Skip to main content
. 2013 Jul 16;66:353–363. doi: 10.1016/j.enbuild.2013.07.018

Table 3.

Description of EnergyPlus inputs.

Unit Office Serviced apartment
Internal loads Occupant 8 m2/person 42 person/floor
Lighting W/m2 15 15
Electric equipment W/m2 25 12
Operating schedule Based on the local BECa Based on the local BECa
Shading No shading device No shading device
Thermostat set point Cooling °C 24.5 24.5
Heating °C 22 22
HVAC system Air side VAV VAV
Water side Direct seawater cooled chiller; COP: 4.135; Partload performance: default curves from EnergyPlusb
Supply air temperature °C Summer: 14 Winter: 18 Summer: 14 Winter: 18
Infiltration ACH 0.1 0.1
Ventilation 0.01 m3/s/person 0.63 m3/s/floor
Exterior wall Concrete wall with gypsum Concrete wall with gypsum
Interior Wall Concrete wall with gypsum Concrete wall with gypsum
Window construction Curtain wall with double glazing Curtain wall with double glazing
Thermal zoning Core and perimeter zoning Core and perimeter zoning
a

BEC = Building energy code (EMSD) [30].

b

Seawater-cooled chiller system is not directly supported in EnergyPlus. A “DistrictCooling” object with the specified leaving temperature on condenser loop is used to simulate the effect of using seawater as a heat rejection method in this study.