Skip to main content
. 2004 Oct 22;44(6):635–645. doi: 10.1016/j.annemergmed.2004.07.451

Table.

Data summary from 7 evaluated trials of 2-patient and single-patient isolation zones created using portable HEPA filtration equipment and common hardware supplies.

Trial No. Supply/Exhaust (Open or Sealed) Source Contained Within Inner Zone? Source MigrationBetween Patients? Worker or Patient Exposure Ratio (95% CI) Comments
2-patient configuration
1 Sealed/sealed N Y 0.59 (0.45–0.76) Curtain entrance closed, leak found under HEPA unit, no HEPA inlet partition
2 Sealed/sealed Y Y 0.67 (0.44–1.06) Curtain entrance gap maintained at 10 in (25 cm), no HEPA inlet partition
3 Sealed/sealed Y N 0.13 (0.10–0.18) Curtain entrance gap maintained at 10 in (25 cm), HEPA inlet partition added
Single-patient configuration
4 Sealed/sealed Y NA 0.29 (0.19–0.46) Increased airflow: curtain entrance gap increased to 12 in (30 cm)
5 Open/open Y NA 0.55 (0.37–0.86) HVAC supply reduces incoming air, curtain entrance gap maintained at 10 in (25 cm)
6 Sealed/open Y NA 0.37 (0.28–0.48) Room HVAC supply located outside of isolation zone was open
7 Open/open Y NA 0.70 (0.55–0.92) Curtain gap maintained at 10 in

Y, Yes; N, no; CI, confidence interval; NA, not applicable.

This ratio is the mean particle count (within range of 1 to 2 μm) observed at the health care worker position divided by that observed near the source patient. It represents the relative ability of a tested scenario to reduce the risk of airborne exposure to the health care worker.