 Pa; EqLA10: Equivalent leakage area at 10 Pa.