Table 2.
Time (in min) to remove airborne particles based on the air changes per hour (ACH) of a room*
| Air changes per hour | Time (mins) required for removal (99% efficiency) | Time (min) required for removal (99.9% efficiency) |
|---|---|---|
| 2 | 138 | 207 |
| 4 | 69 | 104 |
| 6 | 46 | 69 |
| 8 | 35 | 52 |
| 10 | 28 | 41 |
| 12 | 23 | 35 |
| 15 | 18 | 28 |
| 20 | 14 | 21 |
| 50 | 6 | 8 |
Derived from the CDC: Guidelines for Environmental Infection Control in Health-Care Facilities (2003). Available from URL: https://www.cdc.gov/infectioncontrol/guidelines/environmental/appendix/air.html34
*Assuming airborne particles are NOT continuing to be generated (i.e., after tracheal intubation)