Table.
Trial No. | Supply/Exhaust (Open or Sealed) | Source Contained Within Inner Zone? | Source MigrationBetween Patients? | Worker or Patient Exposure Ratio (95% CI)∗ | Comments |
---|---|---|---|---|---|
2-patient configuration | |||||
1 | Sealed/sealed | N | Y | 0.59 (0.45–0.76) | Curtain entrance closed, leak found under HEPA unit, no HEPA inlet partition |
2 | Sealed/sealed | Y | Y | 0.67 (0.44–1.06) | Curtain entrance gap maintained at 10 in (25 cm), no HEPA inlet partition |
3 | Sealed/sealed | Y | N | 0.13 (0.10–0.18) | Curtain entrance gap maintained at 10 in (25 cm), HEPA inlet partition added |
Single-patient configuration | |||||
4 | Sealed/sealed | Y | NA | 0.29 (0.19–0.46) | Increased airflow: curtain entrance gap increased to 12 in (30 cm) |
5 | Open/open | Y | NA | 0.55 (0.37–0.86) | HVAC supply reduces incoming air, curtain entrance gap maintained at 10 in (25 cm) |
6 | Sealed/open | Y | NA | 0.37 (0.28–0.48) | Room HVAC supply located outside of isolation zone was open |
7 | Open/open | Y | NA | 0.70 (0.55–0.92) | Curtain gap maintained at 10 in |
Y, Yes; N, no; CI, confidence interval; NA, not applicable.
This ratio is the mean particle count (within range of 1 to 2 μm) observed at the health care worker position divided by that observed near the source patient. It represents the relative ability of a tested scenario to reduce the risk of airborne exposure to the health care worker.